ELC DeviceNet (ELC-CODNET) Instruction Manual
May 2005
For more information visit: www.EatonElectrical.com Pub. No.
MN0500300
5E
10
Applicable Units and DeviceNet Functions
RS
-4
8
5
X3
X1
X2
X6
X7
X5
X4
C1
Y0
C0
Y3
Y2
C2
EL
C
-PC
1
2
N
N
D
R
BAT.LOW
STOP
RUN
Y1
s
X0
RUN
POWER
ERROR
RS
-2
3
2
1
0
s
ELC-PS01
ELC-PS01
ELC-PC12NNDR
ELC-CODNET
DeviceNet
PC with master card
DeviceNet IO data mapping
From DeviceNet
To DeviceNet
X20~X57
Y20~Y57
4 bytes output
4 bytes input
ELC-Pxxxxxxx
ELC-CODNET
ELC-CODNET provides fixed 4bytes input data and 4bytes output data to user in
DeviceNet network. 4bytes input data are transmitted from ELC-CODNET module to
DeviceNet Master, it are mapping to Y20-Y57 in ELC controller when ELC-CODNET is
the first extension unit of ELC. 4bytes output data are transmitted from DeviceNet
Master, and it are also mapping to X20-X57 in ELC controller.
Configure ELC-CODNET to DeviceNet System
As an extension unit of ELC controller, ELC-CODNET provides an IO link of 32 inputs
and 32 outputs between the DeviceNet master and ELC controller.
One ELC-CODNET module can provide fixed 4bytes(32bits) input data and 4bytes
(32bits) output data to exchange with DeviceNet master, if need more IO data, you must
add other ELC-CODNET to ELC system.