IM05805008K

  

Page 1

 

 

 Effective November 2006 

 

INSTALLATION & MAINTENANCE 

MANUAL FOR REMOTE ALARM 

PANELS 

 

In order to familiarize yourself with the Remote Alarm Panel, please read the instruction manual thoroughly and 
carefully.  Retain the manual for future reference. 
 

1.   Installation and Mounting of the 
Controller

 

 
Carefully unpack the controller and inspect 
thoroughly.   
 
The controller is not free standing and must be bolted 
securely to a wall.  For dimensional and weight data 
please refer to the respective data sheets for the 
Remote Alarm Panels.  
 
Figure #1 - Electric Remote Alarm Panel 
Figure #2 - Diesel Remote Alarm Panel 
 

 
2.  Electrical Connections 

 
All electrical connections should meet national  
and local electrical codes and standards. 
 
The controller should be located or so protected that 
they will not be damaged by water escaping from 
pumps or pump connections.  Current carrying parts 
of controllers shall be a minimum of 12 inches (305 
mm) above the floor level. 
 

• 

Prior to starting, verify all data on the nameplate 
such as, catalog number and AC line voltage.

 

 

• 

Inspect all electrical connections, components 
and wiring for any visible damage and correct as 
necessary.  Ensure that all electrical connections 
are tightened before energization.

 

 

• 

Install necessary conduit using proper methods 
and tools.

 

 

• 

Incoming supervisory power and backup power 
connections are clearly marked L and N and are 
located on the upper right side of the 
microprocessor board.  

 

 

• 

Ensure selector switches are set correctly to 
correspond to the incoming supply voltage – 
(120V or 240V).

 

 

 

 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание Cuttler-Hammer DFDAP-M

Страница 1: ...IM05805008K Effective November 2006 Instructions for EATON Cutler Hammer Microprocessor Based Remote Alarm Panels...

Страница 2: ......

Страница 3: ...PANELS 2 2 3 1 Engine Run Controller in OFF mode check 2 2 3 2 Engine Trouble check 2 2 3 3 Pump Room Trouble check 2 2 4 OPERATION 3 2 4 1 Lamp Test Button 3 2 4 2 Supervisory and Backup Voltage 3 2...

Страница 4: ......

Страница 5: ...ld meet national and local electrical codes and standards The controller should be located or so protected that they will not be damaged by water escaping from pumps or pump connections Current carryi...

Страница 6: ...nel Move the dip switch back to the original position 2 3 Diesel Remote Alarm Panels For Electrical Schematic Refer to Figure 4 Note The alarm buzzer can be silenced by pressing the Silence Alarm push...

Страница 7: ...een satisfied 2 4 5 Supervisory Power Normal Light The supervisory power normal light indicates when supervisory power is available and will turn off when the controller switches to the backup power s...

Страница 8: ...Page 4 IM05805008K Effective November 2006 ELECTRIC REMOTE ALARM PANEL FDAP M Figure 1...

Страница 9: ...IM05805008K Page 5 Effective November 2006 DIESEL ENGINE REMOTE ALARM PANEL DFDAP M Figure 2...

Страница 10: ...Page 6 IM05805008K Effective November 2006 WIRING SCHEMATIC ELECTRIC REMOTE ALARM PANEL FDAP M Figure 3...

Страница 11: ...IM05805008K Page 7 Effective November 2006 WIRING SCHEMATIC DIESEL REMOTE ALARM PANEL DFDAP M Figure 4...

Страница 12: ...Hammer 2256 29th Street NE 10 Calgary Alberta T1Y 7G4 Canada tel 403 717 2000 fax 403 717 0567 www chfire com 2006 Eaton Corporation All Rights Reserved Printed in Canada Publication No IM05805008K N...

Отзывы: