4 Maintenance
ESR5-BWS-31-24VDC
11/23 MN049020EN Eaton.com
32
●
○
●
The sensor circuit is active. The
reset/start circuit (S34) is/was
activated. Both safety circuits
K1 and K2 are not picking up
S34 manual reset error
(stuck-at
on input).
Fix the problem in the reset/start circuit.
Then carry out a functional test.
The sensor circuit is active. The
reset/start circuit (S34) is/was
activated. The safety circuit (K1)
does not pick up.
External error:
The sensor circuit channels were not both
opened / requested.
Internal error:
Diagnostics active.
External error:
Check whether the second channel is
opened with the sensor's request.
Internal error:
Perform a power-down reset followed by a
function test.
If the error occurs again
after the function test, replace the
device.
●
●
○
The sensor circuit is active. The
reset/start circuit (S34) is/was
activated. The safety circuit (K2)
does not pick up.
External error:
The sensor circuit channels were not both
opened / requested.
Internal error:
Diagnostics active.
External error:
Check whether the second channel is
opened with the sensor's request.
Internal error:
Perform a power-down reset followed by a
function test.
If the error occurs again
after the function test, replace the
device.
Legend:
○
– LED o
ff
,
●
– LED on
LED
State
Possible cause
Remedy
Power
K1
K2