2 SPECIFICATIONS

2.1 POWER RATING

POWER

200-600VAC, 50/60 Hz

CONTROL

115 VAC@50 Hz or 120 VAC@60 Hz, 10VA

RATING

Intermitent duty, See Section 2.2

300% for 30 seconds, once every 30 minutes

All models have 1600V PIV SCR's

CONTACTS

DC injection relay contacts rated at 1A, 120VAC

PROTECTION

Short circuit by HRC fuses or circuit breaker 
(supplied upon request)

Voltage surge protection by snubber's and MOV's across the SCR's

2.2 CURRENT AND FUSE RATING

CURRENT RATING

DCI

MODEL

AMPS

MOTOR 

HP @ 575 V

MOTOR

HP @ 460V

FUSE

AMPS

SCR

TYPE

TRU-020-DCI          

20

 

20

 

15

 

20

 

Module

TRU-040-DCI

        40                   40

 

30

 

40

 

Module

TRU-080-DCI  

       75                  75

 

60

 

80

 

Module

TRU-125-DCI        

125

 

125

 

100

 

125               Module

TRU-200-DCI         

200

 

200

 

150

 

200

 

Disc

TRU-300-DCI         

300

 

300

 

250

 

300

 

Disc

TRU-500-DCI         

500

 

500

 

400

 

500

 

Disc

2.2.1 NOTES

2.2.1.1 The HP listing is for reference only. For proper selection use the current rating.

2.2.1.2 The fuses recommended are Class J time-delay type. This fuse is being

suggested even though it may not protect the SCR in an output shorted
condition while braking. It will protect the unit  when starting to operate into a
shorted output. In the case of a shorted SCR, the fuse is there to clear the fault
only.

2.2.1.3 The RMS AC line current is equal to :     AC RMS = DC Amps x 

√ 

Duty Cycle

Assuming 10A motor, TRU-START DC Injection set at 300% current (30 A DC), 
free wheeling for 70% of the cycle,  then the  AC current is 16A.

2.2.1.4

 

All TRU-START DC Injection models are built without cooling fans because they 
are short duty rated.

PAGE 5

Содержание Cutler-Hammer TRU-START

Страница 1: ...r engineering services call 1 800 498 2678 or visit www cutler hammer ca Eaton Corporation is a global 7 3 billion diversified industrial manufacturer that is a leader in fluid power systems electrical power quality distribution and control automotive engine air management and fuel economy and intelligent truck systems for fuel economyand safety Eaton has 48 000 employees and sells products in mor...

Страница 2: ...epresentations included in this manual are for typical installations and should not in any way be considered for specific applications or modifications Consult Cutler Hammer for supplemental instructions Cutler Hammer Canada accepts no liability for any consequences resulting from inappropriate negligent or incorrect installation application or adjustment of this equipment The contents of this man...

Страница 3: ...MENSIONS PAGE 6 2 5 SCR INSTALLATION SPECIFICATIONS PAGE 7 2 5 1 SCR TIGHTENING PROCEDURE PAGE 7 3 CARD FUNCTIONS PAGE 9 3 1 CARD LAYOUT PAGE 9 3 2 LED AND NEON INDICATIONS PAGE 9 3 3 ADJUSTMENTS PAGE 10 3 3 1 POTENTIOMETERS PAGE 10 3 3 2 LINK SELECTION PAGE 10 3 3 3 PUSHBUTTON PAGE 10 3 4 TERMINALS PAGE 11 3 4 1 CUSTOMER TERMINALS PAGE 11 3 4 2 TERMINALS FOR INTERNAL USE PAGE 11 3 5 FAULTS PAGE 1...

Страница 4: ...EFORE POWER UP PAGE 14 4 5 2 WITH POWER ON PAGE 15 5 TYPICAL CONNECTIONS PAGE 17 5 1 STAND ALONE DC INJECTION UNIT WITH ZERO SPEED DISABLE PAGE 17 5 2 TRU START STARTER WITH DC INJECTION PAGE 18 5 3 REVERSING TRU START STARTER WITH DC INJECTION 125 AMPS AND BELOW PAGE 19 5 4 REVERSING TRU START STARTER WITH DC INJECTION 200 AMPS AND ABOVE PAGE 20 6 SPARE PARTS PAGE 21 TABLE OF CONTENTS ...

Страница 5: ...actors are required The unit adapts itself to any input voltage between 200 and 600 VAC with no adjustments required Efficient Power Circuit The power circuit is an efficient four Silicon Controlled Rectifier SCR configuration which uses some of the SCR s as a free wheeling diode thus maximizing the DC current through the motor coils generated by the AC input current With every benefit there is us...

Страница 6: ...s not recommended for continuous or repetitive operation The kinetic energy of the mechanical system is transformed into heat during braking energy conservation That heat is dissipated in the rotor of the motor On wound rotor motors the external rotor resistance will absorb most of the energy On squirrel cage motors overheating of the motor is a real danger if frequent operation is used Keeping DC...

Страница 7: ... when an instantaneous over current is detected The IOC fault is detected and latched until the Reset switch is pressed A form C relay contact is available to interlock the brake unit from the motor starter The starter cannot be energized while DC current is being applied to the motor or during a fault condition 1 3 2 CA398 3 REGULATION The brake module operates in current control at all times The...

Страница 8: ...PAGE 4 ...

Страница 9: ... 125 Module TRU 200 DCI 200 200 150 200 Disc TRU 300 DCI 300 300 250 300 Disc TRU 500 DCI 500 500 400 500 Disc 2 2 1 NOTES 2 2 1 1 The HP listing is for reference only For proper selection use the current rating 2 2 1 2 The fuses recommended are Class J time delay type This fuse is being suggested even though it may not protect the SCR in an output shorted condition while braking It will protect t...

Страница 10: ...cm 22cm 18cm 16 8 5 6 16 8 5 7 TRU 040 DCI 43cm 27cm 19cm 43cm 30cm 27cm 17 10 5 7 5 17 12 10 5 TRU 080 DCI 43cm 27cm 22cm 43cm 30cm 27cm 17 10 5 8 17 12 10 5 TRU 125 DCI 53cm 27cm 24cm 53cm 30cm 27cm 21 10 5 8 5 21 12 10 5 TRU 200 DCI 28cm 33cm 27cm 61cm 61cm 30cm 11 13 10 5 24 24 12 TRU 300 DCI 42cm 37cm 28cm 76cm 61cm 30cm 16 5 14 5 11 30 24 12 TRU 500 DCI 45cm 42cm 36cm 76cm 61cm 30cm 17 5 16 ...

Страница 11: ...rity 2 5 1 4 Install SCR so that roll pins engage dimples on both sides of the SCR 2 5 1 5 Tighten clamp bolts evenly until finger tight 2 5 1 6 Tighten each bolt according to table below based on number of spring bars and size of bars Note SMALL clamps are 4 25 inches 10 5 cm and LARGE clamps are 5 inches 12 5 cm CLAMP SIZE SPRING BARS BOLT TURNS PAST FINGER TIGHT SMALL 1 0 8 SMALL 2 1 LARGE 3 1 ...

Страница 12: ...PAGE 8 ...

Страница 13: ...NDICATIONS LED NAME COLOUR DESCRIPTION LD 1 DC INJCT RED On when unit is braking LD 2 PWR GREEN Must be On when 115 VAC is applied LD 3 IOC RED Instantaneous Over Current fault indication when illuminated NE1 PHASE OK ORANGE Phase loss indication when neon not glowing PAGE 9 C H ...

Страница 14: ...decreased to 30 of the line voltage HI Braking action starts when motor starter has opened and the motor terminal voltage has decreased to 80 of the line voltage See important notes below HI setting is only used when the stopping time is critical and must be around 1 2 seconds For this application 300 DC current is not adequate Consult factory before using this jumper position When the DC Injectio...

Страница 15: ...t exists 6 Normally open DCI relay auxiliary contact 7 Normally closed DCI relay auxiliary contact R7 1 2 Burden resistor terminals for calibration of DC injection current See table in Section 4 4 3 4 2 TERMINALS FOR INTERNAL USE TERMINAL NO DESCRIPTION J1 24V COM This terminal is used by C H as a 24V input to provide battery back up for DC injection in case of power loss J3 1 2 CURRENT FBK From c...

Страница 16: ...vent the use of the starter The faults are explained below 3 5 1 PHASE LOSS If the single phase power 200 600V to L1 and L2 terminals is not present NE1 will be off and the DCI relay de energized When this condition is corrected the unit will allow the starter to be energized 3 5 2 INSTANTANEOUS OVER CURRENT IOC If the current feedback exceeds 1000 of the current setup by the burden resistor Rb th...

Страница 17: ... result in damage to disconnecting device and or bodily injury The electrical code requires all equipment starter motor operator station brake etc to be grounded properly An incoming circuit breaker or disconnect switch must be locked open before wiring and servicing this electrical brake motor or other related equipment This equipment must be installed and serviced only by qualified personnel fam...

Страница 18: ...ons are properly tightened The most important connection is the interlock between the DC Injection unit and the starter 4 5 1 2 Ensure that the burden resistor is equal or larger than the value listed in the following table or calculated by the following equation Rb Effective Current Transformer Ratio Motor Nameplate Amps 4 5 1 3 Set JP1 link to LO 4 5 1 4 Adjust RV2 braking torque and RV1 braking...

Страница 19: ...nd the starter off If the motor reaches zero speed from the DC injection cycle close the switch to the Disable Input to disable the braking 4 5 2 2 Re adjust the braking torque pot RV2 if the actual braking time has to be increased or decreased to bring the motor to zero speed 4 5 2 3 Once the braking torque is set then adjust RV1 to match the DC injection time with the actual stopping time of the...

Страница 20: ...PAGE 16 ...

Страница 21: ...5 TYPICAL CONNECTIONS 5 1 STAND ALONE DC INJECTION UNIT WITH ZERO SPEED DISABLE PAGE 17 ...

Страница 22: ...5 2 TRU START STARTER WITH DC INJECTION PAGE 18 ...

Страница 23: ...5 3 REVERSING TRU START STARTER WITH DC INJECTION 125 AMPS AND BELOW PAGE 19 ...

Страница 24: ...5 4 REVERSING TRU START STARTER WITH DC INJECTION 200 AMPS AND ABOVE PAGE 20 ...

Страница 25: ...0SP03 CA524 CA398 3 TRU 040 DCI 1500 1 T261123 N10SP06 CA524 CA398 3 TRU 080 DCI 2500 1 T262230 N10SP16 CA524 CA398 3 TRU 125 DCI 2500 1 T262230 N20SP06 CA524 CA398 3 TRU 200 DCI 2500 1 T262230 N728452 CA232 CA398 3 TRU 300 DCI 5000 1 T265320 N718602 CA232 CA398 3 TRU 500 DCI 8500 1 T268320 N718133 CA232 CA398 3 PAGE 21 ...

Страница 26: ...PAGE 22 ...

Страница 27: ...78 for engineering services call 1 800 498 2678 or visit www cutler hammer ca Eaton Corporation is a global 7 3 billion diversified industrial manufacturer that is a leader in fluid power systems electrical power quality distribution and control automotive engine air management and fuel economy and intelligent truck systems for fuel economyand safety Eaton has 48 000 employees and sells products i...

Отзывы: