background image

 

Magnum

 

 

1812.900A

 

29

 

 

 
 
How many connectors are mounted depends upon a 
number of considerations, such as whether the circuit 
breaker is electrically or manually operated and how 
many features are required.  When the front cover of the 
circuit breaker is removed, the top of each plug-in 
connector is exposed.  A label on each connector 
identifies the wiring points (Figure 3-21).  
 
Drawout type circuit breakers: Compatible secondary 
plug-in connectors are mounted on the top front portion 
of the drawout cassette (Figure 3-23).  These connectors 
match and plug into the circuit breaker mounted 
connectors.  Contact points are wired from the 
cassette’s plug-in connectors to cassette mounted 
terminal blocks.  The terminal blocks are also mounted 
on the top front portion of the cassette. The secondary 
terminals have finger-proof hinged covers with small 
holes for probe testing.  
 
Fixed type circuit breakers: There are two secondary 
connection options: 
 
(1) Without Terminal Block 
 
(2) With Terminal Block  
 
1. Without Terminal Block - If a terminal block for 
customer use is not required, the circuit breaker is 
supplied with both plug-in connectors (male and female) 
just described in the two previous paragraphs.  The plug-
in connectors are joined and attached to the top portion 
of the circuit breaker.  The customer can plug secondary 
wiring with crimp-on connectors into back of the plug-in 
connectors; subsequently the connections to the circuit 
breaker can be quickly joined or separated as required. 
 
2. With Terminal Block - For those customers 
preferring to wire to a terminal block, terminal blocks 
with finger-proof hinged covers are added to the 
secondary configuration just described for a fixed circuit 
breaker “without a terminal block.”  The terminal blocks 
are wired to the plug-in connectors and also permanently 
attached to the upper rear portion of the circuit breaker. 
 
A standard tool is available from the plug-in connector 
manufacturer (AMP) to facilitate the removal of 
secondary wiring from a plug-in connector, or contact 
Eaton for assistance (Figure 3-24).  The connector halves 
must be separated to use this tool. 
 

 

 
 
 

Figure 3-23: Cassette Mounted Secondary Wiring  

 
1. Closed Hinged Covers with Testing Holes 
2. Terminal Blocks 
3. Plug-in Connectors 
 

Figure 3-24: AMP Secondary Wiring Removal Tool  

 
 

3.7.1 

Connection diagrams  

The connection diagrams for all Magnum  circuit 
breakers using Digitrip RMStrip units are shown in  
Figure 3-25 through Figure 3-30. 
 
 

1

2

Содержание Magnum Air MWI-408

Страница 1: ...Double wide Fixed Standard Frame Fixed User Manual Magnum 1812 900A Magnum LV Air Circuit Breaker Narrow Frame Fixed...

Страница 2: ...chgear installations such as setting up the connecting of cables operation inspection and maintenance must only be carried out by persons authorised to do so Administrative data Version number A Date...

Страница 3: ...assembly 20 3 3 Pole units 20 3 3 1 Primary moving contacts 20 3 3 2 Primary stationary contacts 21 3 4 Operating mechanism 22 3 4 1 Manual operation 22 3 4 2 Electrical operation 23 3 4 3 Anti pump...

Страница 4: ...ect 46 6 4 What to inspect 47 6 4 1 Functional field testing 47 6 4 2 Arc chute inspection 48 6 4 3 Primary contact inspection 49 6 5 Circuit breaker modifications and changes 50 6 5 1 Rating plug rep...

Страница 5: ...reakers use a rigid frame housing of engineered thermoset composite resins which has high strength structural properties excellent dielectric characteristics and arc tracking resistance The drawout Ma...

Страница 6: ...ip units Magnum circuit breaker accessory items are discussed briefly in this manual Field installation instructions for such items however are covered in individual instruction leaflets specific to t...

Страница 7: ...E40 E4N 65 85 100 1 65 85 100 150 2 65 NA 85 65 100 85 150 100 5000 MWI 850 85N MWI C50 C5N MWI E50 E5N 85 100 150 2 85 65 100 85 150 100 6300 MWI 863 86N MWI C63 C6N MWI E63 E6N 85 100 150 2 85 65 10...

Страница 8: ...ghly trained in the operation of the circuit breaker and how it interfaces with the assembly in which it is used In addition the individual should have knowledge of the connected loads For the purpose...

Страница 9: ...sting and or installation When ready to inspect and install the Magnum circuit breaker carefully remove the banding straps and lift off the cardboard box Remove any additional packing material and int...

Страница 10: ...ers once removed from their shipping containers should be visually inspected for any obvious damage The current rating of the rating plug installed in the trip unit should match the current rating of...

Страница 11: ...side rejection plate and key pattern must be assembled and installed by the switchboard builder Figure 2 2 Rear View Showing Current Sensor Rating Through Viewing Window CAUTION DO NOT DISABLE REJECTI...

Страница 12: ...proceed with the rest of the circuit breaker installation From Table 2 2 make a pin location comparison Stop nuts should be torqued to 8 10 Ft Lb Figure 2 4 Cassette Rejection Interlock Pin Positioni...

Страница 13: ...e or Inspection Position Figure 2 5 Remove Position Only Ground Connection Made Breaker Still Behind Door Typical Storage Position Figure 2 6 Disconnect Position Breaker and Trip Unit Testing Primary...

Страница 14: ...reaker is held trip free Begin by rotating the levering in screw to the full counterclockwise DISCONNECT position Close the compartment door and begin levering the breaker into its different positions...

Страница 15: ...econdary connection devices are mounted at the top front of the circuit breaker The fixed circuit breaker frame has two mounting feet one on each side to permit the fixed circuit breaker to be securel...

Страница 16: ...t breakers are available from the factory with several different phase sequences distinguishable by the sixth character in the model number Figure 1 3 The phase sequence is also labeled on the rear of...

Страница 17: ...Chute Cover 2 Secondary Disconnect 3 Faceplate Front Cover 4 Integral Lifting Handle 5 Fixed Horizontal Primary Terminal 6 Fixed Primary Terminal with optional Vertical Adapter 7 Arc Chamber 8 Sensor...

Страница 18: ...Rear Views 1 Baffled Arc Chute Cover 2 Secondary Contact Connector 3 Faceplate Front Cover 4 Integral Lifting Handle 5 Fixed Vertical Primary Terminals with Optional Vertical Adaptor 6 Arc Chamber 7 M...

Страница 19: ...n Close 6 Spring Status Charged Discharged 7 Manual OFF Button Push 8 Manual ON Button Push 9 Manual Charge Handle 10 Optional Operation Counter 11 Padlockable Levering Device Access Door for Drawout...

Страница 20: ...eaker s frame size Double wide circuit breakers use two pole units and arc chute assemblies connected mechanically and electrically in parallel to form each phase Figure 3 5 Typical Magnum Constructio...

Страница 21: ...e is a conductive pad mounted on the line conductor which functions as the stationary main contact The other is an arc runner also connected to the line conductor The integral arc runner serves a dual...

Страница 22: ...by pressing and releasing the appropriate button Access to these pushbuttons can be limited by the use of an optional padlockable cover In addition complete access to the ON button can be prevented w...

Страница 23: ...arged and latched the close command will be ignored until it is removed and reapplied Figure 3 12 Electrical Motor Operator to Charge Closing Spring 1 Electrical Motor Operator For electrical closing...

Страница 24: ...icroprocessor based trip unit Magnum circuit breakers use any one of a family of Digitrip RMS trip units whose main features are summarized in Table 3 1 Versions of the trip unit without the i meet th...

Страница 25: ...vels and the tripping energy are derived from the current sensors integrally mounted in the circuit breaker Control power is required to operate certain optional display and metering functions Table 3...

Страница 26: ...t of the rating plug clearly indicates that the rating plug and sensors must have the same rating 2 It determines the maximum instantaneous setting which is a function of the current sensor rating 3 W...

Страница 27: ...eplate Figure 3 17 It operates by releasing and popping out any time the circuit breaker trips due to to an overcurrent condition Note that the mechanical trip indicator will not prevent the breaker f...

Страница 28: ...ory Figure 3 20 illustrates line side voltage taps Figure 3 20 Line Side Voltage Tap for 1150 Trip Unit Labels Legend OTS Overcurrent Trip Switch UVR Undervoltage Release ATR Automatic Trip Relay 520M...

Страница 29: ...tors male and female just described in the two previous paragraphs The plug in connectors are joined and attached to the top portion of the circuit breaker The customer can plug secondary wiring with...

Страница 30: ...VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRING RELEASE FOR SUBSEQUENT OPERATION 6 TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AND OR GROUND TIME FUNCTIONS FOR TESTING OR NON ZONE INTERLOCKING...

Страница 31: ...NE INTERLOCKING APPLICATIONS A JUMPER FROM B 8 TO B 9 IS REQUIRED 5 ON THREE POLE BREAKERS ONLY HAVING GROUND FAULT FUNCTIONALITY A JUMPER INSTALLED FROM B 6 TO B 7 WILL ENABLE SOURCE GROUND FAULT SEN...

Страница 32: ...PULSE WILL OCCUR WHEN THE MECHANISM IS CHARGED AND RESET LCS OPEN VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRING RELEASE FOR SUBSEQUENT OPERATION 6 TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME...

Страница 33: ...PULSE WILL OCCUR WHEN THE MECHANISM IS CHARGED AND RESET LCS OPEN VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRING RELEASE FOR SUBSEQUENT OPERATION 6 TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME...

Страница 34: ...LSE WILL OCCUR WHEN THE MECHANISM IS CHARGED AND RESET LCS OPEN VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRING RELEASE FOR SUBSEQUENT OPERATION 4 TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AN...

Страница 35: ...LSE WILL OCCUR WHEN THE MECHANISM IS CHARGED AND RESET LCS OPEN VOLTAGE MUST BE REMOVED AND REAPPLIED TO THE SPRING RELEASE FOR SUBSEQUENT OPERATION 4 TO PROVIDE SELECTED TIME DELAYS FOR SHORT TIME AN...

Страница 36: ...windows located in the right front of the circuit breaker Figure 3 31 All four are plug in type and can be factory installed or field installed The four Plug In accessories are Shunt Trip ST Spring Re...

Страница 37: ...the anti pump feature of the electrical charging closing system Figure 3 34 Spring Release with Optional Latch Switch Table 3 4 Spring Release Ratings Control Voltages Operational Voltage Range 70 110...

Страница 38: ...urrent trip switch to operate The overcurrent trip switch has 2a 2b Form C contacts Table 3 6 The status of the contacts changes when the trip indicator pops out This permits the switch to be used as...

Страница 39: ...408 528 Vac 144 288 Vac 400 VA 10 VA 70 600 Vac 2 510 660 Vac 180 360 Vac 400 VA 10 VA 70 1 Required for 200 ms 2 Required for 400 ms Table 3 6 Auxiliary Switch Overcurrent Trip Switch and Cell Switc...

Страница 40: ...eaker and can be viewed through the front cover Figure 3 41 The customer supplies the key lock The provisions available are for Kirk Castell or Ronis Figure 3 41 Cover Mounted Key Lock and Operations...

Страница 41: ...rs in Closed Position Figure 3 45 Safety Shutters in Open Position Door Escutcheon The door escutcheon is a molded frame used to seal the space between the circuit breaker and the compartment door cut...

Страница 42: ...n the relative orientation of the breakers Rods can be used only when the circuit breakers to be interlocked are vertically stacked Cables can be used for any orientation of the breakers Mechanical in...

Страница 43: ...nd secondary connections For the IEC circuit breaker a cassette style using horizontal stabs and horizontal customer bus bar terminals is available as standard Figure 4 3 The cassette terminal connect...

Страница 44: ...3 Secondary Plug in Connectors 4 Secondary Terminal Blocks 5 Arc Hood 6 Optional Cell TOC Switch 7 Optional Key Interlock 8 Earthing Bar 9 Open Safety Shutters 10 Primary Terminals Rear View Figure 4...

Страница 45: ...llation of a fixed circuit breaker was discussed in Section 2 If necessary review that information since it will not be repeated here 5 2 Fixed circuit breaker dimensions The standard fixed circuit br...

Страница 46: ...record sheets be completed for the equipment Careful and accurate documentation of all maintenance activities provides a valuable historical reference on equipment condition over time 6 2 General clea...

Страница 47: ...YPE CIRCUIT BREAKERS MAKE SURE THE BREAKER IS LEVERED OUT TO THE TEST OR DISCONNECT POSITION DURING THE LEVERING OUT AND LEVERING IN OF THE CIRCUIT BREAKER BE AWARE OF ANY SIGNS THAT WOULD INDICATE TH...

Страница 48: ...erify closing by noting the state of the indicating flag Charge the breaker mechanism springs either using the charging handle or the motor operator If using the motor operator disconnect power to it...

Страница 49: ...igure 6 2 A contact wear indicator is provided for each primary contact and indicates whether or not the contact should be replaced Inspection of the contacts using the contact wear indicators is cond...

Страница 50: ...devices Their installation is covered by separate instruction leaflets dedicated to the individual devices The tasks described here do not under ordinary circumstances require any assistance beyond t...

Страница 51: ...crewdriver to tighten the M4 screw and secure the rating plug in the trip unit The maximum torque on the mounting screw is 15 in oz Close the rating plug door 6 5 2 Current sensor replacement NOTICE R...

Страница 52: ...them off of the terminals and unplugging the wiring plugs from the sensors Figure 6 8 Install new current sensors by connecting the wiring plugs to the sensors and sliding the sensors over the termina...

Страница 53: ...ake sure shunt trip is seated and retainer snapped into place Check for shunt trip motion replace shunt trip if faulty Circuit breaker cannot be opened remotely but can be opened locally Secondary con...

Страница 54: ...s Levering in screw n ot in fully DISCONNECT position at insertion Rotate levering in screw counterclockwise to DISCONNECT position then insert breaker fully into cassette Levering in screw in DISCONN...

Страница 55: ...ctorial and or graphic reference Also include the circuit breaker type General Order number and other information as shown on the nameplate on the front cover of the circuit breaker Figures 1 2 and 3...

Страница 56: ...44 0 8700 540 333 E mail ukcommorders eaton com Eaton Electric NV PO Box 23 7550 AA Hengelo The Netherlands Customer Support Centre Tel 31 0 74 246 7066 Fax 31 0 74 246 7070 E Mail c heuropesupport ea...

Отзывы: