DESCRIPTION:
DATE:
DRAWING NO:
1 of 1
SHEET:
REVISION:
B
070804
PHYSICAL FEATURES AND REQUIREMENTS
164201536-2
Installation Information
A-4
EATON
Powerware
®
9390 Integrated Battery Cabinet (Models IBC-S and IBC-L) Installation Manual
S
164201536 Rev D
www.eaton.com/powerquality
1.
The battery cabinet operating environment must meet the weight requirements shown in
Table A and size requirements shown on Drawing 164201536-9.
2.
The battery cabinets are palleted separately for shipping.
3.
Do not tilt cabinets more than
"
10° during handling.
4.
Dimensions are in millimeters (inches).
Table A.
Equipment Weight
Component
Weight
kg (lb)
Shipping
Installed
Point Loading
IBC-S with 32 batteries (384 VDC)
837 (1845)
807 (1780)
4 at 202 (445)
IBC-S with 36 batteries (432 VDC)
909 (2005)
880 (1940)
4 at 220 (485)
IBC-S with 40 batteries (480 VDC)
982 (2165)
953 (2100)
4 at 238 (525)
IBC-L with 32 batteries (384 VDC)
1848 (4075)
1814 (4000)
8 at 227 (500)
IBC-L with 36 batteries (432 VDC)
2029 (4475)
1995 (4400)
8 at 249 (550)
IBC-L with 40 batteries (480 VDC)
2211 (4875)
2177 (4800)
8 at 272 (600)
5.
The clearances required around the battery cabinets are shown in Table B.
Table B. Battery Cabinet Clearances
From Top of Cabinet
Minimum clearance over the battery cabinet is
457.2 mm (18 in.) for ventilation
From Front of Cabinet
36 inches (0.9144m) working space
From Back of Cabinet
None required
From Right Side of Cabinet
None required
From Left Side of Cabinet
None required
6.
The basic environmental requirements of both Models IBC-S and IBC-L for operation of
the UPS system are:
Operational Temperature Range:
22-28°C (72-82°F)
Maximum Relative Humidity:
95%, noncondensing
CAUTION:
It is recommended for optimal battery life and discharge perform
ance to keep the ambient air temperature the battery is used in at 25°C (77°F).