Eaton Lighting Systems EG2-NA 9850-000225-02 5
Supply Wiring
Connecting the Supply
This unit requires a 120-240 VAC single phase
supply (live and neutral) with 0.45 A capability.
A terminal block is used to connect the
incoming feed to the internal power supply.
Control Wiring
iCAN Network
A removable 5 position terminal block is
provided for the connection of iCAN network
cables. If the EG2-NA is located in the middle
of the network, incoming and outgoing cables
will terminate within the same connector.
iCAN Connectors
Cable type: Cooper LC or Belden 1502R or 1502P
Maximum cable length: 305m (1000’) *
Devices per segment: 100 (without bridge or
repeater)
* A maximum segment distance of 1000m (3200’) is possible
if an additional 12V power supply and bridge/repeater is used.
Wire Gauge for Supply Terminals
The live, neutral and earth ground power
connections are made to the terminal
block provided for main power connection.
Recommended cable size for live, neutral, and
earth is 26 AWG - 10 AWG.
Live (Gray)
Neutral (Blue)
Earth (Green/Yellow)
Live (Gray)
Neutral (Blue)
Earth (Green/Yellow)
Termination OFF
Termination ON
+12V
(Red)
CAN-H
(White)
SHIELD
(Gray)
CAN-L
(Blue)
0V
(Black)
iCAN
Device
iCAN
Device
EG2-NA
The EG-2-NA
has in-built
network
termination.
If the
EG-2-NA is
at the end of
the network,
ensure the
CAN TERM
jumper is
fitted in the
Termination
ON position.
iCAN devices are ‘daisy-chained’ on the
network. Spurs from the Network are not
permitted and will result in communications
problems. Devices on an iCAN network can
be wired in any order. Termination is required
at both ends of the network.
T - Indicates where a termination is required.