If you need more information on installing a Profibus-DP network, see “Profibus Planning 

Guideline” available from Profibus.org.   

„

 

Data mapping to the DP network: 

X20~X57

4 bytes output

Y20~Y57

4 bytes input  

            ELC-Pxxxxxxx

ELC-COPBDP

From DP Master

 To DP Master

 

The ELC-COPBDP provides a fixed 4bytes of input data and 4bytes of output data that are 

exchanged with a Profibus master.   

The 4bytes of input data are transmitted from the ELC-COPBDP module to the Profibus 

Master. This data is automatically taken from the output relays (Y) assigned to the extension 

unit. For example if the ELC-COPBDP is the first extension unit, the 4 bytes of data come 

from Y20-Y57 of the ELC controller.. 

The 4bytes output data are transmitted from the Profibus Master to the ELC-COPBDP 

module. This data is automatically placed in the input points (X) assigned to the extension 

unit. For example if the ELC-COPBDP is the first extension unit, the 4 bytes of output data is 

placed in X20-X57 of the ELC controller. 

„

 

Example ladder program : 

M1000

MOV

K4X20

D10

MOV

MOV

MOV

K4X40

D20

D21

K4Y40

K4Y20

D11

 

This program example copies the 4 bytes data from X20-X57 that are transmitted by the 

Profibus-DP master to D10 and D11 registers in the ELC controller. It also copies ELC 

register D20 and D21 to Y20-Y57. These 4 bytes data are sent to the Profibus-DP master. 

 
 

Содержание ELC-COPBDP

Страница 1: ...ELC COPBDP Effective December 2010 Users Manual ...

Страница 2: ......

Страница 3: ...witched on 3 Please read this manual carefully and follow the instructions to avoid damage to the product or personal injury Table of Contents 1 Introduction 2 2 Specification 2 3 Product Profile and Outline 3 4 Installation and Wiring 4 5 Application Description 6 Microsoft and Windows Internet Explorer are the registered trade mark or trade mark of Microsoft Corporation in the United States and ...

Страница 4: ...d slaves z Support Auto Baud rate detection z Support 12MHz baud rate z Cyclical data size is fixed to 4bytes input and 4bytes output z Provides GSD file for configuration using 3rd party tools 2 Specification Profibus DP physical and transport layer Interface DB9 9 pin connector Transfer method High speed RS485 Transfer cable 2 wire twisted shielded cable Electrical isolation 500VDC Message types...

Страница 5: ...a Agency certification UL508 UL1604 Class1 Div2 Operating temperature code T5 European community EMC Directive 89 336 EEC and Low Voltage Directive 73 23 EEC 3 Product Profile and Outline ELC COPBDP x16 x16 NE T POW ER 1 2 3 5 4 1 Power LED 2 Net LED 3 Extension port 4 Address switch 5 Profibus connector Dimension 60 ELC COPBDP x16 x16 63 4 90 25 2 3 Unit mm ...

Страница 6: ...pen the extension cover with a screwdriver Use a screwdriver to lift and unfasten the extension clips Connect the ELC COPBDP to the extension port of the ELC controller and fasten the extension clips 0 1 STOP ELC PC12NNDR RUN RUN BAT LOW ERROR POWER RS 232 RS 485 POWER C0 X7 Y0 C1 Y1 Y2 Y3 C2 ELC CDPBDP s X1 X2 X0 X5 X4 X3 X6 s NET x16 x16 1 0 ...

Страница 7: ...n the transmission speed PROFIBUS DP communicates at speeds from 9 6kbps to 12Mbps over distances from 100 to 1 200 meters Baud Rate bps 9 6k 19 2k 93 75k 187 5k 500k 1 5M 3M 6M 12M Length m 1200 1200 1200 1000 400 200 100 100 100 This demonstrates checking the successful connection of the extension I O using ELC software Connecting to the ELC controller Once the connection is complete the softwar...

Страница 8: ...ress Content 1 to 0x7D Valid PROFIBUS Address 0 or 0x7E to 0xFF Invalid PROFIBUS Address NET LED will rapidly blink RED when node address is at 0 0x7E 0xFF 0 x16 1 x16 5 Application Description Connecting the ELC COPBDP to the Profibus DP network The ELC COPBDP connects as a slave node on a Profibus DP network ELC COPBDP Profibus network ELC PS01 ELC PC12NNDR ELC COPBDP Y3 ELC PC12NNDR 0 1 RS 232 ...

Страница 9: ...signed to the extension unit For example if the ELC COPBDP is the first extension unit the 4 bytes of data come from Y20 Y57 of the ELC controller The 4bytes output data are transmitted from the Profibus Master to the ELC COPBDP module This data is automatically placed in the input points X assigned to the extension unit For example if the ELC COPBDP is the first extension unit the 4 bytes of outp...

Страница 10: ...ELC COPBDP 8 For more Information visit www eaton com MN05006003E MEMO ...

Отзывы: