DG1 Series Overview

PowerXL DG1 Series Option Cards

MN040007EN—April 2014 www.eaton.com

5

Ambient conditions

Ambient operating temperature

–10°C (no frost) to +50°C, up to +60°C with derating (CT)
–10°C (no frost) to +40°C, up to +55°C with derating (VT)

Storage temperature

–40°C to +70°C

Relative humidity

0–95% RH, noncondensing, non-corrosive

Air quality:

Chemical vapors

Mechanical particles

Tested according to IEC 60068-2-60 Test Key:

  Flowing mixed gas corrosion test, Method 1 (H2S [hydrogen sulfide] and SO2 [sulfur dioxide])

Designed according to:

  IEC 60721-3-3, unit in operation, class 3C2
  IEC 60721-3-3, unit in operation, class 3S2

Altitude

100% load capacity (no derating) up to 3280 ft (1000m); 1% derating for each 328 ft (100m) above 
3280 ft (1000m); max. 9842 ft (3000m) (2000m for corner grounded earth main systems)

Vibration:

EN 61800-5-1

EN 60668-2-6

5–150 Hz
Displacement amplitude: 1 mm (peak) at 5 Hz to 15.8 Hz (FR1–FR5)
Maximum acceleration amplitude: 1g at 15.8 Hz to 150 Hz (FR1–FR5)

Shock:

ISTA 1 A

EN 60068-2-27

Storage and shipping: maximum 15g, 11 ms (in package)

Overvoltage

Overvoltage Category III

Pollution degree

Pollution Degree 2

Enclosure class

IP21/Type 1 standard in entire kW/hp range
IP54/Type 12 option
Note: Keypad required to be mounted in drive for IP54/Type 12 rating

Immunity

Fulfills EN 61800-3 (2004), first and second environment

MTBF

FR1: 165,457 hours
FR2: 134,833 hours
FR3: 102,515 hours
FR4: 121,567 hours
FR5: 108,189 hours
FR6: Available in 2015

Standards 

Safety

UL 508C, CSA C22.2 No. 274-13 and EN 61800-5-1

EMC

+EMC2: EN 61800-3 (2004), Category C2
The drive can be modified for IT networks and corner grounding TN system

Electrostatic discharge

Second environment, IEC 61000-4-2, 4 kV CD or 8 kV AD, Criterion B

Fast transient burst

Second environment, IEC 61000-4-4, 2 kV/5 kHz, Criterion B

Dielectrical strength

Primary to secondary: 3600 Vac/5100 Vdc
Primary to earth: 2000 Vac/2828 Vdc

Approvals

EN 61800-5-1 (2007), CE, UL and cUL (see nameplate for more detailed approvals)

Fieldbus connections

Onboard: EtherNet/IP, Modbus

®

 TCP, Modbus RTU, BACnet

Table 2. PowerXL Series—DG1, continued

Attribute

Description

Specification

Содержание Power XL DG1 Series

Страница 1: ...PowerXL DG1 Series Option Cards User Manual Effective April 2014 New Information...

Страница 2: ......

Страница 3: ...E OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT...

Страница 4: ...to find product information You can also find information on local distributors or Eaton s sales offices Website Address www eaton com drives EatonCare Customer Support Center Call the EatonCare Supp...

Страница 5: ...Rating Label 2 Carton Labels U S and Europe 2 Option Card Slots 3 Option Board Summary 3 Option Card Introduction 9 IO1 3 X DI 3 X DO 1 X THERMISTOR 24 VDC EXT OPTION CARD Description 10 Digital Input...

Страница 6: ...ding 9 Figure 8 IO1 Board Layout 11 Figure 9 IO1 Board Wire Layout 12 Figure 10 Digital Input Signal Programming 13 Figure 11 Digital Output Signal Programming 14 Figure 12 Thermistor Parameter Settin...

Страница 7: ...24V Rating 10 Table 8 IO1 Control Terminals 12 Table 9 Thermistor Input Configuration 15 Table 10 IO1 Board Parameters 16 Table 11 IO2 Analog Ratings 17 Table 12 IO2 Board Terminals 18 Table 13 IO2 B...

Страница 8: ...art of programs interrupted after a voltage DIP or failure This should not cause dangerous operating states even for a short time If necessary emergency stop devices should be implemented Wherever fau...

Страница 9: ...ng maintenance Be sure equipment is properly earthed Wear safety glasses whenever working on electronic controllers or rotating machinery WARNING The components in the drive s power section remain ene...

Страница 10: ...the capacitors have fully discharged by measuring their voltage using a multimeter set to measure the DC voltage Failure to follow these precautions may cause death or severe injury WARNING The openin...

Страница 11: ...protective earthing conductor must be connected or the cross section of the equipment grounding conductor must be at least 10 mm2 Cu Drive requires that only copper conductor should be used CAUTION De...

Страница 12: ...malfunction and potential damage CAUTION Make sure that the drive output terminals U V W are not connected to the utility line power as severe damage to the drive may occur CAUTION When the control te...

Страница 13: ...40016EN Quick Start Guide MN040006EN User Manual CD CD040002EN and accessory packet The accessory packet includes Rubber grommets Control cable grounding clamps Additional grounding screw Inspect the...

Страница 14: ...Series Option Cards MN040007EN April 2014 www eaton com Rating Label Figure 2 Rating Label Carton Labels U S and Europe Same as rating label shown above Contains SN PN Type Date Contains EAN Code Date...

Страница 15: ...mary There are a total of five I O option cards available on the DG1 that can be placed in either Slot A or B IO1 3 DI 3 DO 1 thermistor 24 Vdc EXT IO2 1 AI 2 AO isolated to control board IO3 3 Relay...

Страница 16: ...overload 1 5 x IH 1 min 10 min Overload current 150 respectively 110 1 min 10 min Initial output current 200 2s 20s Output frequency 0 400 Hz standard Frequency resolution 0 01 Hz Control characteris...

Страница 17: ...R1 FR5 Shock ISTA 1 A EN 60068 2 27 Storage and shipping maximum 15g 11 ms in package Overvoltage Overvoltage Category III Pollution degree Pollution Degree 2 Enclosure class IP21 Type 1 standard in e...

Страница 18: ...r detailed information see the description of the board of interest Analog Outputs mA V Most of the expander boards with analog output can be configured for a current for a current or voltage output w...

Страница 19: ...ost Requirements for an external 24V power supply Output voltage 24 Vdc 10 max ripple voltage 100 mV rms Maximum current 1A 1A external fuse no internal short circuit protection is provided on the bas...

Страница 20: ...ol power is applied to the PowerXL Drive Verify the board fits tightly in the metal clamp and plastic groove If the board seems to be difficult to install in the slot you should confirm that you are u...

Страница 21: ...are connected to PowerXL DG1 control board in two slots For I O cards various inputs and outputs can be used for control algorithms Outputs also can be used for status of the motor Table 5 I O Card I...

Страница 22: ...30 Vdc Steady state current 5 mA Off state voltage 0 to 10 Vdc Input impedance 5k ohm Input logic Positive logic and negative logic Isolation voltage 500 Vdc Digital Outputs Specification Value Output...

Страница 23: ...IO1 3 x DI 3 x DO 1 x Thermistor 24 Vdc EXT Option Card PowerXL DG1 Series Option Cards MN040007EN April 2014 www eaton com 11 Figure 8 IO1 Board Layout...

Страница 24: ...nction is turned on TI1 is combined with DIN2 and TI1 is combined with DIN3 4 Total combined load on available 24 Vdc out terminals for all optional cards must not exceed 250 mA The maximum load on th...

Страница 25: ...PowerXL DG1 drive To configure these inputs the standard Digital inputs menu will allow for selecting its function DigIN X indicates one of the onboard inputs The option DigIN X IO1 Y will select one...

Страница 26: ...14 www eaton com Digital Outputs The 3 digital output functions can be configured to various functions in the PowerXL DG1 drive To configure these inputs there are parameters in the option card menu f...

Страница 27: ...ril 2014 www eaton com 15 Thermistor Input The signal thermistor input needs to be configured before use It will switch states at 4 7 k ohm Table 9 Thermistor Input Configuration Figure 12 Thermistor...

Страница 28: ...O2 DO3 888 914 Digital Output Status R BX 1 3 Thermistor State 887 913 Thermistor configure R BX 1 4 Thermistor Resistor 891 917 Thermistor resistance value R Parameter Menu BX 2 Code Parameter Min Ma...

Страница 29: ...ut type Single end Single end Input range 10 Vdc 0 4 20 mA Input impedance 200k ohm 250 ohm Resolution 10 bits 0 1 10 bits 0 1 Accuracy 1 of full display 1 of full display Maximum permanent allowed ov...

Страница 30: ...nal Technical 1 FE Connect cable shield 2 AO2 Current 0 4 20 mA RL max 500 ohms 3 AO2 Voltage 0 10V RL 1k ohm default setting 4 AO1 Current 0 4 20 mA RL max 500 ohms 5 AO1 Voltage 0 10V RL 1k ohm defa...

Страница 31: ...0 to 20 mA 1 0 to 10V 2 10V to 10V RW BX 2 2 AI1 Range 0 2 0 124 129 Analog input 1 signal range 0 0 to 100 1 20 to 100 2 Customized RW BX 2 3 AI1 Custom Min 0 100 0 125 130 Analog input 1 custom min...

Страница 32: ...1 0 898 924 Analog output mode 0 0 to 20 mA 1 0 to 10V RW BX 2 15 AO2 Function 0 269 281 Analog output function RW BX 2 16 AO2 Min 0 1 0 270 282 Analog output minimum value 0 0V 0 mA 1 2V 4 mA RW BX 2...

Страница 33: ...acts and 1 form C dry relay The relay functions can be selected via parameters based off of various drive monitoring values Table 14 IO3 Board Rating Figure 16 IO3 Board Layout Specification Value Num...

Страница 34: ...7 COM1 6 NO2 5 Terminal Signal Technical 1 NC3 RO3 common Switching capacity 24 Vdc 8A 250 Vac 8A 125 Vdc 0 4A Min switching load 5V 10 mA 2 COM3 3 NO3 RO3 normal close Switching capacity 24 Vdc 8A 2...

Страница 35: ...the value shown Monitor Menu BX 1 Code Parameter Min Max Default Unit ID Slot A Slot B Description R RW BX 1 1 Relay Outputs Status 900 926 Relay output status indicator R Parameter Menu BX 2 Code Par...

Страница 36: ...e designed to sense temperature from 30 C to 200 C warning for PT100 sensor open or short These sensors are used to fault the drive at a user set temperature level Table 17 IO4 Thermistor Ohm Values T...

Страница 37: ...ire Layout Table 19 IO4 Terminal Layout RM2 6 R2 5 RM3 3 R3 4 R3 2 FE 1 IO4 Board R2 7 R1 10 RM1 9 R1 8 PT100 PT100 Terminal Signal Technical 1 FE Connect cable shield 2 R3 PT100 Input 30 C to 200 C A...

Страница 38: ...tatus R BX 1 2 PT100 Values 902 928 PT100 Temperature values R Parameter Menu BX 2 Code Parameter Min Max Default Unit ID Slot A Slot B Description R RW BX 2 1 PT100 3 2 1 0 7 0 901 927 Active PT100 i...

Страница 39: ...r 240 Vac These inputs can be configured to various functions Table 21 IO5 Rating Figure 22 IO5 Board Layout Specification Value Input points 6 points 2 common lines Rated input voltage 240 Vac curren...

Страница 40: ...Figure 24 IO5 Parameter Structure Terminal Signal Technical 1 CMB For digital input 4 5 6 2 DIN6 Digital input 240 Vac 50 Hz 60 Hz Control voltage 0 40 Vac 1 79 Vac 3 DIN5 4 DIN4 5 CMA For digital inp...

Страница 41: ...in the drive application under the digital input selections Depending on which slot is used the function will be set up with DigIN X IO5 Y X being the slot the board is placed in and Y being the inpu...

Страница 42: ...IO5 6 x DI 240 Vac input Option Card 30 PowerXL DG1 Series Option Cards MN040007EN April 2014 www eaton com...

Страница 43: ......

Страница 44: ...grated solutions to solve our customers most critical challenges Our focus is on delivering the right solution for the application But decision makers demand more than just innovative products They tu...

Отзывы: