background image

7

iLumin Plus

www.eaton.com/lightingsystems

Connecting two wire addressable Bus

The two wire addressable bus is used for user interface 

devices and individually addressable smart LED drivers.  

Each two wire module (SCMD4) will be pre-mounted on the 

interior DIN rail per the order specifications and provide four 

(4) two wire addressable buses. Each two wire addressable 

bus supports up to 64 addresses per bus. 
Use 14AWG cable for the two wire addressable bus and do 

not exceed 300 meters (984ft).  The two wire addressable 

bus is polarity and topology free.  
The two wire addressable bus provides 250mA per bus to 

power addressable devices.  The following table provides 

information on devices that can connected to the two wire 

addressable bus

Device type

Current 

draw

Max per 

bus

# of addr

Lighting driver or ballast

2mA

64

1

2 wire wallstation

3.75mA

64

1

2 wire relay

3.75mA

64

1

2 wire multi sensor

3.75mA

8

1

2 wire high bay sensor

3.75mA

8

1

2 wire 0-10V fixture control

3.75mA

64

1

Follow these rules when connecting the two wire 

addressable bus:
•  Torque = 0.4N-M (XXX in-lbs)
•  Wire Sizes: 18-12AWG solid/stranded copper only
•  Load to: 200mA maximum draw
•  Acceptable for Class 1 or Class 2 wiring per NFPA 70 

section 725.XX and CEC 16.1000 if wiring methods per 

16.114 are used

Connecting to the lighting network

Medium and large iLumin Plus panels include the CR1-RJ PC 

connection device.  A PC can be connected to the iLumin 

Plus panel using the SW2 cable kit plugging into the RJ port 

on the CR1-RJ.  If this iLumin Plus panel is connected to the 

lighting network the PC will have access to all iLumin Plus 

devices on the lighting network.
In a medium or large iLumin Plus panel one side of the CR1-

RJ will not have wires connected.  This terminal is used to 

connect to other iLumin Plus panels.  The lighting network 

is a daisy-chain and requires one in and one out connection.  

The lighting network also requires a terminating jumper 

installed at the two ends of the network
Lighting network wire should use Eaton LCCP or LCCNP 

wire.  (alternate: Belden 1502, 1502P)

Two Wire Digital Bus Wiring Detail

Four: Two wire data buses

Wiring Information:

Strip wire:  

1

2

" to 

5

8

"

Wire size: 18-14AWG 

   Solid/stranded copper only

   Suitable for Class 1 and Class 2 

   wiring per NFPA 70

Load:

   16VDC -225mA maximum  

    per channel 

*Note: Load no more than 64 addressable 

devices per bus.  See device information for  

bus power consumption.

   

Purple 

Purple

Class 2

Class 2

Lighting Network Wiring Detail

Wiring Information:

Strip wire:  

1

2

" to 

5

8

"

Wire size: 18-22AWG 

   Solid/stranded copper only

   Class 2 wiring 

Wire:

   Use Eaton catalog # LCCP or LCCNP

   Alternate: Beldon 1502 or 1502P or equal 

*Note: Lighting control network must be run as a daisy 

chain, with termination jumper in place at two ends.

   

Class 2 Prewired 

five wire network 

wire. 

Class 2 

Field installed five 

wire network wire.

Run five wire 

network wire to 

additional iLumin 

Plus panels 

maintain daisy 

chain

Содержание iLumin Plus

Страница 1: ...large units Failure to comply with these instructions may result in serious injury including death and property damage WARNING DISCLAIMER OF LIABILITY Eaton assumes no liability for damages or losses...

Страница 2: ...ow voltage Input Class 2 Low voltage Input Installation steps 1 Mount enclosure 2 Connect panel power 3 Connect relay wiring 4 Connect 0 10V dimmer wiring 5 Connect 2 wire data bus wiring 6 Connect iL...

Страница 3: ...nd discard before field wiring This includes cardboard spacers in small cabinets and plastic tie wraps used on all SCMR relay modules SCMR Branch Circuit OCP SCCR NOTE Cabinets containing SCMR modules...

Страница 4: ...ct operating conditions The cabinets do not contain fans Allowing airflow around the panel will enhance the reliability and longevity of all models Locating panels away from heat generating equipment...

Страница 5: ...l cabinets have been designed to provide a clear layout and logical progression for all power circuits The main supply conductors enter at the top panel Input power is then fed to the modules inside t...

Страница 6: ...on the interior DIN rail per the order specifications Each 0 10V dimmer requires a corresponding relay from the SCMR1220 NA to turn the lighting load ON OFF This mapping is performed during programmi...

Страница 7: ...R1 RJ PC connection device A PC can be connected to the iLumin Plus panel using the SW2 cable kit plugging into the RJ port on the CR1 RJ If this iLumin Plus panel is connected to the lighting network...

Страница 8: ...to access the lighting network via the buildign LAN or VLAN Note The EG2 can be use as a LAN bridge to connect different building lighting networks as a single lighting network over the building LAN...

Страница 9: ...de taille La d sob issance aux instructions suivantes repr sente un risque de blessures y compris la mort et de dommages mat riels AVERTISSEMENT EXON RATION DE RESPONSABILIT Eaton n assume aucune resp...

Страница 10: ...limentation du panneau 3 Raccordement du c blage de relais 4 Raccordement du c blage du gradateur de 0 10 V 5 Raccordement des deux c bles de conducteur du bus de donn es 6 Raccordement du c blage du...

Страница 11: ...que REMARQUE SUR LA PROTECTION CONTRE LES SURINTENSIT S et LE COURANT DE COURT CIRCUIT NOMINAL du circuit r sonance coupl e magn tique Les armoires qui contiennent les modules r sonance coupl e magn t...

Страница 12: ...armoires ne comportent pas de ventilateur Permettre une circulation d air autour du panneau am liorera la fiabilit et la dur e de vie de tous les mod les Installer les panneaux loin du mat riel qui g...

Страница 13: ...et une progression logique pour tous les circuits d alimentation Les conducteurs de l alimentation principale p n trent dans le haut du panneau La puissance d entr e est ensuite aliment e vers les mo...

Страница 14: ...Humidit entre 0 et 95 sans condensation Les modules de gradation SCMH1200 NA sont pr alablement mont s l int rieur du rail DIN conform ment aux sp cifications de la commande Chaque gradateur de 0 10 V...

Страница 15: ...ge Les moyens et les grands panneaux iLumin Plus comprennent le dispositifs de connexion pour ordinateur CR1 RJ Un ordinateur peut tre raccord au panneau iLumin Plus l aide de la trousse de c bles SW2...

Страница 16: ...suite iCANsoft pour le processus de configuration Connexion Ethernet Wiring Information Connection RJ45 connector Use Category 5 or Category 6 cable minimum Connect Connect to building LAN or VLAN for...

Страница 17: ...e estas instrucciones puede provocar lesiones graves incluida la muerte y da os a la propiedad ADVERTENCIA RENUNCIA DE RESPONSABILIDAD Eaton no asume ninguna responsabilidad por da os o p rdidas de ni...

Страница 18: ...te el recinto 2 Conecte la alimentaci n del panel 3 Conecte el cableado del rel 4 Conecte el cableado del atenuador de 0 10V 5 Conecte el cableado del bus de datos de 2 cables 6 Conecte el cableado de...

Страница 19: ...e separadores de cart n en peque os armarios y envolturas de pl stico que se usan en todos los m dulos SCMR rel s Circuito derivado SCMR OCP y SCCR NOTA Los armarios que contienen m dulos SCMR NO incl...

Страница 20: ...miento correctas Los armarios no contienen ventiladores Permitir el flujo de aire alrededor del panel mejorar la confiabilidad y longevidad de todos los modelos La ubicaci n de paneles lejos de equipo...

Страница 21: ...ise ados para proporcionar un dise o claro y una progresi n l gica para todos los circuitos de alimentaci n Los conductores principales de suministro ingresan en el panel superior La corriente de entr...

Страница 22: ...n Los m dulos de atenuaci n SCMH1200 NA se premontar n en el riel DIN interior seg n las especificaciones del pedido Cada atenuador de 0 10V requiere un rel correspondiente del SCMR1220 NA para ENCEND...

Страница 23: ...4 Conect ndose a la red de iluminaci n Los paneles iLumin Plus medianos y grandes incluyen el dispositivo de conexi n CR1 RJ PC Se puede conectar una PC al panel de iLumin Plus utilizando el kit de ca...

Страница 24: ...Category 6 cable minimum Connect Connect to building LAN or VLAN for lighting network access Note The EG2 can be used to access the lighting network via the buildign LAN or VLAN Note The EG2 can be u...

Отзывы: