Firmware upgrade procedure
Eaton®setUPS_5PX_firmware_upgrade_rev_02
Page 13/14
12. Trouble shooting
The firmware upgrade is stopped during the process :
→ restart the firmware upgrade process and the upload starts again.
The
setUPS
software doesn’t recognize your 5PX UPS : the computer installed a
wrong UPS driver (
MGE USB UPS
) :
→ you have to restart
setUPS
to have the correct driver installed (
Eaton UPS 0463-L
).
In the firmware section, the “
Upload firmware
” button is not available :
→ UPS is not powered OFF, refer to the section “
4. Power OFF the UPS
”
The display is completely blue and it is difficult to read text on it
:
Initial settings :
It is necessary to set UPS local settings, possibly before to adjust the contrast.
→ Language
Bad contrast
Good contrast (for reference)
→ Output voltage
Bad contrast Good contrast (for reference)