
I.L. 17403
Page 11
Effective 9/04
Short Circuit
Circuit Breaker Short Circuit Withstand Rating
Typical
Protective
Max. Rating
Interrupting
Disconnect
Device (SCPD)
SCPD
Rating
Current
Voltage
Device Cat. No.
150A FD-K
Class J or R
400A
-
100,000A
480V
Molded Case
Fuse
65,000A
600V
Switch
250A JD-K
100,000A
600V
Molded Case
Switch;
400A K Switch
Magnetic Only
1
150A
Marked HMCP
100,000A
480V
Type CB
2
50,000A
600V
HMCP
100,000A
100,000A
480V
Thermal/Mag
35,000A
50,000A
600V
JDC
Type CB
3
250A
65,000A
65,000A
480V
25,000A
25,000A
600V
HJD
Magnetic Only
1
150A
HMCP plus
100,000A
600V
HMCP + CL
Type CB + CL
4
Current Limiter
TABLE VII - SIZE 4 SHORT CIRCUIT RATINGS
TABLE NOTES
1
Instantaneous Adjustable Trip
2
Circuit Breaker
Use a 150VA machine tool control transformer. Protect
the coil and printed wiring board with a 2 ampere time
delay fuse. See Table VIII.
AC COIL DATA (TYPICAL VALUES)
Inrush VA
Sealed VA
Sealed Watts
500
50
10
TROUBLESHOOTING HINTS
If the controller does not operate as expected, check the
following:
a. All control power to terminals 3-P-E-C must be supplied
from the same phase.
b. Terminal P must be energized to permit the contactor
to pick up.
c. Terminals E and C must be energized to obtain a
tripped indication.
d. An overload relay in a tripped condition caused by a
phase loss or a ground fault must be reset with control
power ON.
e. Each DIP switch handle must be in the full ON or full
OFF postion.
A Type WCMU central monitoring unit can be of great
assistance in troubleshooting.
TABLE VIII - AUXILIARY CONTACTS AND TIE POINTS
Cat. No.
Contacts
Tie Points
W11T
1 NO & 1 NC
2
W13
1 NO & 3 NC
0
W22
2 NO & 2 NC
0
W31
3 NO & 1 NC
0
W40
4 NO
0
W04
4 NC
0
WTBF34
NONE
6*
NO - Normally Open, NC = Normally Closed
* Four points are color-coded and prewired for connection to
control terminals 3, P, E, and C. A 2A Buss Type MDL control
circuit fuse and two unwired tie points are included.
5
Inverse Time Circuit Breaker
with Current-Limiting
Attachment
CONTROL POWER AND TERMINALS
Advantage motor controllers require a constant source
of control power to operate and indicate a tripped condi-
tion. Loss of control power or a severe drop in control
voltage will cause an Advantage motor controller to
open.
3
= Terminal to which the START signal must be delivered
P
= Terminal which must be energized to permit operation
E
= Ungrounded side of control power source
C
= Grounded (common) side of control power source
3
Inverse Time Circuit Breaker
4
Instantaneous Adjustable Trip with Current
Limiting Attachment