12 Appendix
12.3 Technical data
346
Control Relay easy800
11/11 MN04902001Z-EN
www.eaton.com
12.3.3 Power supply
12.3.3.1 AC Power supply
12.3.3.2 Voltage supply: DC
EASY8..-AC-..
Rated operational voltage
Rated value (sinusoidal)
Ue
V AC,
(%)
100/110/115/120/230/240 AC (+10/-15)
permissible range
V AC
85 - 264
Frequency, tolerance
Hz (%)
50/60 (± 5)
Input current consumption
At 115/120 V AC 60 Hz
m A
Normally 70
at 230/240 V AC 50 Hz
m A
Normally 35
Voltage dips, IEC/EN 61131-2
ms
20
Heat dissipation
At 115/120 V AC
VA
Normally 10
at 230/240 V AC
VA
Normally 10
EASY8..-DC-.., easy800-SWD
Rated operational voltage
Rated value U
e
V DC,
(%)
24 DC (-15/+20)
permissible range
1)
V DC
20.4 - 28.8
Residual ripple
%
5
Protection against polarity
reversal
yes
Input current
At rated operating voltage
m A
easy800 standard: 140
EASY802-DC-SWD: 500
EASY806-DC-SWD: 900
Inrush current and duty factor
easy800-SWD: 12.5 A for 6 ms
Voltage dips (IEC/EN 61131-2)
ms
10
Heat dissipation
At 24 V DC
W
easy800 standard: normally 3.4
EASY802-DC-SWD: max 5
EASY806-DC-SWD: max. 6
Fuse
A
1 to 4
easy800-SWD:
3
1) Use power feed modules
if the cable length of the SWD line causes excessive voltage drop.
Содержание easy800
Страница 1: ...11 11 MN04902001Z EN replaces AWB2528 1423GB Manual Control Relay 800 4 patpks nycmyn...
Страница 4: ...2...
Страница 16: ...0 About This Manual 0 5 Writing conventions 12 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 138: ...4 Wiring with 800 4 7 Working with function blocks 134 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 300: ...7 SmartWire DT 7 4 Errors on the SWD line 296 Control Relay easy800 11 11 MN04902001Z EN www eaton com...
Страница 336: ...10 Diagnostics possibilities 10 4 Transistor output 332 Control Relay easy800 11 11 MN04902001Z EN www eaton com...