7. Technical Data

Eaton Arc Flash Relay System

   MN026010EN   March 2016   www.eaton.com

7. Technical Data

7.1 Protection Stages

Trip Time Using HSO

2 ms*

Trip Time Using Mechanical Trip Relays

7 ms*

Reset Time (Light Stage)

1 ms 

Reset Time (Over-current Stages)

50 ms

Protection Operational After Power Up

50 ms

* = Total trip time using arc light or phase/earth over-current from 

EAFR-110 and arc light.

7.2 Current Measuring Circuits

Nominal Current

1 or 5 A

Rated Frequency

2 to 1,000 Hz

Number of Inputs

3 (Phase) + 1 (Earth)

Thermal Withstand Continuous

30 A

Thermal Withstand 1 s

500 A

Thermal Withstand 10 s

100 A

Phase Over-current Setting Range

0.5 to 6 *In

Earth Over-current Setting Range

0.05 to 2 *In

Measurement Accuracy

10%

Rated AC Burden (VA)

Input Resistance 10 mΩ

Power Consumption of Current Inputs 

Circuit

<10 mΩ

7.3 Trip relays T1, T2, T3, and T4

Number

3 NO + 1 NC or 4 NO

Rated Voltage

250 Vac/dc

Continuous Carry

5 A

Make and Carry for 0.5 s

30 A

Make and Carry for 3 s

16 A

Breaking Capacity DC, When Time Constant 

L/R = 40 ms

40 W; 0.36 A at 110 Vdc

Contact Material

AgNi 90/10

7.4 High Speed Outputs HSO1 and HSO2

Number

2

Rated Voltage

250 Vdc

Continuous Carry

2 A

Make and Carry for 0.5 s

15 A

Make and Carry for 3s

6 A

Breaking Capacity DC, When Time Constant 

L/R = 40 ms

1 A/110 W

Contact Material

Semiconductor

7.5 Binary Output BO1

Rated Voltage

+24 Vdc

Rated Current 

20 mA (max)

Number of Outputs

1

7.6 Binary Inputs BI1 and BI2

Rated Voltage

24 

Rated Current 

3 mA

Number of Inputs

2

7.7 Disturbance Tests

EMC Test

CE approved and tested according to 

EN 50081-2, EN 50082-2.

Emission
- Conducted (EN 55011 class A)

0.15 - 30 MHz

- Emitted (EN 55011 class A)

30 - 1 000 MHz

Immunity 
- Static discharge (ESD) (According 

to IEC244-22-2 and EN61000-4-2, 

class III)

Air discharge 15 kV.
Contact discharge 8 kV.

- Fast Transients (EFT) (According to 

EN61000-4-4, class III and IEC801-4, 

level 4)

Power supply input 4 kV, 5/50 ns
Other inputs and outputs 4 kV,   

5/50 ns

- Surge (According to EN61000-4-5 

[09/96], level 4)

Between wires 2 kV / 1.2/50 µs.
Between wire and earth 4 kV / 

1.2/50 µs.

- RF Electromagnetic Field Test  

(According. to EN 61000-4-3, class 

III)

f = 80 to 1,000 MHz 10 V/m

- Conducted RF Field (According. to 

EN 61000-4-6, class III)

f = 150 kHz to 80 MHz 10 V

7.8 Voltage Tests

Insulation Test Voltage Acc - to IEC 60255-5 2 kV, 50 Hz, 1 min
Impulse Test Voltage Acc - to IEC 60255-5

5 kV, 1.2/50 us, 0.5 J

7.9 Mechanical Tests

Vibration Test

2 to 13.2 Hz ± 3.5 mm (0.14 in.)
13.2 to 100 Hz, ± 1.0 g (0.04 oz)

Shock/Bump Test Acc. to IEC 60255-21-2

20 g, 1,000 bumps/dir.

Содержание EAFR-110F

Страница 1: ...Eaton Arc Flash Relay System EAFR 110F EAFR 101 MN026010EN...

Страница 2: ...ICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUME...

Страница 3: ...eaker Failure 2 3 8 Communications 2 4 EATON ARC FLASH RELAY MODULES 5 5 DIMENSIONS 6 6 EATON ARC FLASH RELAY SENSORS 8 7 TECHNICAL DATA 9 7 1 Protection Stages 9 7 2 Current Measuring Circuits 9 7 3...

Страница 4: ...iv MN026010EN Eaton Arc Flash Relay System MN026010EN March 2016 www eaton com...

Страница 5: ...egrated dual trip criteria It is designed to minimize the damage caused by an arcing fault arc flash by tripping the circuit breaker sourcing the fault current Three phase instantaneous overcurrent el...

Страница 6: ...er the set time delay 3 8 Communications Because of the simplicity of the system all monitoring is done through contact outputs on the modules The advan tage of this approach is that cybersecurity iss...

Страница 7: ...Eaton Arc Flash Relay EAFR 101 EAFR 101 ERROR T1 T3 T4 T2 T4 POWER SET S1 S2 S3 S4 S5 BI1 BI2 BO1 Eaton Arc Flash Relay EAFR 101 EAFR 101 ERROR T1 T3 T4 T2 T4 POWER SET S1 S2 S3 S4 S5 BI1 BI2 BO1 Eato...

Страница 8: ...010EN March 2016 www eaton com Figure 4 Single Ended Substation Using Fiber Loop Sensors and External Current Input A T1 T2 S2 BI 1 CB CB CB S1 S3 E Series CB CB EAFR 102 ERROR T1 T3 T4 T2 T4 POWER SE...

Страница 9: ...Modules Features EAFR 110F EAFR 110P EAFR 102 EAFR 101 D 3 Phase Current Detection Yes Yes No No Ground Current Detection Yes Yes No No Maximum Point Sensors 0 12 0 12 Maximum Fiber Loop Sensors 3 0...

Страница 10: ...IP 1 TRIP 2 SEN 1 SEN 2 SEN 3 SEN 4 FIBER I IN L OUT M TRIP L1 L2 L3 Io BO1 BO2 ARC PROTECTION SET AQ 1 10 157 6 18 82 3 23 164 6 46 102 4 01 EAFR 110P ERROR POWER SET T1 T2 S1 IL1 S2 IL2 S3 IL3 S4 Ig...

Страница 11: ...ns in Millimeters inches Side View Figure 11 EAFR 101D Dimensions in Millimeters inches Side View 175 6 89 157 6 18 160 6 30 10 0 39 17 0 67 48 5 1 91 10 0 39 110 4 33 145 5 71 21 5 0 85 108 4 25 34 1...

Страница 12: ...026010EN March 2016 www eaton com 6 Eaton Arc Flash Relay Sensors Figure 13 EAFR 06 Arc Light Plastic Fiber Sensor Figure 14 EAFR 07 Arc Light Glass Fiber Sensor Figure 15 EAFR 01 A Point Sensor Figur...

Страница 13: ...Carry 2 A Make and Carry for 0 5 s 15 A Make and Carry for 3s 6 A Breaking Capacity DC When Time Constant L R 40 ms 1 A 110 W Contact Material Semiconductor 7 5 Binary Output BO1 Rated Voltage 24 Vdc...

Страница 14: ...package 7 11 Environmental Conditions Specified Ambient Service Temp Range 35 to 70 C 31 to 158 F Transport and Storage Temp Range 40 to 70 C 40 to 158 F Relative Humidity Up to 97 7 12 Approvals UL...

Страница 15: ...glass fiber sensor 20 m 65 62 ft EAFR 07 25 65C2014G04 Arc light glass fiber sensor 25 m 82 02 ft EAFR 07 30 65C2014G05 Arc light glass fiber sensor 30 m 93 43 ft EAFR 07 35 65C2014G06 Arc light glas...

Страница 16: ...rd Cleveland OH 44122 United States Eaton com 2016 Eaton All Rights Reserved Printed in USA Publication No MN026010EN TBG1274 March 2016 Eaton is a registered trademark All trademarks are property of...

Отзывы: