Installation Leafl et 

IL04209007E-HVR

Effective May 2011

C441 Motor Insight™ Overload Relay (120V

Control Powered) Product Installation Leafl et

EATON CORPORATION

 www.eaton.com

Terminal Connections

Motor Insight overload relay provides the following terminal connec-
tions. NC 95/96 contact is open when the device is unenergized.

Figure 3. Terminal Connection Diagram

Table 2.  Terminal Connection Specifications

Name

Designation

Input

Description

Control Power

L1, L2

L, N

93.5 - 132Vac

Voltage input
- X1*, X2*,  = 120V  
- Tie X1 to X1
- Tie X2 to X2
- Inputs should have short circuit 
  protection
- Terminal provided for wiring 
  control power transformer 
  (9A maximum capacity).

Fault Relay

95/96

UL

®

 508 

B300

- 95/96 Contact opens when the unit 
  is faulted or unpowered.

Programable
Auxiliary Relay*

97/98

UL

®

 508 

B300

 -97/98 Contact closes when the unit 
is faulted or unpowered.

Reset
Input

R1
R2

120 Vac 
+10%/-15%

Fault Reset Input.

* See section 6.7 of Users Manual  MN04209001E for instructions to config-
ure the programmable auxiliary relay, which changes the behavior of the relay 
from the default and allows for greater flexibility and alarming.

                             

CAUTION! 

THE OPENING OF BRANCH-CIRCUIT PROTECTIVE DEVICE MAY BE AN INDI-
CATION THAT A FAULT HAS BEEN INTERRUPTED. TO REDUCE THE RISK OF 
FIRE OR ELECTRIC SHOCK, CURRENT-CARRYING PARTS AND OTHER COM-
PONENTS OF THE CONTROLLER SHOULD BE EXAMINED AND REPLACED 
IF DAMAGED. IF BURNOUT OF THE ELEMENT OF AN OVERLOAD RELAY 
OCCURS, THE COMPLETE OVERLOAD RELAY SHOULD BE REPLACED. 

                               

ATTENTION 

LE DÉCLENCHEMENT DU DISPOSITIF DE PROTECTION DES DÉRIVATIONS 
PEUT SIGNIFIER QU’UN COURANT DE DÉFAUT A ÉTÉ INTERROMPU. POUR 
RÉDUIRE LE RISQUE D’INCENDIE OU DE CHOC ÉLECTRIQUE, LES PIÈCES 
PORTEUSES DE COURANT ET LES AUTRES COMPOSANTS DE LA COM-
MANDE DOIVENT ÊTRE VÉRIFIÉS ET REMPLACÉS S’ILS SONT ENDOM-
MAGÉS. SI L’ÉLÉMENT PORTEUR DE COURANT DU RELAIS DE SURCHARGE 
GRILLE, LE RELAIS DE SURCHARGE ENTIER DOIT ÊTRE REMPLACÉ.

Initial Configuration 

On initial power-up, Motor Insight overload relay displays a “rOF” 
message. This indicates that the fault relay is OFF. Configure the 
device for the application prior to resetting the device. 

To turn the fault relay OFF, press the Trip button.

Programming Set Points 

Motor Insight overload relay is easy to configure. Viewing and 
editing protection set points can be performed in the Protection 
and Operation Mode. The following steps outline the procedure 
for modifying any of the set points. 

Configuring the Thermal Overload Protection Feature

Motor Insight overload relay features electronic motor overload pro-
tection. This feature protects the motor and power wiring against 
overheating caused by excessive current for extended periods 
of time.

The trip current is programmed by entering the motor full load 
amperes (FLA) using the Motor FLA parameter. The trip class 
(5 to 30) is set using the Trip Class parameter.

The FLA range of the overload relay can be modified with the use 
of multiple turns through the CTs or with the use of external CTs. 
Use the following tables to appropriately configure the device for the 
application. If the application requires the FLA range to be extended, 
program the CT multiplier first.

Table 3A. FLA Range

Current 
Range

Catalog 
Number

Motor 
FLA

Number of 
Conductors 
Through CT

CT 
Multiplier

.33 – 9

C441P3309NOUI-HVR

.33 - 1.5
.4 - 1.8
.5 - 2.25
.67 - 3.0
1 – 5
2 – 9
60 – 135
120 – 270
240 – 540

6
5
4
3
2
1
1
1
1

6
5
4
3
2
1
150 - (150:5)
300 - (300:5)
600 - (600:5)

5 – 90

C441059ONOUI-HVRI

5 – 22.5
6.67 – 30
10 – 45
20 – 90

4
3
2
1

4
3
2
1

Important Note

: After an overload trip, Motor Insight relay cannot be reset 

until the thermal model decays to a thermal capacity that is thermally safe for 
a motor restart. Cycling the power does not reset the thermal model. 

Table 3B. Service Factor FLA Setting

Service Factor

Motor FLA Setting 

        >1.15

Enter the motor nameplate FLA

        =1.10

Enter the FLA as (1.1* nameplate FLA/1.15)

Step 1: Press Mode button until Protection or Operation

Mode Led is lit.

Step 2: Press Up or Down button until the desired O/P LED

is lit. Display shows the current parameter value.

Step 3: Press the Edit/Save button. The display now shows

the parameter value but is now flashing.

Step 4: Use the Up/Down button to adjust the parameter

to the desired value.

Step 5: Press the Edit/Save button. The Display now shows

the new parameter value that has been saved by the device.

Mode

Edit/Save

120

110

110

120

Edit/Save

120VAC

120VAC Control Power 50/60 Hz

X1

X2

L

NC

NO

CTRL PWR

RESET

B300 PILOT DUTY ONLY

95 96 9798 X1 X2 R1

18-12 AWG Torque 0.6 Nm/5.3 lb-in.

USE 75°C CU WIRE ONLY

120VAC

R2

* No Motor Loads, 9A Max

120VAC

N