EMR-4000
IM02602009E
Forcing Analog Inputs*
* = Availability depends on ordered device.
The parameters, their defaults, and setting ranges have to be taken from
Analog Inputs section.
Principle – General Use
The User MUST ENSURE that the Analog Inputs operate normally after
maintenance is completed.
For commissioning purposes or for maintenance, Analog Inputs can be set by force.
Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Analog Inputs], Analog Inputs can be set by force:
Permanent; or
Via timeout.
If they are set with a timeout, they will keep their “Forced Value” only as long as this timer runs.
If the timer
expires, the
Analog Input will operate normally.
If they are set as »
Permanent«, they will keep the “Forced Value” continuously.
This menu will show the current value that is fed to the Analog Input until the User activates the force mode by calling
up the »
Function«. As soon as the force mode is activated, the shown value will be frozen as long as this mode is
active. Now the User can force the Analog Input value. As soon as the force mode is deactivated, measured value will
be shown again.
www.eaton.com
810
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...