Note:
ELC-CODNET module support auto baud rate function, when set all DR1-DR0 to ON,
ELC-CODNET will detect the baud rate of DeviceNet networks. But we do not
recommend using auto baud rate function. As you know, CAN message can be transmit
successfully, the network need two nodes is working normal at least, if all nodes use
auto baud rate function, then no one node can go online in DeviceNet network. So we
recommend you’d better use fixed baud rate setting in DeviceNet networks.
IN0-IN1 meaning as follow:
IN0
ON – Hold the input and output buffer data when unit loss the
DeviceNet communication.
OFF – Clear the input and output buffer data when unit loss the
DeviceNet communication.
IN1 Reserved