Instruction Leaflet
IL01906008E
Effective March 2011
Instructions for Testing Magnum DS
Digitrips with the MTK2000 Test Kit
EaTon CorporaTIon www.eaton.com
5.15 Maintenance Mode Setting
5.15.1 MDS 1150 Digitrip Models
If any of the red LEDs are blinking press “Reset” on Digitrip .
•
Set the desired test value for the “Maint PU” funtion .
•
Set the “MaintenanceMode” menu to “Enable” .
Once selection has been made, press “Save” under the “Edit Value”
Menus buttons .
•
Set value for the “LONG PU” function to maximum .
•
Set value for the “LongTIME” function to maximum .
•
Set value for the “SHORT PU” function to maximum .
Once selection has been made, press “Save” under the “Edit Value”
Menus buttons .
5.15.2 MTK2000
Press
Test Select
until “MAINTENANCE MODE TEST” comes up on
the MTK2000 . Press
Start
.
The MTK2000 display is specifying that values need to be set, these
values were set in the Digitrip Instructions . Press
Start
.
Set the “R” value on the MTK2000 display to match the Digitrip’s
“MAINT PU” values by scrolling the
up and down arrows
.
ote:
N
If you are not sure which R value is needed the next menu will allow
the multiplier value to be set .
Press
Test Select
for “MMODE TRIP SET” menu, the “mm” value
can be adjusted up or down to give you the R value desired for test-
ing .
Once value is set press
Start
on MTK2000 .
A message of “TRIP CURRENT FOUND –> PASSED” or “TRIP
CURRENT FOUND –> FAILED” will appear on the MTK2000 display .
5.16 Maintenance Mode Time Settings
5.16.1 MDS 1150 Digitrip Models
If any of the red LEDs are blinking press “Reset” on Digitrip .
5.16.2 MTK2000
After the “MAINTENANCE MODE” current is found press
Test
Select
until “MMODE MAX TIME” comes up on the MTK2000 dis-
play .
ote:
N
If
Test Select
is hit more than twice, the MTK will skip the next test
sequence . The only way to return to the time test is to redo the Im current
test .
Press
Start
and the MTK2000 will return the Maintenance Mode trip
time .
A message of “MAINTENANCE PASSED” or “MAINTENANCE
FAILED” will appear on the MTK2000 display .
ote:
N
If test is failing please reference Section 2 .3 MTK2000 Breaker Cables .
Section 6: Troubleshooting
Listed below are resolutions to common problems experienced with
MTK2000 . Please review this section prior to contacting Eaton with
questions .
Trip Unit keeps indicating the wrong type of trip (i.e. Long Delay
Trip when testing Short Delay Pickup).
Verify that the trip unit is set correctly as indicated on the MTK2000
prior to Starting the test and that the trip unit is reset prior to
Starting a test . Verify that the Zone Interlock plug is installed when
the breaker is removed past the Test Position or is removed from the
cell .
Measured values for a particular Digitrip are not consistent with
settings on the Digitrip.
Press
Cancel
twice to reach the Home Screen . Proceed as normal
and ensure that the MTK2000 performs the self calibration proce-
dure with the new Digitrip . Verify that the thermal memory jumper is
in the correct position or setting (see paragraph 2 .2 .2) . Ensure that
the SD Card provided from the factory is installed in the MTK2000
and still has the original calibration data stored .
Digitrip seems not to respond to input from the MTK2000.
Verify that the Digitrip Cable is plugged correctly into the Digitrip as
well as the rear of the MTK2000 .
Long Delay Times seem to decrease during testing.
Verify that the thermal memory jumper is in the correct position (see
paragraph 2 .2 .2)
The values on the MTK2000 Test Kit and the values on my
metering Digitrip do not match.
It is important to understand that the Digitrip has a tolerance band
within which it is expected to perform . Some difference is accept-
able, although this value should be minimal .