Connecting the serial multi-
function interface
69
02/16 MN05013001Z EN
Connection to a PC
Connect one of the following programming cables to the
COM or USB interface of your PC and to the serial multi-
function interface of the easySafety device.
Table 5:
Programming cable
for connecting to a PC
Figure 25:
Connecting the programming cable
a
to an
easySafety device
X
Remove the cover from the interface and fit the connector
plug.
Device
Programming cable
Baud rate
easySafety
EASY800-PC-CAB
up to 19.2 KBaud
easySafety
EASY800-USB-CAB
up to 57.6 KBaud
h
Caution!
When connecting the programming cable, the easySoft-
Safety programming software must be offline. On no
account should the programming cable be moved from
one easySafety device to another when the connection is
online.