3.6 External Pushbuttons

3.6.1 Stop

The stop pushbutton will initiate the stopping sequence of the 
fire pump engine only if no starting conditions are present. 
Pressing the stop button will not change the mode the panel 
was in when the button was pressed.

4. OPERATION

4.1 General

This section specifically describes the operation and functional 
use of the Diesel Plus controller. The practical use of and 
operation within each category will be discussed. In this 
section, it is assumed that prior sections of this manual were 
reviewed and that the operator has a basic understanding of 
the hardware.

4.2 Start Sequence

In the Automatic Mode the Diesel Plus controller will 
automatically start and stop the fire pump motor as dictated by 
the features supplied and their programmed set-point values. A 
summary of the controller intelligence and supervisory circuits 
that constantly monitor the condition of the system pressure, 
inputs, and system alarm points is provided.

4.2.1 Manual Start Sequence

Manual start is defined as a remote start. Whenever the engine 
is running via a manual start, the motor needs to be manually 
stopped via the stop pushbutton located on the enclosure 
flange or by placing the controller in off mode.

4.2.2 Automatic Start Sequence

Automatic start is defined as a low-pressure pump start contact 
closure, and Deluge Valve start condition. (Terminals 11 and 36) 
Whenever the engine is running via an automatic start the 
engine can be automatically stopped. In order for the controller 
to automatically stop the engine automatic stopping must be 
enabled, the RPT must be finished its timing cycle and no 
starting conditions can exist. If the controller is programmed 
for automatic shutdown, the motor needs to be manually 
stopped via the local stop pushbutton located on the enclosure 
flange or by placing the controller in the off mode.

OFF Mode

In the OFF position the controller will not attempt to start the 
engine for any reason. Off mode also resets and silences all 
alarms.

MANUAL Mode

This position allows the starting of the engines using the 
manual crank buttons, Crank #1 and Crank #2, are located on 
the enclosure flange. For added cranking capacity, both Crank 
buttons can be depressed simultaneously.

The engine can be stopped by the “Local Stop” pushbutton or 
by placing the controller in the OFF mode. The engine will 
automatically stop in the case of an OVERSPEED condition.

All alarms, except for “FAIL TO START”, are active in the 
MANUAL mode.

CAUTION

Only depress Crank #1 or Crank #2 pushbuttons with controller in the 
“MANUAL” mode. 

Do not depress the crank pushbuttons in any other mode or while engine is 
running. Doing so can result in serious damage to the engine.

AUTO Mode

A drop in pressure, “Remote Start” signal, “Pump Start” signal, 
a signal from the “Deluge Valve” or Weekly Test Timer will 
initiate the “attempt to start” cycle. This cycle consists of 6 
crank periods of 15 seconds duration separated by 5 rest 
periods of 15 seconds duration. Battery 1 and Battery 2 are 
alternated for each crank cycle. In the event that one battery is 
inoperative or missing, the controller will lock-in on the 
remaining battery during the cranking sequence. Once the 
engine is running, the controller will stop all further cranking.

STOP Modes

The Stop Mode is programmable for Auto Shutdown - On or Off 
(see Appendix C). Note that the engine can be stopped in many 
cases by pressing the local stop push button or at any time by 
placing the controller in the OFF position or automatically in 
case of an OVERSPEED condition.

Manual Stop Mode:

 The engine will continue to run until the 

“Local Stop” pushbutton is depressed - providing all starting 
causes have been eliminated.

Auto Shutdown:

 The engine will continue to run until the 

running period timer (RPT) has timed out and all starting 
causes have been eliminated. 

Weekly Test Timer

Each Diesel Plus controller is equipped with a Weekly Test 
Timer, to automatically exercise the engine in one week 
intervals, based on the programmed setting. The controller 
initiates the starting sequence by opening a drain valve 
resulting in a simulated system pressure loss. The drain valve 
is automatically closed once the controller receives a Low 
Pressure signal. The engine will continue to run for the 
programmed duration. “Weekly Test Started” will be saved into 
the controller memory.

In order to protect the engine, during the Weekly Test sequence, 
an OVERSPEED condition, LOW OIL PRESSURE or HIGH 
ENGINE TEMP alarm will automatically shutdown the engine.

Engine Test Pushbutton

Pressing the Engine Test pushbutton initiates a starting 
sequence by opening the drain valve resulting in a pressure 
loss. The controller will start the engine in the automatic mode.

The TEST sequence can be terminated by putting the controller 
in the OFF mode, otherwise the STOP mode prevails as 
programmed.

All alarms are active in the test mode. In order to protect the 
engine, in the test mode, an OVERSPEED condition, LOW OIL 
PRESSURE or HIGH ENGINE TEMP alarm will automatically 
shutdown the engine. 

Содержание FD120

Страница 1: ...scription The DIESEL Plus Fire Pump Controllers from Eaton are designed to control and monitor 12 or 24 volt diesel fire pump engines and are among the most technically advanced diesel engine controll...

Страница 2: ...BATTERY 2 FAILURE CHARGER 2 FAILURE LOW PRESSURE SYSTEM OVER PRESSURE LOW SUCTION PRESSURE LOW FUEL FAIL TO START HIGH ENGINE TEMP LOW OIL PRESSURE ENGINE OVER SPEED ECM SELECTOR IN ALT POSITION FUEL...

Страница 3: ...NTERLOCK ON SPEED SWITCH FAULT ECM SELECTOR IN ALT POSITION FUEL INJECTION MALFUNCTION LOW FUEL LOW SUCTION PRESSURE LOW OIL PRESSURE ENGINE OVERSPEED HIGH ENGINE TEMPERATURE LOW ENGINE TEMPERATURE LO...

Страница 4: ...ne Controller Technical Data MD081012EN Main Display Effective April 2015 NOTES 1 Refer to the DIESEL Plus technical manual for details and setup information as well as programming and custom labeling...

Страница 5: ...Dimensions Diesel Plus Engine Controller Technical Data MD081014EN Fuel Level Switch Effective April 2015 3A14119G01 16 inch unit 3A14119G02 45 inch unit Dimensions in Inches...

Страница 6: ...RELAY 8 2 SETS FORM C 2 SETS FORM C OPTION RELAY 2 2 SETS FORM C OPTION RELAY 3 2 SETS FORM C OPTION RELAY 4 2 SETS FORM C AUX ANALOG INPUT 4 20MA ENERGIZED OPTION RELAY 1 FUTURE 1 FUTURE 1 FUEL SPIL...

Страница 7: ...7 62 15 24m Field Connections 100 240VAC POWER BATTERY 2 CRANK FUEL INJECTOR FAIL ECM IN ALTERNATE BATTERIES BATTERIES ECM WARNING HIGH RAW WATER TEMP ECM FAILURE LOW ENGINE TEMPERATURE LOW RAW WATER...

Страница 8: ...M PER CU AL 2 2 0 500MCM PER CU AL For Proper Cable Size Refer to National Electrical Code NFPA 70 1 63 5 83 mm 1 63 8 25 mm 4 11 12 70 mm 8 25 12 70 mm 9 27 17 96 mm Qty Cable Sizes American Wire Gau...

Страница 9: ...O Powered Louver Contacts Up to 8 0 Amp LX Extra Light Specify Description Ni Ni Cad Batteries P5 Proof Pressure Switch ALCO 19 250 PSI P7 Low Suction Pressure Switch P8 Shutdown Requires P7 Option P1...

Страница 10: ...ontacts Form C rated at 8A 250VAC 30VDC shall be provided for remote indication of 1 ENGINE RUN 10A 2 LOW FUEL 3 AUTO MODE 4 COMMON ALARM B Two 2 FUTURE relays each containing two sets of alarm contac...

Страница 11: ...00 characters each which will contin ually scroll across the fourth line of the dis play 7 Remaining time left on active timers D The controller shall be supplied with six 6 green status LED s for the...

Страница 12: ...standard with nine 9 custom inputs two 2 programmable LED indi cators and two 2 future outputs with the ability to add up to another 8 outputs via optional relay boards B The user shall be able to pro...

Страница 13: ...Powering Business Worldwide EATON Diesel Plus Diesel Engine Fire Pump Controller O M Manual IM05805019K 002 Effective April 2015...

Страница 14: ...ts 9 4 3 2 Control Input Descriptions 9 4 3 3 Loss of DC Power 10 4 3 4 Speed Switch Malfunction 10 4 3 5 Engine Starter Coil Failure 10 4 3 6 Audible Alarm Silencing 10 4 3 7 Power Failure Alarm 10 4...

Страница 15: ...dian Standards Association CSA New York Department of Buildings NYSB and meet CE and U B C C B C Seismic approval requirements 2 INSTALLATION AND ELECTRICAL CONNECTIONS 2 1 Mounting Carefully unpack t...

Страница 16: ...er is fully electronic and will protect itself by shutting down during a short circuit condition The maximum current draw that the chargers will draw when operating at 100 charging rate is 12 Volt Sys...

Страница 17: ...4 Volt battery charger cycle with NiCad batteries set DIP switches 3 and 6 to the ON position and all other DIP switches to the OFF position 3 1 7 Forced Charging There is provision for the battery ch...

Страница 18: ...uge Valve This green LED will be illuminated after receiving a start signal from special starting equipment This is a normally closed contact that is required to be opened to start A factory installed...

Страница 19: ...he LED s on the operator panel Pressing and holding this button will illuminate each LED on the operator panel in successive steps Reset Save Exit The reset save exit button serves two functions Press...

Страница 20: ...engine will automatically stop in the case of an OVERSPEED condition All alarms except for FAIL TO START are active in the MANUAL mode CAUTION Only depress Crank 1 or Crank 2 pushbuttons with control...

Страница 21: ...e Control Input state definitions are as follows Connected When the input is shorted by an external contact or connection Unconnected When the input is NOT shorted by an external contact or connection...

Страница 22: ...alls below its pre set level this relay will energize 4 4 2 Future 1 Future 2 The two Form C relays can be programmed for a number of alarm or status conditions Refer to Appendix E b for programming d...

Страница 23: ...roller will initiate a start sequence Pressure Stop Point The value programmed determines the pressure the system must reach before the controller will automatically stop the fire pump motor via the r...

Страница 24: ...automatically stop the engine after a programmed time It can be programmed to operate based on either of two separate conditions the stop pressure point or when the engine has started to run If the R...

Страница 25: ...delay the time before the alarm becomes active Default value is 0 seconds Range is 0 500 seconds The timer will reset if the input is removed before the time has timed out Custom Outputs The optional...

Страница 26: ...me Pressing the up or down arrow buttons will allow navigation showing the most recent message to the oldest message Refer to Appendix L for common messages and their meaning Refer to Section 7 to sav...

Страница 27: ...irst selection is Save to USB Press the Ack Alarm button and the controller will save the information to the USB storage device There will be five 5 files saved to the storage device Refer to Table 6...

Страница 28: ...line of the display The message can be up to one hundred 100 characters in length Column B contains the message type reference number Refer to Table 7 for the message types Column C and D are used to...

Страница 29: ...Events Number Event Number Event 1 Battery 1 2 Failure 16 Relief Valve Open 2 Charger 1 2 Failure 17 Transmitter Failure 3 AC Failure 18 Pump Room Trouble 4 Low Oil Pressure 19 Controller Trouble 5 Hi...

Страница 30: ...MPANY www chfire com APPENDIX A MAIN MENU TREE MENU PASSWORD LANGUAGE REGIONAL SETTINGS PRESSURE SETTINGS TIMER VALUES CUSTOM INPUT OUTPUT SYSTEM CONFIG MENU MAIN MENU PASSWORD ACK ACK SELECT LANGUAGE...

Страница 31: ...il 2015 EATON INDUSTRIES CANADA COMPANY www chfire com 19 APPENDIX B REGIONAL SETTINGS MENU TREE REGIONAL SETTINGS CHANGE DATE CHANGE TIME ACK ACK SET MONTH ACK SET HOUR ACK SET DAY SET YEAR SET DAY O...

Страница 32: ...MENU ITEM NEXT MENU ITEM ACK LOW PRESSURE ALARM ACK SET LOW PRESSURE ALARM ACK MENU HOURLY PRESSURE RECORDING ACK SET HOURLY PRESSURE RECORDING ACK MENU HIGH PRESSURE ALARM ACK SET HIGH PRESSURE ALARM...

Страница 33: ...ET RUN PERIOD TIMER ACK SET RPT START MODE ACK SET DAY SET TIME SET TEST INTERVAL ACK ACK ACK ACK NEXT MENU ITEM NEXT MENU ITEM MENU MENU NEXT MENU ITEM SEQUENTIAL START TIMER ACK SET SEQUENTIAL START...

Страница 34: ...Fire Pump Controller 22 EATON INDUSTRIES CANADA COMPANY www chfire com APPENDIX E CUSTOM INPUT OUTPUT MENU TREE CUSTOM INPUT OUTPUT CUSTOM INPUTS CUSTOM OUTPUTS ACK ACK GO TO APPENDIX E a ACK GO TO A...

Страница 35: ...ELAY TIM ER A C K M EN U C O M M O N ALAR M R ELAY A C K SET C O M M O N ALAR M R ELAY A C K M EN U LIN K TO R ELAY A C K SET LIN K TO R ELAY A C K N EXT M EN U ITEM M EN U LIN K TO LIG H T A C K SET...

Страница 36: ...M OUTPUTS MENU TREE CUSTOM OUTPUTS SELECT RELAY SELECT ALARM TYPE ACK MENU MENU NEXT MENU ITEM AUDIBLE ALARM ACK SET AUDIBLE ALARM ACK MENU FAIL SAFE ACK SET FAIL SAFE ACK MENU DELAY TIMER ACK SET DEL...

Страница 37: ...nual IM05805019K 002 Diesel Engine Fire Pump Controller Effective April 2015 EATON INDUSTRIES CANADA COMPANY www chfire com 25 APPENDIX E c CUSTOM LIGHTS MENU TREE CUSTOM LIGHTS SELECT LIGHT SELECT TY...

Страница 38: ...ive April 2015 Diesel Engine Fire Pump Controller 26 EATON INDUSTRIES CANADA COMPANY www chfire com APPENDIX F MAIN MENU PASSWORD MENU TREE MENU MAIN MENU PASSWORD SELECT PASSWORD ACK ACK SELECT BUTTO...

Страница 39: ...2015 EATON INDUSTRIES CANADA COMPANY www chfire com 27 APPENDIX G CUSTOM MESSAGE LOAD ACTIVATION DATA SELECT CUSTOM MESSAGES SELECT LOAD ACK ACK CUSTOM MESSAGES WILL BE UPLOADED DATA SELECT CUSTOM ME...

Страница 40: ...ire Pump Controller 28 EATON INDUSTRIES CANADA COMPANY www chfire com APPENDIX K For control wiring use 14 AWG wire for all electrical connections except battery connections For battery connection ter...

Страница 41: ...nal has been received from the engine Engine Stopped The engine run signal is no longer being received Engine Test Start The engine has started on an engine test Engine Test Fail An Engine Test has be...

Страница 42: ...will be delayed by the number of seconds programmed 9 2 Manual Start Test Turn the mode selector switch to the Manual position Press the Crank 1 pushbutton The Engine will crank and start the Engine...

Страница 43: ...on The engine will stop NOTE Engine will shutdown if Low Oil Pressure High Water Temp or Overspeed alarms are detected during the engine test 9 4 Weekly Exerciser Test Turn the mode selector switch to...

Страница 44: ...dd to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and EATON NO WARRANTIES EXPRESSED OR IMPLIED INCLUDIN...

Отзывы: