5 Technical data
5.2 Specific rated data
DB1 variable frequency drive
11/20 MN040031EN
Eaton.com
95
5.2.4 DB1-12… device series
Size
Symbol
Unit
2D3
4D3
7D0
Rated current
I
e
A
2.3
4.3
7.0
Overload current for 60 s every 600 s
I
L
A
3.45
6.45
10.5
Overload current for 3.75 s every 600 s
I
L
A
4.03
7.53
12.25
Apparent power at rated operation 230 V
S
kVA
0.53
0.99
1.61
Apparent power at rated operation 240 V
S
kVA
0.55
1.03
1.68
Assigned motor output
at 230 V, 50 Hz
P
kW
0.37
0.75
1.5
at (220 - 240) V, 60 Hz
P
HP
0.5
1
2
Mains side (primary side):
Number of phases
single-phase or two-phase
Rated voltage
U
LN
V
200 - 10 % - 240 + 10 %, 50/60 Hz
180 - 264 ±0 %, 48 - 62 Hz ±0 %
Input current (phase current)
I
LN
A
4.5
9.1
15.5
Switching frequency (pulse frequency)
Default setting
f
PWM
kHz
8
8
8
Adjustable range
f
PWM
kHz
4 - 32
4 - 32
4 - 32
Maximum leakage current
(touch current) to ground (PE) at U
LN
: 240 V,
without motor
I
Touch
mA
< 3.5
< 3.5
< 3.5
Power loss (% n
N
/ % M
N
)
90 / 100 @ 4 kHz
P
V
W
n/s
57
113
90 / 100 @ 8 kHz
P
V
W
34
60
116
90 / 100 @ 12 kHz
P
V
W
n/s
47
119
90 / 100 @ 16 kHz
P
V
W
n/s
59
110
90 / 100 @ 24 kHz
P
V
W
n/s
59
115
90 / 100 @ 32 kHz
P
V
W
n/s
60
119
90 / 50 @ 8 kHz
P
V
W
29
32
74
50 / 100 @ 8 kHz
P
V
W
28
41
87
50 / 50 @ 8 kHz
P
V
W
25
23
56
50 / 25 @ 8 kHz
P
V
W
23
18
45
0 / 100 @ 8 kHz
P
V
W
23
27
95
0 / 50 @ 8 kHz
P
V
W
22
18
46
0 / 25 @ 8 kHz
P
V
W
21
13
50
in no-load state, (device not enabled)
P
V
W
4.3
4.3
5
Frame size
–
–
FS1
FS1
FS1B
Note: n/ s = not specified