Appendix
10/10 MN05003003Z-EN
100
Relay outputs
Number of outputs
6
Parallel switching of outputs to increase performance
Not permissible
Protection of an output relay
Miniature circuit-breaker B16
A
16
or fuse (slow-blow)
A
8
Electrical isolation
Yes
Safe isolation
V AC
300
Basic insulation
V AC
600
Mechanical lifespan
Switch
operations
10
x
106
Contacts relays
Conventional therm. current
A
8
Recommended for load at 12 V AC/DC
mA
> 500
Protected against short-circuit cos
v
= 1
Characteristic B (B16) at 600 A
A
16
Protected against short-circuit cos
v
= 0.5 bis 0.7
Characteristic B (B16) at 900 A
A
16
Rated impulse withstand voltage
U
imp
contact coil
kV
6
Rated insulation voltage
U
i
Rated operational voltage
U
e
V AC
250
Safe isolation to EN 50178 between coil and contact
V AC
300
Safe isolation to EN 50178 between two contacts
V AC
300
Making capacity, IEC 60947
AC-15 250 V AC, 3 A (600 Ops/h)
Operation
s
300000
DC-13 L/R
F ?
?
0 ms 24 V DC, 1 A (500 Ops/h)
Switch
operations
200000
Breaking capacity, IEC 60947
AC-15 250 V AC, 3 A (600 Ops/h)
Switch
operations
300000
DC-13 L/R
F
150 ms 24 V DC, 1 A (500 ops/h)
Switch
operations
200000
Filament bulb load
1000 W at 230/240 V AC
Switch
operations
25000
500 W at 115/120 V AC
Switch
operations
25000
Fluorescent tube load, 10
x
58 W at 230/240 V AC
Fluorescent tubes
- with ballast
- with conventional compensation
- uncompensated
Switch
operations
25000
Содержание easyControl EC4-200
Страница 4: ...II...
Страница 10: ...10 10 MN05003003Z EN 6...
Страница 14: ...10 10 MN05003003Z EN 10...
Страница 22: ...10 10 MN05003003Z EN 18...
Страница 38: ...10 10 MN05003003Z EN 34...
Страница 62: ...10 10 MN05003003Z EN 58...
Страница 78: ...10 10 MN05003003Z EN 74...