User Manual

 

Safety Coupling Relay SR7D 

M03 

Ver. A 

E61-358-00 

H. ZANDER  GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Germany 

Tel +49 241 9105010 • Fax +49 241 91050138 • 

[email protected] • www.zander-aachen.de 

Safety 
Precautions 

• 

Cyclical monitoring of the output contacts 

• 

LED indicators for power and status channel 1 and 2 

• 

2 start modes: 

  -  monitored manual start 

  -  automatic start 

• 

Short-circuit monitoring and earth fault monitoring 

• 

Up to PL e, SILCL 3, category 4 

• 

Stop category: 0 

Correct Use 

SR7D is a safety coupling relay/safety switchgear with seven safe 
relay  contacts  for  fast  and  safe  shutdown  of  hazardous  plant 
components in the event of danger. It can be used in particular 
for furnaces and thermal process plants.  

The device can be operated as a coupling relay for connection to 
safe semiconductor outputs (e.g. output of a safety PLC). Due to 
the integrated self-monitoring, no feedback loop is required for 
error monitoring.  

The  SR7D  is  specially  designed  and  certified  for  the  use  on 
furnaces  and  thermal  process  plants  in  continuous  operation 
according to EN 50156-1 and EN 746-2. 

• 

7 safety contacts 

• 

4 auxiliary contacts (relay); 2 solid-state auxiliary outputs 

• 

Connection of sensors for: 

• 

    -  temperature 
    -  pressure 
    -  volume flow 

• 

Control: single or dual channel 

• 

Can be used as emergency stop relay with separate 
safety circuit 

• 

Feedback loop for external contactors or extension    
modules    

Function 

The  emergency  stop  safety  switching  device  SR7D  is 
designed  for  safe  isolation  of  safety  circuits  according  to 
EN 60204-1 and can be used up to SIL 3 according to IEC 
61508  and  safety  category  4,  PL  e  according  to  EN  ISO 
13849-1. 
When  the  control  signal  is  switched  on  or  off,  the  safety 
contacts  are  closed  or  opened  by  the  internal  logic  of  the 
SR7D.  The  SR7D  can  also  be  used  as  a  classic  emer-
gency-stop  relay  by  appropriate  wiring.  In  this  case,  the 
safety  contacts  are  closed  by  closing  the  emergency  stop 
circuit  and  a  proper  start  command.  Opening  the  emer-
gency stop circuit immediately opens the safety contacts. 
It  is  ensured  that  a  single  fault  does  not  lead  to  a  loss  of 
the safety function and that every fault is detected by cycli-
cal  self-monitoring  no  later  than  when  the  system  is 

Installation 

As per EN 60204-1, the device is intended for installation in 
control  cabinets  with  a  minimum  degree  of  protection  of 
IP54. It is mounted on a 35 mm mounting rail according to                
EN 60715 TH35. 
The load curves (see page 4) specify the maximum permis-
sible  total  thermal  current  as  a  function  of  the  ambient 
temperature.  

Fig. 2  Mounting / Demounting 

Electrical 
Connection 

• 

A safety transformer according to EN 61558-2-6 or a 
power supply unit with electrical isolation from the mains 
must be connected 

• 

Observe the instructions in the section “Tech. Data” 

• 

Use adequate protective circuit for inductive loads (e.g. 
free-wheeling diode) 

• 

If the device does not function after commissioning, it 
must be returned to the manufacturer unopened. Open-
ing the device will void the warranty 

• 

The  auxiliary  outputs  81-82,  91-92,  101-102,  101-112 
and O1, O2  may not be used as safety contacts 

Fig. 3  Terminals 

 

• 

It is not allowed to open the device, tamper with the de-
vice or bypass the safety devices. 

• 

All relevant safety regulations and standards are to be 
observed. 

• 

The overall concept of the control system in which the 
device is incorporated must be validated by the user. 

• 

Failure to observe the safety regulations can result in 
death, serious injury and serious damage. 

• 

Note down the version of the product (see label “Ver.”) 
and check it prior to every commissioning of a new de-
vice. If the version has changed, the overall concept of 
the control system in which the device is incorporated 
must be validated again by the user. 

• 

Installation and commissioning of the device must be 
performed 

only by authorized personnel

 and who has 

read and understood this operating instructions. 

• 

Observe the country-specific regulations when installing 
the device. 

• 

The electrical connection of the device is only allowed to 
be made with the device isolated. 

• 

The wiring of the device must comply with the instruc-
tions in this operating instructions, otherwise there is a 
risk that the safety function will be lost. 

• 

The contact protection and the insulation of the supply 
cables must be designed for the highest voltage to the 
device. 

switched off and switched on again. The operating status of 
the  device  is  signalled  via  the  semiconductor  monitoring 
outputs O1 and O2 (reference potential: 0V terminal). 

O1: Device ready for operation, PWR (UB) applied. 

O2: Both relays K1 and K2 are switched on. 

Fig. 1 Block diagram SR7D 

A1:  

Power Supply 

A2 : 

Power Supply 

S11:  

DC 24 V control voltage 

S10:  

Control line 

S12: 

Control line 

S13: 

Control line 

S14: 

Control line 

S21: 

Control line Start 

O1;O2: 

Solid-state aux. outputs 

0V: 

Ref. potential O1/O2 

81-82: 

Auxiliary contact 

91-92: 

Auxiliary contact 

101-102:  Auxiliary contact 
101-112:  Auxiliary contact 
13-14 ..  
73-74: 

Safety contacts 1 to 7 

English Translation 

Errors and technical changes reserved

 

Pwr: AC/DC 24V 