COMMUNICATION
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
7−3
7.3.2
Profile Log
If a computer operating in terminal mode is connected to the RS−232 port on the
PDU, press
[Esc] [P]
to print the entire Profile Log. The printout begins with the oldest
monthly entries in the queue and ends with the most recent. Statistics for the current
month and past 23 months are displayed.
7.3.3
Event History Log
If a computer operating in terminal mode is connected to the RS−232 port on the
PDU, press
[Esc] [H]
to print the entire History Log with a firmware version header.
The printout begins with the oldest alarm entry in the queue and ends with the most
recent. Any alarms that occur while the History Log is printing are included in
chronological order.
The History Log lists up to 127 system events in chronological order with the most
recent event listed last. Figure 7-2 shows a sample History Log printout.
In this mode, system events are continually logged through the serial port to the
device connected to the port.
The printed log entries contain a time and date stamp and the alarm text message.
Terminal mode uses the following format for printing alarm entries:
MM DD YYYY HH:MM:SS.hhh KYWD MESSAGE <CR> <LF
>
Where
Equals
MM
Month (2 digits)
DD
Day (2 digits)
YYYY
Year (4 digits)
HH
Hour (2 digits)
MM
Minute (2 digits)
SS
Second (2 digits)
hhh
Hundredths of Second (3 digits)
KYWD
Keyword (ALARM, NOTICE, COMMAND, or STATUS)
Message
System Diagnostic Information
<CR>
Carriage Return Character (ASCII 13)
<LF>
Line Feed (ASCII 10)
An alarm that clears is prefixed by the word CLEAR" in the history log.