Interlocked pop-out mechanical trip indicator
An interlocked, red mechanical trip indicator is an optional
feature. It is located in the front of the breaker near the top
and to the right of the trip unit (Figure 5). It operates by
releasing and popping out any time the circuit breaker trips
due to an overcurrent condition.
ote:
N
The interlocked mechanical trip indicator will prevent
the breaker from being reclosed until the red, pop-
out indicator is reset or pushed back in.
The indicator is reset manually by pushing it back in, or
remotely with the available accessory. If the interlocked
indicator is not reset, the circuit breaker will not close until
the indicator is pushed back in.
An overcurrent trip switch (bell alarm), discussed later in this
section, that operates off the position of the mechanical trip
indicator is also available.
Operations counter
The operations counter is a mechanical device used to indi-
cate a record of the number of circuit operations. It can be
viewed through the breaker’s front cover (Figure 5).
Off key lock
The off key lock secures the circuit breaker in the OFF
position. It can be viewed through the front cover (Figure
6). The customer supplies the key lock. The provisions are
available for Kirk, Castell, Ronis, and CES.
Pushbutton cover
Padlockable covers are available to limit access to the ON
and OFF pushbuttons.
Safe-off pushbutton cover
When padlocked, it maintains the OFF button in the actu-
ated position, which prevents closure of the breaker.
Cassette safety shutters
Automatically operated insulating type safety shutters
(Figure 3) are available for use with the drawout cassette to
cover the fixed primary contacts when the circuit breaker is
not in the CONNECT position. The shutters are activated by
barriers which must be installed on the rear of the drawout
breaker.
Door escutcheon
The door escutcheon is a molded frame used to seal the
space between the circuit breaker and the compartment
door cutout. It is supplied with a mounting gasket. Refer to
IL01301012E for installation information.
IP55 dust and water resistant cover
A hinged dome-shaped waterproof cover attaches to the
metal compartment door to provide protection for the circuit
breaker.
Mechanical interlock
Mechanical interlocks are available to interlock the operation
of two or three Series NRX circuit breakers. The mechanical
interlock holds one or more circuit breakers tripped (pre-
vents closure) when others are closed. Consult Eaton for
details.
Publications
Table 5. Series NRX publications.
Description
Publication
number
Frame
PXR 20/25 Trip Unit for Series NRX User Manual
MN013003EN NF and RF
PXR 20/25 Trip Unit for Series NRX Screen
Navigation Guide
IL0131128EN NF and RF
Series NRX with PXR Circuit Breaker Wiring
Diagrams
TD013001EN
NF and RF
Series NRX NF & RF Circuit Breakers with PXR
20/25 Trip Units - Time Current Curves
AD013001EN NF and RF
Series NRX - Installation Instructions for Fixed
and Drawout Breaker Door Escutcheon
IL01301012E
NF and RF
Series NRX Drawout Circuit Breaker and Cassette
Rejection Interlocks
IL01301006E
NF and RF
Series NRX - Installation Instructions for IP55 Dust
And Water-Resistant Cover
IL01301038E
NF and RF
Series NRX with PXR - Instructions for Auxiliary
Switch
IL0131096EN NF and RF
Series NRX with PXR - Instructions for
Undervoltage Release, Shunt Trip, and Overcurrent
Trip Switch
IL0131087EN NF and RF
Series NRX with PXR - Instructions for Spring
Release, Latch Check Switch, and motor Operator
IL0131088EN NF and RF
Series NRX with PXR - Instructions for Secondary
Terminal Blocks
IL0131093EN NF and RF
Series NRX with PXR - Instructions for Source
Ground and Zero Sequence Ground Sensor
IL0131089EN NF and RF
Series NRX with PXR - Installation Instructions for
Ethernet Communications Adapter Module
IL0131125EN NF and RF
Series NRX with PXR - Instructions for PROFIBUS
DP Communications Adaptor Module (PCAM)
IL0131092EN NF and RF
Series NRX with PXR – Instructions for Modbus
Communications Adapter Module (MCAM)
IL0131091EN NF and RF
Series NRX with PXR – Instructions for INCOM
Communications Adapter Module
IL0131124EN NF and RF
Series NRX with PXR - Instructions for PT Module IL01301074E
NF and RF
Time Delay Undervoltage Module for Use with
Undervoltage Release in Eaton Circuit Breakers
IL5721B33
NF and RF
Series NRX with PXR - Instructions for Neutral
Current Sensor - Type RF
IL0131094EN RF