Eaton Lighting Systems EG2-NA 9850-000225-02 6
Setup Instructions
Ethernet Network
Connect the provided RJ45 (568B) jack to an
Ethernet Switch or Wireless Router.
Configuration
iCAN Device Number
The EG2-NA is supplied with a iCANnet Device
number with Segment number 255 and a node
number in the range 1-255. Both Segment and
Node number can be changed using iCANsoft.
Power Up
The EG2-NA takes approximately 60 seconds
to be ready for use once power is applied.
Wait for the Green CAN LED to flash slowly.
The Green Power LED will double flash
continuously while EG2-NA is on. If Ethernet is
connected the Link and Data LEDs will indicate
successful connection.
Setting the IP Address
The factory set IP Address can be changed
using iCANsoft software either through a direct
PC Node connection through the iCANnet or
directly into the Ethernet port of the EG2-NA.
PC Node Method
Connect a computer running iCANsoft to the
iCAN network using an iLight/iLumin PC Node.
Search the network and load the EG2-NA into
iCANsoft.
Open the EG2-NA device and select the
Ethernet tab. Type in the desired settings.
Select OK or Apply to downoad the changes
to the EG2-NA.
To restore settings back to default, select the
‘Restore Settings’ button. Select OK or Apply
to download the changes to the EG2-NA.
NOTE: The EG2-NA default settings are to
use a fixed IP address of 192.168.0.100.
Any device used to communicate with
the EG2-NA will need to be located within
the 192.168.0.x subnet unless IP Address
settings are changed.
Factory Default IP Settings
• IP Address
192.168.0.100
•
Mask
255.255.255.0
• Default Gateway
192.168.0.1
•
DHCP
Off
Ethernet Input