Step 6
Center the splice body over the compression connector,
using the raised areas on the cable entrances of the splice
body as indicators. (See Figure 6.) Run one of the neutral
wires from cable #2 through the drain wire tabs on both
ends of splice as shown. Ensure neutral wires are twisted
tightly to grounding tab. Terminate this neutral wire in the
concentric neutral compression connector.
Bundle both sets of concentric wires into a single conductor
and jumper across the splice body.
Using the appropriate compression connector (user
supplied), connect the concentric neutrals together.
Step 7
Slide the rejacketing sleeve into place so that it covers the
entire area that was exposed when the cable jacket was
originally removed. Install the rejacketing sleeve per the
manufacturer's recommended instructions.
Figure 6. Cutaway of installed splice.
CONCENTRIC NEUTRAL
CONNECTED TOGETHER
SINGLE CONCENTRIC NEUTRAL
(BOTH ENDS)
CENTER SPLICE BETWEEN BUMPS
Table 2. Typical Crimping Tools
Connector
Size
Connector
O. D.
(Inches)
Mfg.
Tool
Die
#3 Str.
Thru
3/0 Sol.
0.640
(16 mm)
Burndy
MD-6
Y35
W-BG
U-BG
Kearney
O
5/8"
620
H1 H2
H3
9/16"
T & B
EEI Equiv.
OD58
5/8"
8A
3/0 Str.
Thru
250 Comp.
0.775
(20 mm)
Burndy
MD-6
Y35
W247
U27ART
Y 35 Y39
Y45 Y47
U247
U27ART
Kearney
O
737
747
H1 H2
H3
737
747
T&B
TBM-15
66R
Alcoa
12A
839EA
EEI Equiv.
10A
Table 1. Measurement Guide
0.775"
(20 mm)
0.640"
(16 mm)
0.775" DIA.
(20 mm)
SHOWN
2
1
/
8
"
(54 mm)
Compression Connector
O.D. Measurement Guide
Compression Connector
Length Guide
ote:
N
Install as many crimps as possible without
overlapping. Rotate each successive crimp 90° to
prevent distortion.
4
15 KV AND 25 KV CLASS EZ II SPLICE INSTALLATION INSTRUCTIONS
MN650007EN January 2016