Specification are subject to change without notice. Copyright 2005 Eaton Power Quality Pty Ltd 

Technical Specification – DSFi 

Tvss Doc# 510067 

Page 2 of 2 

 

Web: 

http://www.powerware.com.au

 Phone: 1300 UPS UPS

 

WARNING – OBSERVE THE SUPPLY VOLTAGE LIMITATIONS 

OF THIS UNIT. FAILURE TO OBSERVE THIS WARNING WILL 

RESULT IN DAMAGE TO THE UNIT. DAMAGE FROM 

EXCESSIVE SUPPLY VOLTAGE IS NOT WARRANTABLE. 

If you experience any problems with the installation or 

commissioning, contact your Eaton representative for guidance.

INSTALLATION 

Refer to the procedure and diagram shown to connect the DSFi. 
 

PROCEDURE:

 

1. 

CHECK 

 !

Always work safely – disconnect power before making 
connections. 

 !

All wiring must be carried out by suitably qualified 
personnel according to the applicable standards. 

 !

Check for correct operating voltage and power system.  

 
This model (DSFi) is designed for TN-C and TN C-S power 
systems in the range of 200-250V. 

If your power system is 

different or a different voltage, this model is not suitable

Please contact your supplier for information. 
 

 !

Always use the correct size supply fuses or breaker(32A 
max.). 

2. 

INSTALL

 

 !

Remove  4  screws  on  face  of  unit  and  remove 
termination covers. 

 !

Fit  cable  glands  as  required.  If  glands  are  not  required, 
use a grommet to prevent cable damage.  

 !

Install unit to switchboard geartray, equipment cabinet or 
other  suitable  location.  Do  not  expose  to  direct  sun  or 
water. Allow plenty of ventilation - do not mount inside a 
small or sealed enclosure. 

3. 

CONNECT 

 !

Connect wiring - refer to connection diagram.  

 !

Use a suitably rated cable for power connections and 
6mm

2

 to 10mm

2

 cable for earth connections. 

 !

Tighten glands if fitted. If not using glands, use cable ties 
to secure cables. 

 !

Use short cables for phase, neutral and earth input 
connections or protection will be reduced.

 !

Use a suitably-rated cable for alarm connections. Cable 
should be rated for operation at the system voltage and 
should be 0.5mm

2

 to 1.5mm

2

 !

Refit termination covers and screws.

4. 

NOTES:

 !

Wiring to the unit’s input is carrying surge currents as 
well as load current. Use the shortest possible 
connection lengths. Keep input and output cables apart

 !

Maximum alarm relay resistive load is 5A.

 !

It is recommended not to connect the alarm contacts to 
AC mains circuits if possible, to prevent flashover from 
surges on the AC line. Connect to a PLC or BMS if 
available.

 !

Do not Megger test cabling with unit connected.

EARTHING 

For  proper  operation,  all  surge  filters  rely  upon  a  good  earth 

connection.  In  some  installations  the  existing  earth  system  may 

require upgrading. Important things to look for are: 

 !

The main earth wire (from earth link on switchboard to ground 

rod  or  system)  MUST  be  at  least  6mm  diameter  (preferably 

larger) and should be as short as possible.  

 !

Earth connections from the unit to earth link 

MUST

 be as short 

as possible. 

Failure to consider the above points can result in improper 
operation of the unit and possible damage to the installation. 

 

Normal connection 

 

 

Series-load connection 

- Install separate equipment earth if practical. 

 