IO2—1 x AI, 2 x AO Option Card
PowerXL DG1 Series Option Cards
MN040007EN—April 2014 www.eaton.com
19
IO2 Board Parameters
Parameters are all listed in the Optional board menu for this
card.
Figure 15. IO2 Parameter Structure
Table 13. IO2 Board Parameters
Monitor Menu—BX.1
Code
Parameter
Min.
Max.
Default
Unit
ID (Slot A / Slot B)
Description
R / RW
BX.1.1
AI1 Value
894 / 920
Analog Input Status
R
BX.1.2
AO1 Value
897 / 922
Analog Output Status
R
BX.1.3
AO2 Value
899 / 924
Analog Output Status
R
Parameter Menu—BX.2
Code
Parameter
Min.
Max.
Default
Unit
ID (Slot A / Slot B)
Description
R / RW
BX.2.1
AI1 Mode
0
2
0
893 / 919
Analog input 1 Mode
0: 0 to 20 mA
1: 0 to 10V
2: –10V to +10V
RW
BX.2.2
AI1 Range
0
2
0
124 / 129
Analog input 1 signal range
0: 0 to 100%
1: 20 to 100%
2: Customized
RW
BX.2.3
AI1 Custom Min
0
100
0
%
125 / 130
Analog input 1 custom minimum range
RW
BX.2.4
AI1 Custom Max
0
100
100
126 / 131
Analog input 1 custom maximum range
RW
BX.2.5
AI1 Filter Time
0
10
0.1
s
123 / 128
Analog input 1 filter time
RW
BX.2.6
AI1 Invert
0
1
0
127 / 132
Analog input 1 signal inversion
0: Not Inverted
1: Inverted
RW
BX.2.7
AO1 Mode
0
1
0
896 / 922
Analog output mode
0: 0 to 20 mA
1: 0 to 10V
RW
BX.2.8
AO1 Function
0
235 / 275
Analog output 1 function
RW
BX.2.9
AO1 Min
0
1
0
238 / 276
Analog output minimum value
0: 0V / 0 mA
1: 2V / 4 mA default 0V / 0 mA
RW
BX.2.10
AO1 Filter Time
0
10
1
s
236 / 277
Analog output filter time range
RW
BX.2.11
AO1 Scale
0
100
100
%
239 / 278
Analog output 1 scale
RW