ELECTRICAL INSTALLATION
Eaton FERRUPS Rack Mount UPS (850 VA–7 kVA) Installation Guide
S
164201425 Rev 1
www.eaton.com/powerquality
55
C
A
U
T
I
O
N
To prevent electrical shock or damage to your equipment, verify that the UPS ON/OFF switch
is in the OFF position before you remove the UPS front cover panel. The circuit breaker or
disconnect switch must be turned off at the AC input service panel.
5.
Remove the knockouts in the UPS rear panel for AC Input and AC
Output. If your UPS has a separate battery cabinet, also remove the
knockout for DC.
6.
Install the conduit adapters. AC Input and AC Output conductors
must be run through separate pieces of conduit. UPS output circuits
shall be installed in dedicated conduit systems and not shared with
other electrical circuits.
C
A
U
T
I
O
N
To prevent electrical shock or damage to your equipment, verify that the AC input is OFF at
the service panel and the bypass and AC disconnect switches are in the OFF position before
you connect any wires to the bypass switch terminal strip.
7.
Find the terminal strip inside the bypass switch. Using the label on
the back of the switch's lower front cover panel, wire the terminal
strip and tighten all connections securely. Use copper wire and the
appropriate wire size for the current. See Figure 33 for sample
terminal strip labels.