Eaton Lighting Systems                                                                                          EG2-NA     9850-000225-02                                 5

Supply Wiring

Connecting the Supply

This unit requires a 120-240 VAC single phase 
supply (live and neutral) with 0.45 A capability.
A terminal block is used to connect the 
incoming feed to the internal power supply.

Control Wiring

iCAN Network

A removable 5 position terminal block is 

provided for the connection of iCAN network 

cables.  If the EG2-NA is located in the middle 

of the network, incoming and outgoing cables 

will terminate within the same connector.

iCAN Connectors

Cable type: Cooper LC or Belden 1502R or 1502P

Maximum cable length: 305m (1000’) * 

Devices per segment: 100 (without bridge or 

repeater)

* A maximum segment distance of 1000m (3200’) is possible 
if an additional 12V power supply and bridge/repeater is used.

Wire Gauge for Supply Terminals

The live, neutral and earth ground power 
connections are made to the terminal 
block provided for main power connection. 
Recommended cable size for live, neutral, and 
earth is 26 AWG - 10 AWG.

Live (Gray)

Neutral (Blue)

Earth (Green/Yellow)

Live (Gray)

Neutral (Blue)

Earth (Green/Yellow)

Termination OFF

Termination ON

+12V

(Red)

CAN-H

(White)

SHIELD

(Gray)

CAN-L

(Blue)

0V

(Black)

iCAN

Device

iCAN

Device

EG2-NA

The EG-2-NA 

has in-built 

network 

termination.  

If the  

EG-2-NA is 

at the end of 

the network, 

ensure the 

CAN TERM 

jumper is 

fitted in the 

Termination 

ON position.

iCAN devices are ‘daisy-chained’ on the 

network.  Spurs from the Network are not 

permitted and will result in communications 

problems.  Devices on an iCAN network can 

be wired in any order. Termination is required 

at both ends of the network.

T  - Indicates where a termination is required.

Содержание EG2-NA

Страница 1: ...EG2 NA Ethernet Gateway Installation guide Eaton Lighting Systems...

Страница 2: ...ure that all wiring used conforms fully to local specifications and is sufficiently rated for the installation All new wiring must be fully verified before applying power The high voltage supply shoul...

Страница 3: ...2 NA houses internal webserver pages that allow for basic scene control functions These internal pages are accessed through an internet browser and are password protected for security The EG2 NA also...

Страница 4: ...ese be blocked Allow 50mm 2 above and below the unit if trunking with a depth greater than 50mm 2 is used Mounting Holes The unit is provided with four 6mm 1 4in diameter fixing holes for wall mountin...

Страница 5: ...00 is possible if an additional 12V power supply and bridge repeater is used Wire Gauge for SupplyTerminals The live neutral and earth ground power connections are made to the terminal block provided...

Страница 6: ...be changed using iCANsoft software either through a direct PC Node connection through the iCANnet or directly into the Ethernet port of the EG2 NA PC Node Method Connect a computer running iCANsoft to...

Страница 7: ...y to use a crossover cable however most current computers are able to connect directly to another Ethernet device using a standard Ethernet cable iCANsoft will be used for the configuration process Op...

Страница 8: ...reinabove limited warranty INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS No employee agent dealer or other person is authorised to give any w...

Отзывы: