Chapter 6 — Communication Board Fault Tracking
The table below presents the faults related to the Siemens FLN (P1) option board. For more
fault code information, see also
HVX9000 User Manual
,
Fault Tracking Section.
Table 6-1: Communication Board Faults
You can define with parameters how the AFD shall react to certain faults:
Table 6-2: AFD Response to Faults
Fault
Code
Fault
Possible cause
Possible solutions
37
Device change
Option board changed
Reset
38
Device added
Option board added
Reset
39
Device removed
Option board removed
Reset
40
Device unknown
Unknown option board
Check the installation.
If installation is correct contact the
nearest Eaton distributor.
53
Communication
bus fault
The data connection between the
communication bus master and the
communication bus board has
failed.
Check the installation.
If installation is correct contact the
nearest Eaton distributor.
54
Slot fault
Defective option board or slot
Check that the board is properly
installed and seated in slot. If
installation is correct, contact the
nearest Eaton distributor.
Code
Parameter
Min.
Max
Unit
Step
Default
Note
P1.7.22
Response to
fieldbus fault
0
3
1
2
0=No response
1=Warning
2=Fault, stop acc. to 2.4.7
3=Fault, stop by coasting
P1.7.23
Response to slot
fault
0
3
1
2
0=No response
1=Warning
2=Fault, stop acc. to 2.4.7
3=Fault, stop by coasting