Page 2

            

IM05805008K

 

 

 Effective November 2006 

 

2.1 Electrical Checkout Instructions (For Use with Eaton Cutler-Hammer Remote Alarm  
      Panels)

 

 

WARNING

The following procedures should be carried out by a qualified electrician familiar with the electrical 
safety procedures associated with this product and its associated equipment. 

 

2.2 Electric Remote Alarm Panels (Full Service) – For Electrical Schematic Refer to Figure #3 

 

Note:

 The alarm buzzer can be silenced by pressing the ‘Silence Alarm’ pushbutton on the front of the controller. 

 
2.2.1 

- Turn power on to the Fire Pump Controller and to the Remote Alarm Panel 

 

- In the Fire Pump Controller press the ‘Local Start’ pushbutton, the controller will start 

 

 - The ‘Pump Operating’ light should illuminate and the alarm will sound on the Alarm Panel 

 

- Press the ‘Stop’ pushbutton on the front of the fire pump controller 

 
2.2.2 

- Move the disconnect handle on the Fire Pump Controller to the ‘OFF’ Position 
- The ‘Common Alarm’ and ‘Phase Failure’ lights should illuminate and the alarm will sound on the Alarm Panel 

 

- Move the disconnect handle back to the ‘ON’ Position 

 
2.2.3   - Move dip switch #4 in the Fire Pump Controller, located on the top left hand corner of the main board, to the    

  opposite direction 

- The ‘Common Alarm’ and ‘Phase Reversal’ lights should illuminate and the alarm will sound on the Alarm     

                 Panel 
 

- Move the dip switch back to the original position 

 
 

2.3 Diesel Remote Alarm Panels – For Electrical Schematic Refer to Figure #4

 

 

Note:

 The alarm buzzer can be silenced by pressing the ‘Silence Alarm’ pushbutton on the front of the controller. 

 
2.3.1 

- Turn power on to the Fire Pump Controller and to the Remote Alarm Panel 

 

- Place the controller in the ‘AUTO’ mode by depressing the “AUTO” button 

 

- Start the controller either by jumpering the remote start (Terminal #11 & #28) or by dropping the pressure in  
  the Fire Pump Controller 

 

- The ‘Engine Run’ light should illuminate and the alarm will sound on the alarm panel 

 

- Place the controller in the ‘OFF’ mode by depressing the “OFF” button 

 

- The ‘Controller in OFF Mode’ light will illuminate and the alarm will sound on the alarm panel 

 
2.3.2 

- Place the controller in the ‘AUTO’ mode by depressing the “AUTO” button 

 

- Start the controller either by jumpering the remote start (Terminal #11 & #28) or by dropping the pressure in  

  

   the Fire Pump Controller  

 

- Place a jumper between Terminal #4 & #11 in the Fire Pump Controller (Low Oil Pressure) 

 

- The ‘Engine Trouble’ light should illuminate and the alarm will sound on the alarm panel 

 

- Place the controller in the ‘OFF’ mode by depressing the “OFF” button  

 
2.3.3 

- Place the controller in the ‘MANUAL’ mode by depressing the “MANUAL” button 
- Place a jumper between Terminal #21 & #11 in the Fire Pump Controller (Low Room Temp.) 

 

- The ‘Pump Room Trouble’ light should illuminate and the alarm will sound on the alarm panel 

 

- Place the controller in the ‘OFF’ mode by depressing the “OFF” button 

 
 
 
 
 
 
 
 

Содержание Cuttler-Hammer DFDAP-M

Страница 1: ...IM05805008K Effective November 2006 Instructions for EATON Cutler Hammer Microprocessor Based Remote Alarm Panels...

Страница 2: ......

Страница 3: ...PANELS 2 2 3 1 Engine Run Controller in OFF mode check 2 2 3 2 Engine Trouble check 2 2 3 3 Pump Room Trouble check 2 2 4 OPERATION 3 2 4 1 Lamp Test Button 3 2 4 2 Supervisory and Backup Voltage 3 2...

Страница 4: ......

Страница 5: ...ld meet national and local electrical codes and standards The controller should be located or so protected that they will not be damaged by water escaping from pumps or pump connections Current carryi...

Страница 6: ...nel Move the dip switch back to the original position 2 3 Diesel Remote Alarm Panels For Electrical Schematic Refer to Figure 4 Note The alarm buzzer can be silenced by pressing the Silence Alarm push...

Страница 7: ...een satisfied 2 4 5 Supervisory Power Normal Light The supervisory power normal light indicates when supervisory power is available and will turn off when the controller switches to the backup power s...

Страница 8: ...Page 4 IM05805008K Effective November 2006 ELECTRIC REMOTE ALARM PANEL FDAP M Figure 1...

Страница 9: ...IM05805008K Page 5 Effective November 2006 DIESEL ENGINE REMOTE ALARM PANEL DFDAP M Figure 2...

Страница 10: ...Page 6 IM05805008K Effective November 2006 WIRING SCHEMATIC ELECTRIC REMOTE ALARM PANEL FDAP M Figure 3...

Страница 11: ...IM05805008K Page 7 Effective November 2006 WIRING SCHEMATIC DIESEL REMOTE ALARM PANEL DFDAP M Figure 4...

Страница 12: ...Hammer 2256 29th Street NE 10 Calgary Alberta T1Y 7G4 Canada tel 403 717 2000 fax 403 717 0567 www chfire com 2006 Eaton Corporation All Rights Reserved Printed in Canada Publication No IM05805008K N...

Отзывы: