3.4 TERMINALS
3.4.1 CUSTOMER TERMINALS
TERMINAL
NO.
DESCRIPTION
J2
L1, N
115 VAC control voltage input, L1 being hot and N, neutral
L1 input is protected with internal fuse, 1A 250VAC
J4
1, 2
115 VAC supply for external interlock contacts
3
A normally open contact from the motor starter auxiliary must
be connected between this teminal and terminals 1 or 2 to sense
when the starter is de-energized to enable braking action
When using a TRU-START starter in conjuction with the DC
Injection, this terminal is to be jumpered to terminal 1 or 2
4
When 115VAC from terminals 1 or 2 is applied to this input,
braking is disabled
5
Common DCI relay contact
The Form-C relay is de-energized while braking and when a
fault exists
6
Normally open DCI relay auxiliary contact
7
Normally closed DCI relay auxiliary contact
R7
1, 2
Burden resistor terminals for calibration of DC injection current
See table in Section 4.4
3.4.2 TERMINALS FOR INTERNAL USE
TERMINAL
NO.
DESCRIPTION
J1
24V, COM
This terminal is used by C-H as a 24V input to provide
battery back up for DC injection in case of power loss
J3
1, 2
CURRENT FBK
From current transformer for motor current feedback
J5
1, 2
MOTOR VFBK
From T1, T2 motor terminals for motor voltage feedback
SCR1
G1, K1
Gate connection to SCR 1
SCR2
G2, K2
Gate connection to SCR 2
SCR3
G3, K3
Gate connection to SCR 3
SCR4
G4, K4
Gate connection to SCR 4
OPT
1-20
Provided for ribbon cable link to TRU-START starter
This provides signals from the TRU-START to the DCI that
indicate the run status of the starter, replacing the auxiliary
input and prevents starting during DC injection or a fault
PAGE 11
Содержание Cutler-Hammer TRU-START
Страница 8: ...PAGE 4 ...
Страница 12: ...PAGE 8 ...
Страница 20: ...PAGE 16 ...
Страница 21: ...5 TYPICAL CONNECTIONS 5 1 STAND ALONE DC INJECTION UNIT WITH ZERO SPEED DISABLE PAGE 17 ...
Страница 22: ...5 2 TRU START STARTER WITH DC INJECTION PAGE 18 ...
Страница 23: ...5 3 REVERSING TRU START STARTER WITH DC INJECTION 125 AMPS AND BELOW PAGE 19 ...
Страница 24: ...5 4 REVERSING TRU START STARTER WITH DC INJECTION 200 AMPS AND ABOVE PAGE 20 ...
Страница 26: ...PAGE 22 ...