LonWorks Option Board User Manual
MN04003008E
For more information visit:
www.eatonelectrical.com
5-1
April 2004
Chapter 5 — Start-Up
First read the Start-Up chapter in your
9000X AF Drive User Manual
.
Fieldbus Board Parameters
The LonWorks board is commissioned with the control keypad by giving values to
appropriate parameters in menu M6 (for locating the expander board menu, see the
9000X AF Drive User Manual
).
Expander Board Menu (M6)
The Expander board menu makes it possible for the user 1) to see what expander boards are
connected to the control board and 2) to reach and edit the parameters associated with the
expander board.
Enter the following menu level (
G#
) with the menu button right. At this level, you can browse
through slots A to E with the browser buttons to see what expander boards are connected.
On the lowermost line of the display, you also see the number of parameter groups
associated with the board.
If you still press the menu button right once, you will reach the parameter group level
including one parameter (Service pin).
LonWorks Parameters
To commission the LonWorks board, enter the parameter G6.5.1.1 from the Parameters
group (G6.5.1). Give the desired value to the LonWorks parameter.
Table 5-1: LonWorks Parameters
Figure 5-1: Changing the Parameter Value
#
Name
Default
Range
Description
1
Service Pin
0
0 – 1
Broadcasts a service pin message to the network.
OPTC5
Parameters
Expander Board
G1 G5
G1 G2
P1 P4
M6
Service Pin
Change Value to 1 and
Confirm Change
0
G6.5.1.1
G6.5
Service Pin
1
G6.5.1.1
G6.5.1