Safety, Use, & Installation
English
Safety guidelines to read before installing the product
w
The product must be used indoors only.
w
Do not place the product near liquid or in an excessively damp environment.
w
Do not place the product directly in the sun or near a heat source.
w
Do not let liquid or foreign objects enter the product.
w
Ground the product using a 2 poles + ground socket (2P + G).
w
When installing the product, ensure that the sum of the leakage currents of the product and the devices
it supplies does not exceed 3.5 mA.
w
The AC-power input must be connected to an appropriate electrical network protection or tap-off circuit
(fuse or circuit-breaker).
Use
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the
connected loads (HotSwap function). Refer to the illustrations.
Installation
Refer to the UPS installation and user manual.
HotSwap MBP module operation
The HotSwap MBP module has a rotary switch with two positions:
w
Normal - the load is supplied by the UPS,
w
Bypass - the load is supplied directly by the AC-power source.
UPS start-up with the HotSwap MBP module
1.
Check that the UPS is correctly connected to the HotSwap MBP module.
2.
Set switch to the Normal position.
3.
Start the UPS by pressing the ON/OFF button on the UPS control panel:
w
The load is supplied by the UPS.
w
Green LED "UPS ON - OK to switch" on the HotSwap MBP module goes ON.
HotSwap MBP module test
1.
Set switch to the Bypass position and check that the load is still supplied.
2.
Set switch back to the Normal position.
Maintenance on a UPS equipped with the HotSwap MBP module
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the
connected loads (HotSwap function).
Maintenance:
1.
Set switch to the Bypass position. The red LED on the HotSwap MBP module goes ON, indicating that
the load is supplied directly with AC power.
2.
Stop the UPS: green LED "UPS ON - OK to switch" goes OFF, the UPS can now be disconnected and
replaced.
Return to normal operation:
1.
Check that the UPS is correctly connected to the HotSwap MBP module.
2.
Start the UPS: green LED "UPS ON - OK to switch" on the HotSwap MBP module goes ON (otherwise,
there is a connection error between the HotSwap MBP module and the UPS).
3.
Set switch to the Normal position. The red LED on the HotSwap MBP module goes OFF.
2 — 1
86-58100-00 A0
3
Safety, Use, & Installation
Содержание HotSwap MBP - 115
Страница 2: ......
Страница 3: ...HotSwap Connections 1 1 86 58100 00 A03 HotSwap Connections...
Страница 4: ...HotSwap Installation 1 2 86 58100 00 A03...
Страница 10: ......
Страница 11: ......