18
Eaton 93PM Integrated Battery Cabinet-Small Welded (IBC-SW) Installation Manual 164000639—Rev 03
Table 5. External Power Cable Terminations for the Eaton 93PM IBC-SW
Model
Terminal
Function
Terminal
Function
Number and Size of
Pressure Termination
Tightening
Torque Nm (lb in)
Screw Size
and Type
IBC-SW
DC Output
B
Positive
2 - #6-250 kcmil
31 (275)
5/16" Hex
Battery –
Negative
2 - #6-250 kcmil
31 (275)
5/16" Hex
Customer Ground
Ground
Ground
6 - #6-1/0
5.1 (45)
Slotted
NOTE
Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed. Refer to the appropriate
UPS manual.
External DC input overcurrent protection and disconnect switch for the remote battery location (three or four
IBC–SWs) is to be provided by the customer.
lists the maximum rating for continuous-duty rated circuit
breakers satisfying the criteria for both.
Table 6. Recommended DC Circuit Breaker or Disconnect Ratings (Three or Four IBCs)
Model
UPS Model
Input Rating
IBC-SW
50 kW
100 kW
150 kW
200 kW
250A
33..22..33
IIB
BC
C––S
SW
W IInntteerrffaaccee W
Wiirriinngg P
Prreeppaarraattiioonn
Control wiring for features and options should be connected at the customer interface terminal blocks located
inside the IBC–SW.
WARNING
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required.
Read and understand the following notes while planning and performing the installation:
•
Use Class 1 wiring methods (as defined by the NEC) for interface wiring from 30V to 600V. The wire
should be rated for 600V, 1A minimum. 12 AWG maximum wire size.
•
Use Class 2 wiring methods (as defined by the NEC) for interface wiring up to 30V. The wire should be
rated for 24V, 1A minimum.
•
Because of the battery shunt trip wiring route in the 93PM UPS cabinet, the wiring from the IBC to the
UPS must use wire rated for 600V and Class 1 wiring methods.
•
The battery detect signal wiring from the battery cabinet must be connected to a programmed UPS
building alarm.
•
Battery detect and 48 Vdc shunt trip wiring should be a minimum of 18 AWG.
•
Use twisted-pair wires for each input and return or common.
•
All interface wiring and conduit is to be supplied by the customer.
•
Interface wiring can be installed using the inter-cabinet wiring access pass-through or by routing wiring
through conduit between cabinets.