37

Bypass mode

Instruction manual

   IM1002004E   September 2015   www.powerquality.eaton.com

Bypass mode

With the switch in the bypass position, the Power-Sure 700 

will provide clean power to the critical loads. In the bypass 

position, the unit will not regulate the incoming voltage. The 

transformer and suppression circuitry remains in the circuit 

when in the bypass mode. The Power-Sure 700 should be 

placed in the bypass position when a failure of the system 

has occurred. This provides the user with some protection 

until a service technician arrives.

 CAUTION 

Prior to switching from one position to another, turn off the 

AC input breaker. Some systems are equipped with push-

to-turn switches. With these switches, the switch will shunt 

trip the input breaker when pressed in.

Standard monitoring

Overtemp sensing devices are mounted at critical points on 

the SCR regulating assembly and the main transformer. If 

an overtemp condition exists, the unit will electronically shut 

off; however, the cooling fans will continue to operate. The 

“ALERT” light will illuminate and hold until the overtemp is 

corrected. The main AC input breaker must be turned off in 

order to reset the “ALERT” light.

Alert light

—An indicator light indicates if the output has 

been disabled by one of the following conditions:
(1) Transformer over-temperature
(2) SCR thermal over-temperature

Indicating lamps

—Output ON indicating lamps are 

provided for each phase.

Metering option

The Power-Sure 700 offers two metering options. The IQ 130 

meter is the standard option on the Power-Sure 700. The 

IQ 130 has programmable voltage, current transformer 

ratios, and true rms indication for accurate measurement 

of distorted waveforms, which can be viewed through 

four screens via a high visibility LED display. Installation 

and operation instructions for this meter can be found in 

Instructional Leaflet IL02601002E. The premium metering 

option is the IQ 150—which offers all the features of the 

IQ 130, along with energy, power, communications ability, 

and many other enhanced features. Please refer to Technical 

Data TD02601025E for additional information.

Warranty

Eaton warrants the Power-Sure 700 to be free from defects 

in material and workmanship for a period of one year from 

the shipment date. The warranty includes parts only during  

this time.
These units are sold in accordance to Eaton Selling  

Policy 25-000.

Содержание Power-Sure 700

Страница 1: ...Instruction manual Effective September 2015 Supersedes September 2013 Power Sure 700...

Страница 2: ...FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF...

Страница 3: ...allation 5 Unpacking 5 Storing 5 Choice of location 5 Inspection 5 Installation procedure 5 Input wire size grounding and output wiring 5 Startup sequence 7 Preventive maintenance 7 General troublesho...

Страница 4: ...iv Power Sure 700 Instruction manual IM1002004E September 2015 www powerquality eaton com...

Страница 5: ...thermal sensors are strategically located at critical points on the regulator assemblies and transformer The main AC input circuit breaker must be turned off in order to reset the ALERT light Protecti...

Страница 6: ...ion Input electronic circuit breakers Nationwide customer support service Specifications Dynamic electrical specifications Output maintained to within 3 of nominal a Input 10 to 23 of the nominal rate...

Страница 7: ...e system The power transformer is manufactured with a unique method of shielding which produces very low capacitive coupling between the primary and secondary This low coupling provides excellent atte...

Страница 8: ...40 1955 8 x 1839 0 x 1229 4 Frequency 6 60 Hz 5 50 Hz Nominal output voltage Wye output L L L N G L 120 208 M 230 400 N 277 480 P 347 600 A Units with no surge protection option bypass option or meter...

Страница 9: ...learance to allow a free flow of air Allow at least 4 00 inches 101 6 mm of space between the unit and the wall or other equipment Allow enough space for maintenance on all four sides of larger units...

Страница 10: ...100 350 500 3 125 400 3 0 a 3 150 500 250 kcmil a 2 225 800 500 kcmil a 1 0 300 1000 500 kcmil b 2 0 500 1600 500 kcmil c 4 0 a 2 pcs b 3 pcs c 4 pcs d 5 pcs Note N Refer to NEC for output wire size...

Страница 11: ...horted mode When this happens normally the fusible link in series with the SCR will be blown open to clear the short and prevent damage to the transformers The individual SCR can be checked with an oh...

Страница 12: ...ce checks are not interfered by fan motor coils Also remove main semi conductor fuse located on all three SCR assemblies and any wires attached to the fuse Each power module contains two inverse paral...

Страница 13: ...on the card 3 Turn on AC input breaker to unit IMPORTANT Extreme caution must be taken when measuring voltages on Molex connectors Do not press meter leads into connectors or bend connectors back 4 Me...

Страница 14: ...this adjustment on phase 1 you may see the output voltage change from line to neutral on two phases It is best to use procedures in Steps 1 9 adjusting Final testing and adjustment 1 Connect AC voltm...

Страница 15: ...ment Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 4 Unit component location diagram 10 15 kVA 60 Hz all input voltages 10 15 kVA 50 Hz all input voltages and 25 30 kV...

Страница 16: ...12 Final testing and adjustment Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 5 Unit component location diagram 45 150 kVA 60 Hz 30 100 kVA 50 Hz...

Страница 17: ...13 Final testing and adjustment Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 6 Power Sure 700 50K component location...

Страница 18: ...14 Final testing and adjustment Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 7 Power Sure 700 75 150K component location...

Страница 19: ...iagram 225 300 kVA 50 60 Hz all voltages Left Side View Front View Right Side View Rear View Output Terminals Cabinet Cooling Fan Heatsink Assembly With Snubber Card Heatsink Assembly Cooling Fan Powe...

Страница 20: ...16 Final testing and adjustment Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 9 Unit component location diagram 500 kVA 50 Hz and 60 Hz all voltages...

Страница 21: ...ent Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 10 10 30 kVA heat sink layout a a Heat sink layout does not necessarily follow kVA size shown Input voltage is also a...

Страница 22: ...ent Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 11 45 150 kVA heat sink layout a a Heat sink layout does not necessarily follow kVA size shown Input voltage is also...

Страница 23: ...nt Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 12 225 300 kVA heat sink layout a a Heat sink layout does not necessarily follow kVA size shown Input voltage is also...

Страница 24: ...ment Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 13 500 kVA heat sink layout a a Heat sink layout does not necessarily follow kVA size shown Input voltage is also a...

Страница 25: ...21 Final testing and adjustment Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 14 Control board 49120 407415...

Страница 26: ...y Parts kits Table 5 50 and 60 Hz all voltages kVA size Kit price U S funds 10 kVA Consult factory 15 kVA Consult factory 25 50 kVA Consult factory 75 kVA Consult factory 100 125 kVA Consult factory 1...

Страница 27: ...23 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Technical diagrams Figure 15 Generic circuit diagram primary SCR no bypass...

Страница 28: ...24 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 16 Generic circuit diagram primary SCR with bypass...

Страница 29: ...25 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 17 Generic circuit diagram secondary SCR no bypass...

Страница 30: ...26 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 18 Generic circuit diagram secondary SCR with bypass...

Страница 31: ...27 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 19 Installation diagram Power Sure 700 10 15 kVA with optional bypass...

Страница 32: ...28 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 20 Installation diagram Power Sure 700 10 30 kVA with optional meter and bypass...

Страница 33: ...29 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 21 Installation diagram Power Sure 700 45K with optional meter and bypass...

Страница 34: ...30 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 22 Installation diagram Power Sure 700 50K with bypass and optional meter...

Страница 35: ...31 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 23 Installation diagram Power Sure 700 50K with bypass and optional meter top and bottom view...

Страница 36: ...32 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 24 Installation diagram Power Sure 700 75 150K with bypass and optional meter...

Страница 37: ...33 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 25 Installation diagram Power Sure 700 75 150K with bypass and optional meter top and bottom view...

Страница 38: ...34 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 26 Installation diagram Power Sure 700 225 300K with bypass and optional meter...

Страница 39: ...35 Technical diagrams Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 27 Installation diagram Power Sure 700 500K with bypass and optional meter...

Страница 40: ...25 Yes Yes 76 0 x 34 4 x 35 5 14 748 2 137 150 Yes Yes 76 0 x 34 4 x 35 5 17 698 2 240 225 Yes Yes 77 4 x 56 0 x 41 5 23 000 3 300 300 Yes Yes 77 4 x 56 0 x 41 5 30 750 4 000 500 Yes Yes 77 0 x 72 4 x...

Страница 41: ...emp is corrected The main AC input breaker must be turned off in order to reset the ALERT light Alert light An indicator light indicates if the output has been disabled by one of the following conditi...

Страница 42: ...38 Warranty Instruction manual IM1002004E September 2015 www powerquality eaton com Figure 28 Performance Checklist...

Страница 43: ...39 Instruction manual IM01002002E September 2015 www eaton com...

Страница 44: ...a world that demands more With over 100 years experience in electrical power management we have the expertise to see beyond today From ground breaking products to turnkey design and engineering servi...

Отзывы: