background image

IM05805008K

  

Page 3

 

 
 

 Effective November 2006 

 

 

 

2.4 Operation 

 

 

2.4.1 

Lamp Test Button 

Each remote alarm panel is equipped with a 
Lamp Test button that fully tests all lights and 
audible alarm buzzer when pressed. Operating 
the lamp test button will not change the state of 
the internal output relays 

  

2.4.2 

Supervisory and Backup Supply Voltage 

The remote alarm panels will accept both 120 
volt 50/60Hz and 240 volt 50/60Hz power 
supply on either of the supervisory and backup 
source inputs. If the supervisory source of 
supply is lost, the panel will automatically 
switch to the backup source. Both the 
supervisory and backup sources must be 
independent of each other.  

 

2.4.3 Audible 

Alarm 

When any alarm conditions are present, the 
audible alarm will sound. It will continue to 
sound until either the silence pushbutton is 
pressed, or the alarm condition is satisfied. 
 

2.4.4 Silence 

Pushbutton 

An audible alarm silencing pushbutton is 
provided that silences all active alarms when 
pressed. Pressing the button has no effect on 
the associated alarm light(s). Should a second 
alarm condition occur after the silence 
pushbutton has been pressed, the audible alarm 
will re-sound until the silence pushbutton is  
pressed again, or the alarm condition has been 
satisfied. 

 

2.4.5 

Supervisory Power Normal Light 

The supervisory power normal light indicates when 
supervisory power is available and will turn off 
when the controller switches to the backup power 
source. An audible alarm will sound when 
supervisory power is not available and will remain 
ON until supervisory power is restored, or the 
silence pushbutton is pressed. 

 

 

2.4.6 Output 

Contacts 

The FDAP-M electric remote alarm panel has five 
alarm outputs to indicate supervisory power normal, 
pump operating, phase reversal, phase failure and 
common alarm. The DFDAP-M diesel remote 
alarm panel also has five alarm outputs that indicate 
supervisory power normal, engine running, engine 
trouble, pump room trouble and controller in OFF 
mode. An additional Common Alarm relay output 
consisting of two Form-C contacts, is provided that 
energizes under any alarm condition.  Three 
additional alarm outputs are provided to indicate 
specific alarm conditions within the fire pump 
controller. 
 

2.4.7      Output Relays 

The alarm panel relays are printed circuit board 
style that plug into sockets mounted on the alarm 
panel main circuit board. They are rated for 8 amps 
/ 250VAC. They are de-energized under normal 
conditions regardless of input status selected. 
 

2.4.7 Alarm 

Inputs 

Each controller is equipped with seven user 
selectable alarm inputs. Each can be selected as 
normally open (N.O.) or normally closed (N.C.) by 
the use of jumpers on the microprocessor board. 

Содержание Cuttler-Hammer DFDAP-M

Страница 1: ...IM05805008K Effective November 2006 Instructions for EATON Cutler Hammer Microprocessor Based Remote Alarm Panels...

Страница 2: ......

Страница 3: ...PANELS 2 2 3 1 Engine Run Controller in OFF mode check 2 2 3 2 Engine Trouble check 2 2 3 3 Pump Room Trouble check 2 2 4 OPERATION 3 2 4 1 Lamp Test Button 3 2 4 2 Supervisory and Backup Voltage 3 2...

Страница 4: ......

Страница 5: ...ld meet national and local electrical codes and standards The controller should be located or so protected that they will not be damaged by water escaping from pumps or pump connections Current carryi...

Страница 6: ...nel Move the dip switch back to the original position 2 3 Diesel Remote Alarm Panels For Electrical Schematic Refer to Figure 4 Note The alarm buzzer can be silenced by pressing the Silence Alarm push...

Страница 7: ...een satisfied 2 4 5 Supervisory Power Normal Light The supervisory power normal light indicates when supervisory power is available and will turn off when the controller switches to the backup power s...

Страница 8: ...Page 4 IM05805008K Effective November 2006 ELECTRIC REMOTE ALARM PANEL FDAP M Figure 1...

Страница 9: ...IM05805008K Page 5 Effective November 2006 DIESEL ENGINE REMOTE ALARM PANEL DFDAP M Figure 2...

Страница 10: ...Page 6 IM05805008K Effective November 2006 WIRING SCHEMATIC ELECTRIC REMOTE ALARM PANEL FDAP M Figure 3...

Страница 11: ...IM05805008K Page 7 Effective November 2006 WIRING SCHEMATIC DIESEL REMOTE ALARM PANEL DFDAP M Figure 4...

Страница 12: ...Hammer 2256 29th Street NE 10 Calgary Alberta T1Y 7G4 Canada tel 403 717 2000 fax 403 717 0567 www chfire com 2006 Eaton Corporation All Rights Reserved Printed in Canada Publication No IM05805008K N...

Отзывы: