background image

5

Instruction Leaflet 

IL012001EN

Effective October 2013

Instruction Leaflet for the

KES 310+ Electronic Trip Unit

 

EATON 

www.eaton.com

12. The Ground Fault Relay option will provide a SPST contact clo-

sure immediately before the breaker will trip on a ground fault 

over current detect. This closure is momentary (50ms) and the 

customer must provide the necessary external circuitry in order 

to latch this signal. The yellow and green wires that exit the right 

side of the breaker are the common (C) and normally open (NO) 

of this relay.

otee:

N

The High Load Alarm Relay can be selected with LS, LSI, and LSG, 

LSIG trip units. For the LSG and LSIG trip units, the High Load Alarm will func-

tion as normal. [11.] However, if the breaker trips due to a ground fault condi-

tion, the relay will respond with a ground fault alarm as indicated in [12.]. 

 

The Ground Fault Alarm Only can be selected for LSG and LSIG trip units only. 

This selection has precedence over all other relay functions. 

 

When the Ground Fault Alarm Only is selected, the High Load Alarm Relay 

feature is not available.

otee:

N

The contact ratings of the relay are: 2A at 30 VDC and 0.5 A at  

125 VAC.

13.  The Zone Selective Interlock (ZSI) option provides a wired meth-

od of coordinating Upstream and Downstream breakers. The 

coordinating signals are provided by the White\Red stripe (Zin), 

White\Black stripe (Zout), and Black (common ground) wires that 

exit the right side of the breaker. 

 

A typical connection for a two breaker system is accomplished 

by connecting the Zout wire of the downstream breaker to the 

Zin of the upstream breaker. The common black wires of both 

breakers must also be connected. 

 

If a high current fault is sensed from the load on the down-

stream breaker, both breakers will sense the fault. However, 

the downstream breaker will send the interlock signal to the 

upstream breaker informing it not to trip defined by the SD time 

settings of both breakers. This delay allows the downstream 

breaker to clear the fault without the upstream breaker tripping.

 

However, if for some reason the downstream breaker does not 

clear the fault in the set delay time, the upstream breaker will 

then clear the fault.

otee:

N

This option must be ordered from the factory. 

14.  Zone Selective Interlocking is provided for the short delay and 

the ground fault delay tripping functions for improved system 

protection. The KES 310+ Trip Unit Zone Selective Interlocking 

feature is compatible with OPTIM and Digitrip Trip Units, Model 

510 and higher. It is also compatible with Series G: RG, NG LG, 

JG, breakers, as well as, with FDE breakers.

 

The Zone Selective Interlocking feature is a means of commu-

nications over a pair of wires between two or more compat-

ible trip units. Zone Selective Interlocking makes it possible for 

programmed trip unit settings to be altered automatically to 

respond to different fault conditions and locations, thereby local-

izing the effects of an interruption and providing positive coordi-

nation between circuit breakers.

 

Three wires exit the breaker with the following color code and 

function: White/Black Stripe=Zone Out, White/Red Stripe=Zone 

In, and Black=Common.

 

 

An example of a Zone Interlock system would be a KES 310+. A 

breaker used as the upstream breaker and a 225A FDE breaker 

used as the downstream breaker. The Zout wire (white/black 

stripe) of the 225A breaker would be connected to the Zin wire 

(white/red stripe) of the KES 310+ breaker. Also both common 

wired (black must be connected). There could be more breakers 

added in a similar fashion to form a zone of protection.

 

For faults outside the zone of protection, the trip unit of the cir-

cuit breaker nearest the fault sends an interlocking signal (Zout) 

to the trip unit of the up-stream circuit breaker. (Zin) This inter-

locking signal restrains immediate tripping of the upstream cir-

cuit breaker until its programmed coordination time is reached. 

Thus zone selective interlocking applied correctly can reduce 

damage due to circuit or ground fault conditions. A table of the 

settings of the two breakers versus the outcomes (Both Trip, 

Downstream (Dn) Trips) of the breakers is indicated below for 

the conditions mentioned in the table heading.

Upstream

INST

120ms

300ms

Do
wnstream

INST

Both

Dn 43ms

Dn 43ms

120ms

Both

Dn 52ms

Dn 52ms

300ms

Both

Dn 43ms

Dn 43ms

otee:

N

A single Series G, FDE, or KD310+ breaker with the Zone Interlocking 

feature enabled will not trip at the programmed time settings, unless Self 

Interlocked. That is, the Zout wire should be connected to the Zin wire.

15. Remote Maintenance Mode (RMM) places the trip unit in the 

2.5x instantaneous mode.  For example, a 400 A (In) KD breaker 

with the switch set to 2.5x would trip instantaneously when the 

current exceeded 1000 A.

 

The Remote Maintenance Mode is enabled by applying 24VDC 

to the two wire cable that exits the left side of the breaker.  The 

wires are color coded as follows:

 

24V and Black=common ground.  A blue colored 

LED, on the trip unit lights when the breaker is the Remote 

Maintenance Mode.

 

The lighted blue LED indicates that the instantaneous setting of 

the Maintenance Mode is enabled. This setting corresponds to 

2.5x of In. Turning the Isd switch on the trip unit has no effect 

on either the Maintenance Mode or the tsd\tg settings while the 

blue LED is lit.

 

Also, a relay contact closure indicates that the Maintenance 

Mode has been enabled. The blue and red wires are the C and 

NO contacts of this relay.  The relay has a dual function: 1) 

enable RMM and 2) provide a contact closure indication that 

RMM is enabled.

 

Both the yellow and black set of wires and the red and blue set 

of wires exit the left side of the breaker.

otee:

N

 The RMM and High Load\GFA Alarm contacts are rated at 2A at 30 

VDC and 0.5A at 125 VAC.  

Содержание KES 310+

Страница 1: ...it Installation 2 2 Trip Unit Controls and Functions 4 3 Neutral Current Sensor Installation 6 4 100 Rated K Frame Breakers 7 Effective October 2013 Instruction Leaflet IL012001EN Instruction Leaflet for the KES 310 Electronic Trip Unit ...

Страница 2: ... WHILE IT IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING 1 Trip Unit Installation Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 TORQUE 6TO 8 LB FT 3X 8TO 10 N m LINE END LOAD END TRIP UNIT RETAINING SCREWS TRIP UNIT TEST PORT TORQUE 18 23 LB IN 8X 2 0 2 6 N m Note N Wires for optional features ...

Страница 3: ...nd Current Sensor Bend Tab at Scored Line and Break Out Notch Is Positioned Towards Load End of Circuit Breaker and Is Closer to Base than Cover Retaining Screw 3 Places Trip Unit Secondary Winding Connector Barrier Current Sensor Retaining Screw Position the trip unit together with the barrier and current sensor in the circuit breaker Make sure the latch bracket pin is properly seated in the slot...

Страница 4: ...t conditions that exceed the short delay pick up setting the trip unit initiates a trip after a predetermined delay Note N In addition to the short delay trip function there is a fixed instanta neous override for the 400A 250A and 125A trip units The override for the 400A is fixed at 4400A the override for the 250A is fixed at 4200A and the override for the 125A is fixed at 3000A If a fault curren...

Страница 5: ...rammed trip unit settings to be altered automatically to respond to different fault conditions and locations thereby local izing the effects of an interruption and providing positive coordi nation between circuit breakers Three wires exit the breaker with the following color code and function White Black Stripe Zone Out White Red Stripe Zone In and Black Common An example of a Zone Interlock syste...

Страница 6: ...al is grounded but no phase to neutral loads are used the neutral cur rent sensor is not necessary In that case the white and grey leads on the trip should be cut off before installation If the system neutral is grounded and phase to neutral loads are used then the neutral current sensor must be used It should be connected to the breaker according to Figure 11 It has the same turns ratio as the ph...

Страница 7: ...n accessory wir ing for ground fault breakers Then install the ground fault alarm and neutral current sensor connector printed circuit board as described previously CAUTION LEADS COULD BE DAMAGED IF IN CONTACT WITH MOVING PARTS ACCESSORY WIRES SHOULD BE FORMED AND ROUTED TO CLEAR ALL MOVING PARTS When the appropriate accessory and the connector board are installed there are up to three sets of lea...

Страница 8: ...e considered all inclusive If further information is required you should consult an authorized Eaton sales representative The sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole...

Отзывы: