4.3.3 Loss of DC Power

A visual indication and audible alarm is provided to indicate DC 
power loss due to both batteries being disconnected from the 
controller. This indication will also be provided if the controller 
is not operating due to an electronic board failure. 

4.3.4 Speed Switch Malfunction

A visual indication and audible alarm is provided to indicate 
when the following condition has occurred: The controller is 
running, the engine run signal has been lost and the oil 
pressure has not dropped. (Terminals 2 and 4) 

4.3.5 Engine Starter Coil Failure

The Diesel Plus controller constantly monitors the health of the 
engine starter solenoids. A visual indication and audible alarm 
is provided if the Diesel Plus detects that the engine starter 
solenoid is disconnected or damaged.

4.3.6 Audible Alarm Silencing

A separate audible alarm silence switch is provided which can 
manually silence the alarm buzzer for optional alarms. The 
silencing switch is located adjacent to the visual indicator. 

4.3.7 Power Failure Alarm

An alarm signal is provided when both circuit breakers have 
tripped or been opened.

4.4 Output Relays

The primary control outputs of the Diesel Plus controller are dry 
relay contacts. These relays include 2 separate “Form C” 
outputs for each of the following: Engine Run, Future #1, Future 
#2, Low Fuel, Auto Mode and Common Alarm.

The Engine Run relay is UL/CSA rated at 10A, 1/2HP, 240Vac. The 
remaining alarm relays are UL/CSA rated at 8A, 250Vac. The DC 
rating is 8A, 30Vdc.

Each relay has a green LED on the I/O board to indicate the relay 
status.

If the LED is “On” the relay is energized. If the LED is “Off” the 
relay is de-energized.

4.4.1 Relay Functions

Engine Run

This relay is used for remote monitoring when the engine is 
running. When the engine speed switch sends a signal to the 
Diesel Plus controller, this relay will energize.

Common Alarm

This relay is used to signal pump room or engine trouble 
alarms. This relay is energized under normal conditions and 
will de-energize during alarm.

Low Fuel

This relay is used for remote monitoring of the fuel tank level. 
When the level switch in the fuel tank falls below its pre-set 
level, this relay will energize.

4.4.2 Future #1 - Future # 2

The two Form C relays can be programmed for a number of 
alarm or status conditions. Refer to Appendix E(b) for 
programming details.

4.4.3 Engine Alarm Functions

Engine Overspeed

An “Engine Overspeed” alarm will shutdown the engine 
regardless of the start condition -

 in all modes.

 The signal is 

sent from the engine to the controller.

Fail To Start

After 6 cranking attempts, three attempts per battery, the “Fail 
To Start” annunciator will illuminate. Attention to the diesel and 
its associated equipment is required immediately.

High Engine Temperature

Indicates that the coolant temperature in the water jackets is 
extremely hot. The over temperature switch on the engine 
signals the controller. The engine continues to run in the AUTO 
and MANUAL modes. During a manual engine test and during 
the weekly test cycle the engine will shutdown. 

Low Oil Pressure

The controller has an inherent delay to bypass the low oil 
pressure alarm during engine start up. After the delay, should 
the engine receive a “Low Oil Pressure” signal, the controller 
will initiate an alarm. The engine will continue to run in the 
“AUTO” and “MANUAL” mode. During a manual engine test 
and during the weekly test cycle this alarm will automatically 
shutdown the engine. 

Low Fuel

(When Fuel Level Switch Wired)

Indicates that the engine fuel supply is low. The engine 
continues to run.

5. PROGRAMMING

5.1 Introduction

The Diesel Plus controller is fully programmable from the 
device’s faceplate. Users can program set points as well as 
other parameters. The time, date, and set points can only be 
changed from the menu system. The menu system is broken 
down to seven (7) menu groupings. They include, Language, 
Regional Settings, Pressure Settings, Timer Values, Custom 
Input/Output, System Configuration Menu, and Main Menu 
Password.

5.2 Navigation

In order to enter the menu system, press the Menu button on 
the Diesel Plus faceplate. If the main menu password has been 
enabled, the user will be required to enter the password at this 
time. Once in the menu system, the Up and Down arrow keys 
will provide navigation between each menu item. The display 
will show the previous, current, and next menu items. The 
current menu item is located on the middle of the four line 
display. All Diesel Plus controller programmable features and 
associated set-point possibilities are presented in Table 1.

The following set points are programmable in the Diesel Plus 
controller.

Содержание FD120

Страница 1: ...scription The DIESEL Plus Fire Pump Controllers from Eaton are designed to control and monitor 12 or 24 volt diesel fire pump engines and are among the most technically advanced diesel engine controll...

Страница 2: ...BATTERY 2 FAILURE CHARGER 2 FAILURE LOW PRESSURE SYSTEM OVER PRESSURE LOW SUCTION PRESSURE LOW FUEL FAIL TO START HIGH ENGINE TEMP LOW OIL PRESSURE ENGINE OVER SPEED ECM SELECTOR IN ALT POSITION FUEL...

Страница 3: ...NTERLOCK ON SPEED SWITCH FAULT ECM SELECTOR IN ALT POSITION FUEL INJECTION MALFUNCTION LOW FUEL LOW SUCTION PRESSURE LOW OIL PRESSURE ENGINE OVERSPEED HIGH ENGINE TEMPERATURE LOW ENGINE TEMPERATURE LO...

Страница 4: ...ne Controller Technical Data MD081012EN Main Display Effective April 2015 NOTES 1 Refer to the DIESEL Plus technical manual for details and setup information as well as programming and custom labeling...

Страница 5: ...Dimensions Diesel Plus Engine Controller Technical Data MD081014EN Fuel Level Switch Effective April 2015 3A14119G01 16 inch unit 3A14119G02 45 inch unit Dimensions in Inches...

Страница 6: ...RELAY 8 2 SETS FORM C 2 SETS FORM C OPTION RELAY 2 2 SETS FORM C OPTION RELAY 3 2 SETS FORM C OPTION RELAY 4 2 SETS FORM C AUX ANALOG INPUT 4 20MA ENERGIZED OPTION RELAY 1 FUTURE 1 FUTURE 1 FUEL SPIL...

Страница 7: ...7 62 15 24m Field Connections 100 240VAC POWER BATTERY 2 CRANK FUEL INJECTOR FAIL ECM IN ALTERNATE BATTERIES BATTERIES ECM WARNING HIGH RAW WATER TEMP ECM FAILURE LOW ENGINE TEMPERATURE LOW RAW WATER...

Страница 8: ...M PER CU AL 2 2 0 500MCM PER CU AL For Proper Cable Size Refer to National Electrical Code NFPA 70 1 63 5 83 mm 1 63 8 25 mm 4 11 12 70 mm 8 25 12 70 mm 9 27 17 96 mm Qty Cable Sizes American Wire Gau...

Страница 9: ...O Powered Louver Contacts Up to 8 0 Amp LX Extra Light Specify Description Ni Ni Cad Batteries P5 Proof Pressure Switch ALCO 19 250 PSI P7 Low Suction Pressure Switch P8 Shutdown Requires P7 Option P1...

Страница 10: ...ontacts Form C rated at 8A 250VAC 30VDC shall be provided for remote indication of 1 ENGINE RUN 10A 2 LOW FUEL 3 AUTO MODE 4 COMMON ALARM B Two 2 FUTURE relays each containing two sets of alarm contac...

Страница 11: ...00 characters each which will contin ually scroll across the fourth line of the dis play 7 Remaining time left on active timers D The controller shall be supplied with six 6 green status LED s for the...

Страница 12: ...standard with nine 9 custom inputs two 2 programmable LED indi cators and two 2 future outputs with the ability to add up to another 8 outputs via optional relay boards B The user shall be able to pro...

Страница 13: ...Powering Business Worldwide EATON Diesel Plus Diesel Engine Fire Pump Controller O M Manual IM05805019K 002 Effective April 2015...

Страница 14: ...ts 9 4 3 2 Control Input Descriptions 9 4 3 3 Loss of DC Power 10 4 3 4 Speed Switch Malfunction 10 4 3 5 Engine Starter Coil Failure 10 4 3 6 Audible Alarm Silencing 10 4 3 7 Power Failure Alarm 10 4...

Страница 15: ...dian Standards Association CSA New York Department of Buildings NYSB and meet CE and U B C C B C Seismic approval requirements 2 INSTALLATION AND ELECTRICAL CONNECTIONS 2 1 Mounting Carefully unpack t...

Страница 16: ...er is fully electronic and will protect itself by shutting down during a short circuit condition The maximum current draw that the chargers will draw when operating at 100 charging rate is 12 Volt Sys...

Страница 17: ...4 Volt battery charger cycle with NiCad batteries set DIP switches 3 and 6 to the ON position and all other DIP switches to the OFF position 3 1 7 Forced Charging There is provision for the battery ch...

Страница 18: ...uge Valve This green LED will be illuminated after receiving a start signal from special starting equipment This is a normally closed contact that is required to be opened to start A factory installed...

Страница 19: ...he LED s on the operator panel Pressing and holding this button will illuminate each LED on the operator panel in successive steps Reset Save Exit The reset save exit button serves two functions Press...

Страница 20: ...engine will automatically stop in the case of an OVERSPEED condition All alarms except for FAIL TO START are active in the MANUAL mode CAUTION Only depress Crank 1 or Crank 2 pushbuttons with control...

Страница 21: ...e Control Input state definitions are as follows Connected When the input is shorted by an external contact or connection Unconnected When the input is NOT shorted by an external contact or connection...

Страница 22: ...alls below its pre set level this relay will energize 4 4 2 Future 1 Future 2 The two Form C relays can be programmed for a number of alarm or status conditions Refer to Appendix E b for programming d...

Страница 23: ...roller will initiate a start sequence Pressure Stop Point The value programmed determines the pressure the system must reach before the controller will automatically stop the fire pump motor via the r...

Страница 24: ...automatically stop the engine after a programmed time It can be programmed to operate based on either of two separate conditions the stop pressure point or when the engine has started to run If the R...

Страница 25: ...delay the time before the alarm becomes active Default value is 0 seconds Range is 0 500 seconds The timer will reset if the input is removed before the time has timed out Custom Outputs The optional...

Страница 26: ...me Pressing the up or down arrow buttons will allow navigation showing the most recent message to the oldest message Refer to Appendix L for common messages and their meaning Refer to Section 7 to sav...

Страница 27: ...irst selection is Save to USB Press the Ack Alarm button and the controller will save the information to the USB storage device There will be five 5 files saved to the storage device Refer to Table 6...

Страница 28: ...line of the display The message can be up to one hundred 100 characters in length Column B contains the message type reference number Refer to Table 7 for the message types Column C and D are used to...

Страница 29: ...Events Number Event Number Event 1 Battery 1 2 Failure 16 Relief Valve Open 2 Charger 1 2 Failure 17 Transmitter Failure 3 AC Failure 18 Pump Room Trouble 4 Low Oil Pressure 19 Controller Trouble 5 Hi...

Страница 30: ...MPANY www chfire com APPENDIX A MAIN MENU TREE MENU PASSWORD LANGUAGE REGIONAL SETTINGS PRESSURE SETTINGS TIMER VALUES CUSTOM INPUT OUTPUT SYSTEM CONFIG MENU MAIN MENU PASSWORD ACK ACK SELECT LANGUAGE...

Страница 31: ...il 2015 EATON INDUSTRIES CANADA COMPANY www chfire com 19 APPENDIX B REGIONAL SETTINGS MENU TREE REGIONAL SETTINGS CHANGE DATE CHANGE TIME ACK ACK SET MONTH ACK SET HOUR ACK SET DAY SET YEAR SET DAY O...

Страница 32: ...MENU ITEM NEXT MENU ITEM ACK LOW PRESSURE ALARM ACK SET LOW PRESSURE ALARM ACK MENU HOURLY PRESSURE RECORDING ACK SET HOURLY PRESSURE RECORDING ACK MENU HIGH PRESSURE ALARM ACK SET HIGH PRESSURE ALARM...

Страница 33: ...ET RUN PERIOD TIMER ACK SET RPT START MODE ACK SET DAY SET TIME SET TEST INTERVAL ACK ACK ACK ACK NEXT MENU ITEM NEXT MENU ITEM MENU MENU NEXT MENU ITEM SEQUENTIAL START TIMER ACK SET SEQUENTIAL START...

Страница 34: ...Fire Pump Controller 22 EATON INDUSTRIES CANADA COMPANY www chfire com APPENDIX E CUSTOM INPUT OUTPUT MENU TREE CUSTOM INPUT OUTPUT CUSTOM INPUTS CUSTOM OUTPUTS ACK ACK GO TO APPENDIX E a ACK GO TO A...

Страница 35: ...ELAY TIM ER A C K M EN U C O M M O N ALAR M R ELAY A C K SET C O M M O N ALAR M R ELAY A C K M EN U LIN K TO R ELAY A C K SET LIN K TO R ELAY A C K N EXT M EN U ITEM M EN U LIN K TO LIG H T A C K SET...

Страница 36: ...M OUTPUTS MENU TREE CUSTOM OUTPUTS SELECT RELAY SELECT ALARM TYPE ACK MENU MENU NEXT MENU ITEM AUDIBLE ALARM ACK SET AUDIBLE ALARM ACK MENU FAIL SAFE ACK SET FAIL SAFE ACK MENU DELAY TIMER ACK SET DEL...

Страница 37: ...nual IM05805019K 002 Diesel Engine Fire Pump Controller Effective April 2015 EATON INDUSTRIES CANADA COMPANY www chfire com 25 APPENDIX E c CUSTOM LIGHTS MENU TREE CUSTOM LIGHTS SELECT LIGHT SELECT TY...

Страница 38: ...ive April 2015 Diesel Engine Fire Pump Controller 26 EATON INDUSTRIES CANADA COMPANY www chfire com APPENDIX F MAIN MENU PASSWORD MENU TREE MENU MAIN MENU PASSWORD SELECT PASSWORD ACK ACK SELECT BUTTO...

Страница 39: ...2015 EATON INDUSTRIES CANADA COMPANY www chfire com 27 APPENDIX G CUSTOM MESSAGE LOAD ACTIVATION DATA SELECT CUSTOM MESSAGES SELECT LOAD ACK ACK CUSTOM MESSAGES WILL BE UPLOADED DATA SELECT CUSTOM ME...

Страница 40: ...ire Pump Controller 28 EATON INDUSTRIES CANADA COMPANY www chfire com APPENDIX K For control wiring use 14 AWG wire for all electrical connections except battery connections For battery connection ter...

Страница 41: ...nal has been received from the engine Engine Stopped The engine run signal is no longer being received Engine Test Start The engine has started on an engine test Engine Test Fail An Engine Test has be...

Страница 42: ...will be delayed by the number of seconds programmed 9 2 Manual Start Test Turn the mode selector switch to the Manual position Press the Crank 1 pushbutton The Engine will crank and start the Engine...

Страница 43: ...on The engine will stop NOTE Engine will shutdown if Low Oil Pressure High Water Temp or Overspeed alarms are detected during the engine test 9 4 Weekly Exerciser Test Turn the mode selector switch to...

Страница 44: ...dd to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EXPRESSED OR IMPLIED INCLUDIN...

Отзывы: