background image

 
 

INSTALLATION SPECIFICATION 

 

Eaton Industries Pty Ltd 

 

August 2010 

10 Kent Road, Mascot, NSW 2020, Australia 

 

Page 

5

 of 

13

 

 

 

DOCUMENT# 510091 

4. Fit unit to mounting surface 

Follow the instructions – either 4.1 or 4.2 depending upon enclosed or gear-tray models. 

Please ensure you remove all internal shipping and packaging materials! 

4.1 Enclosure models 

F

 

Note that mounting brackets may be used in 2 positions. At least one pair of brackets must be fitted 

in the vertical position to prevent skewing, preferably the upper pair. Determine the bracket 
positions before marking the mounting surface. 

F

 

Mark the surface where drilling is to take place.  

F

 

Install mounting anchors appropriate for the mounting surface. Refer to unit weight in the technical 

specifications (supplied with unit). For safety, one anchor should be capable of supporting this 
weight alone.  

F

 

Attach the mounting brackets using the short M8 fasteners supplied.  

F

 

Using a suitable lifting device or a team of persons, lift the unit into position and secure to the 

mounting surface. Assure that all mountings are made secure and the unit is solid. 

F

 

At this point, fit cable mounting plates or brackets as required for cable installation.  

4.2 Gear-tray models 

F

 

Determine the mounting position. Unit shall be located such that it has 150mm clearance on the 
sides, top and bottom, and that adequate clearance exists at the front. 

F

 

Mark the surface where drilling is to take place.  

F

 

Attach the unit to the mounting surface using 4x M8 or 5/16” fasteners.  

F

 

Assure that all mountings are made secure and the unit is solid. 

F

 

At this point, fit cable mounting plates or brackets as required for cable installation.  

Unit is now mounted, ready for cable installation. 

Completed by: 

 

Date: 

 

 

 

Содержание ESF Series

Страница 1: ...t or require clarification of any issue please contact your local Eaton distributor or office PREPARATION FOR INSTALLATION Prior to installation please read the following application statement then fo...

Страница 2: ...Mounting location for geartray models is more than 150mm from any surface to the sides top and bottom with adequate clearance at the front for installation with the cable cover in place F Mounting lo...

Страница 3: ...Input and output cables must be kept well apart Minimum distance is 300mm F IF INSTALLED IN A SWITCHBOARD THE LOAD EARTH IS TO BE DIRECTLY CONNECTED TO MAIN SYSTEM EARTH NOT THIS UNIT F Ensure that y...

Страница 4: ...ect may be required prior to commissioning or the actual commissioning may be carried out or witnessed by an energy authority representative For these reasons ensure that the enclosed instructions are...

Страница 5: ...ed with unit For safety one anchor should be capable of supporting this weight alone F Attach the mounting brackets using the short M8 fasteners supplied F Using a suitable lifting device or a team of...

Страница 6: ...INSTALLATION SPECIFICATION Eaton Industries Pty Ltd August 2010 10 Kent Road Mascot NSW 2020 Australia Page 6 of 13 DOCUMENT 510091...

Страница 7: ...INSTALLATION SPECIFICATION Eaton Industries Pty Ltd August 2010 10 Kent Road Mascot NSW 2020 Australia Page 7 of 13 DOCUMENT 510091...

Страница 8: ...INSTALLATION SPECIFICATION Eaton Industries Pty Ltd August 2010 10 Kent Road Mascot NSW 2020 Australia Page 8 of 13 DOCUMENT 510091...

Страница 9: ...this case the normal safety earthing conductor should still be connected at the supply point Ensure that the correct wiring diagram is followed for each model Refer to the diagrams on the preceding pa...

Страница 10: ...ing is required fit the 16mm cable gland removing the blanking plug first F Connect alarm cable must be double insulated through the 16mm cable gland F Using self adhesive cable tie holders secure ala...

Страница 11: ...the master switch if applicable Power should now be applied to the unit F After a short period 5 seconds there should be a blue indicator visible through the window on the door panel Be aware of any...

Страница 12: ...e would like to hear from you if you have any suggestions or complaints regarding our products Please contact your supplier to discuss the matter Finalised by Date Warranty Eaton Industries warrants t...

Страница 13: ...______________________________________________________________________ ______________________________________________________________________ _________________________________________________________...

Отзывы: