1 DB1 device series
1.8 Voltage classes
DB1 variable frequency drive
11/20 MN040031EN
Eaton.com
21
DB1-12…
•
U
LN
= 1~, 200 (-10 %) V - 240 (+10 %) V, 50/60 Hz
•
Single-phase mains connection, rated operating voltage 230 V
•
I
e
= 2.3 - 4.3 A
•
Motor: 0.37 - 0.75 kW (230 V, 50 Hz), 1/2 - 1 HP (230 V, 60 Hz)
Figure 11: DB1-12…
DB1-32…
•
U
LN
= 3~, 200 (-10 %) V - 240 (+10 %) V, 50/60 Hz
•
Three-phase mains connection, rated operating voltage 230 V
•
I
e
= 2.3 - 7.0 A
•
Motor: 0.37 - 1.5 kW (230 V, 50 Hz), 1/2 - 2 HP (230 V, 60 Hz)
Figure 12: DB1-32…
DB1-34…
•
U
LN
= 3~, 380 (-10 %) V - 480 (+10 %) V, 50/60 Hz
•
Three-phase mains connection, rated operating voltage 400/480 V
•
I
e
= 2.2 - 4.1 A
•
Motor: 0.75 - 1.5 kW (400 V, 50 Hz), 1 - 2 HP (460 V, 60 Hz)
Figure 13: DB1-34…
Motor
L1
N
PE
U
V
W
L1/L
L2/N
M
3 ∼
I
e
BR
DC+
Brake Chopper
(FS2)
230 V (U
LN
= 1 ~ 230 V)
EMC Filter
Motor
L1
PE
U
V
W
L1/L
L2
L2/N
L3
L3
M
3 ∼
I
e
EMC Filter
230 V (U
LN
= 3 ~ 230 V)
Motor
L1
PE
U
V
W
L1/L
L2
L2/N
L3
L3
M
3 ∼
I
e
BR
DC+
Brake Chopper
(FS2)
EMC Filter
400 V (U
LN
= 3 ~ 400 V)
460 V (U
LN
= 3 ~ 480 V)