2
Operation
Instruction manual
IM1002004E September 2015 www.powerquality.eaton.com
Operation
The Power-Sure 700 is operated by simply turning on the
main AC input circuit breaker. All units 50 kVA and larger are
equipped with a bypass switch as a standard feature. For
units 45 kVA and smaller, the bypass switch is optional. This
is a no load switch and MUST only be operated when the
unit is OFF. The bypass switch should be in the “NORMAL”
position unless a problem occurs with the system. If a
problem occurs, turn OFF the main AC circuit breaker
and turn the bypass switch to the “BYPASS” position.
Re-energize the system by turning on the AC circuit breaker
and contact the Customer Support Department for repairs.
Any “ALERT” condition requires the main AC input breaker
to be turned off in order to reset the “ALERT” light.
FOR ASSISTANCE, CALL 1-800-809-2772, option 4, and
then option 2.
Benefi ts of owning and using the
Power-Sure 700
●
●
Line harmonic filtering
●
●
Small physical size
●
●
Simple and inexpensive installation
●
●
Highly efficient
●
●
Quiet operation
●
●
Low BTU output
●
●
Low failure rate
●
●
Seven-tap, microprocessor control and diagnostics
●
●
UL
®
Listed to 1012 standards
●
●
Priced to be affordable
●
●
Conservatively rated
●
●
Extremely high surge capability
●
●
Simple operation
●
●
Input electronic circuit breakers
●
●
Nationwide customer support service
Specifi cations
●
●
Dynamic electrical specifications
●
●
Output: maintained to within ±3% of nominal
a
●
●
Input: +10% to –23% of the nominal rated input
ab
●
●
Frequency: 60 Hz ±3 Hz
a
●
●
Input power factor: >0.99 PF with resistive load
●
●
Line regulation: output is ±3% of nominal for input
variations of +10% to –23% of nominal
●
●
Load regulation: output maintained within 3% from no
load to full load
●
●
Response time: <1/2 cycle
●
●
Correction time: output will correct to within ±3% of
nominal in 1.5 cycles or less
●
●
Harmonic distortion: Less than 1.0% THD added to
the output waveform under any dynamic linear loading
conditions presented to the line regulator
●
●
Transverse-mode noise attenuation: 3 dB down at 1000 Hz,
40 dB/decade to below 50 dB with resistive load
●
●
Common-mode noise attenuation: 146 dB
●
●
Audible noise: 45 dB or less
●
●
Turn on characteristics: when energized, voltage
overshoot will be less than 5% of nominal for 1 cycle
or less
●
●
Overload rating: 1000% for 1 cycle and 200% for
10 seconds
●
●
Ambient rating: –10º to +40º Celsius
●
●
Integral manual rotary maintenance bypass switch
standard on 50 to 500 kVA units and optional on
smaller units
otes:
N
50 Hz models available.
Figure 1. Regulation graphs
a
Optional extended input regulation range provided on some units.
If provided, reference the description next to the units specification tag.
b
Between 160 V and 229 V at 208 V nominal. Between 369 V and 528 V
at 480 V nominal.