Reaction time of an ea
s
ySafety
device
613
02/16 MN05013001Z EN
– Transistor output: 150 ms + 1 ms = 151 ms
– Relay output: 150 ms + 50 ms = 200 ms
If the calculated circuit diagram processing time is longer
than the detetction time of the easySafety device (150 ms),
the following applies in regard to the reaction time:
Reaction time = circuit diagram processing time + output
delay
– Transistor output:
circuit diagram processing time (ms) + 1 ms
– Relay output:
circuit diagram processing time (ms) + 50 ms
Table 30:
Maximum circuit diagram processing time as a func-
tion of the number current rungs
1) The maximum circuit diagram processing time is achieved
under maximum load, i.e. the following conditions are
applied to the maximum utilization of the system in addition
to the configuration with safety and standard circuit
diagram:
• Device in the NET with seven other stations.
• Maximum data volume on the NET through the use of the
maximum number of PUT and GET standard function
Number of circuit
connections
Max. circuit diagram processing
time
1)
[ms]
1 - 39
100
40 - 79
135
80 - 119
170
120 - 159
205
160 - 199
245
200 - 239
275
240 - 253
300