LonWorks Option Board User Manual
6-6
For more information visit:
www.eatonelectrical.com
MN04003008E
April 2004
Output Network Variables
Table 6-6: Output Network Variables
NvoStatus
This output network variable reports the status for Node object or Adjustable Frequency
Motor Drive object.
Table 6-7: Object Status Variable Parameters
nvoDrvSpeed
This output network variable provides the speed of the drive as a percentage of the nominal
speed.
nvoDrvCurnt
This output network variable provides the drive output current in amperes.
nvoDrvPwr
This output network variable provides the drive output power in kW.
Function
Variable Name
SNVT Type
Min. Value
Max. Value
Node Object status
nvoStatus
SNVT_obj_status
Drive speed feedback
nvoDrvSpeed
SNVT_lev_percent
-163.840%
+163.830%
Actual motor current
nvoDrvCurnt
SNVT_amp
0.0A
3276.7A
Actual drive power
nvoDrvPwr
SNVT_power_kilo
0.0 kW
6553.5 kW
Drive total running hours nvoDrvRunHours
SNVT_time_hour
0 h
65535
Status word
nvoDrvStatus
SNVT_state
n/a
n/a
kWh trip counter
nvoDrvEnrgy
SNVT_elect_kwh
0 kWh
65535 kWh
Active fault code
nvoActFault
SNVT_count
0
41
Process Out
nvoProcessOut1-8
SNVT_lev_percent
0
65535
Digital Out
nvoDigitalOut1-8
SNVT_switch
0
4
Parameter Out
nvoParResp
SNVT_preset
—
—
Field
Description
object_id
ID of object within node
invalid_id
1 means requested ID is not implemented in
this node
invalid_request
1 means request for unimplemented function
disabled
1 means object disabled
electrical_fault
1 means drive is faulted
in_alarm
1 means drive is in alarm
report_mask
1 means status is an event mask