Instruction Leaflet 

I. L. 29-888B

Effective July 2011

 Instructions for Digitrip RMS 810 Trip Unit

 

 

eaton corporation

 www.eaton.com

1.1.1  Operational Status and Protection TRIP Indicators

The "Green" Light Emitting Diode (LED) in the lower right corner of 

the Trip Unit (Figure 1) "blinks" once each second to indicate the Trip 

Unit is operating normally .

otee:

N

If the LED is steadily "GREEN", i .e . not blinking, the Trip Unit is not 

ready . Check the 120 VAC control power to the Power / Relay Module, if the 

LED is not blinking (see Section 1 .4 .) .

The LEDs, shown in Figures 1 and 3 thru 8 on the face of the Trip 

Unit, light "RED" to indicate the reason for any automatic trip opera-

tion .  As indicated in Figures 3 - 8, each LED is strategically located 

in the related segment of the time-current curve depicted on the 

face of the Trip Unit .  The reason for trip is identified by the segment 

of the time-current curve where the LED is lighted "RED", and is 

also identified on the Display .  Following an automatic protection trip 

operation, the external control power to the Power / Relay Module 

(see Section 1 .4) will maintain the LED "RED" and will continue to 

send a 

TRIP

 signal to 

LOCKOUT

 the circuit breaker until the Trip 

Unit is 

RESET.

  The Digitrip RMS 810 Trip Unit can be 

RESET

 in two 

ways:

• 

Either press and release the "

TRIP RESET

" button (See Figure 1 

lower right corner just above the "

UNIT STATUS

" LED);

 

 

 

or

• 

By the "Trip Reset" remote communications function (see Section 

5 .9 .) .

Figure 1. Digitrip RMS 810 Trip Unit Type LSIG with Rating Plug.

Green LED's 

Light to Identify 

Which Value Is 

Presently Being 

Displayed in 

Window

The Unit INCOM 

Address 

(Circuit Breaker 

Location References)

Catalog Number

LED's light "Red" 

to indicate cause 

of trip

Time-Current 

Curve for Ground 

Protection

SPB Rating Plug

View Settings in 

Window

Adjust Protection Settings 

for Desired Values with 

Rotary Switches

Trip Unit Operation Status 

"Blinking Green"=OK  

(See Section 1 .1 .1)

R-Frame Rating Plug

Press and Release "Trip 

Reset" Push Button to 

Reset Trip Unit

Press and Release "Test" 

Push Button to Initiate 

Self-Test (See Section 4)

Press and release "STEP" Push button 

to Display Value of Next Parameter in 

Window

Press and release "PEAK RESET" 

Push button to Reset Peak Demand 

Reading to Zero

4-Character 

Display Window

Keyed 

Receptacle 

for Auxiliary 

Power Module 

Connector (See 

Section 1 .6)

Time-Current curve for    

Phase Protection

DS Rating Plug

Содержание Cutler-Hammer Digitrip RMS 810

Страница 1: ...persedes I L 29 888A 5 97 Instruction Leaflet I L 29 888B Instructions for Digitrip RMS 810 Trip Unit BCS Switchgear Inc Switchgear Circuit Breakers Parts Tech Support bcsswitchgear com 888 599 0486 N...

Страница 2: ...7 No Instantaneous Current Setting 18 3 8 Ground Fault Current Setting 18 3 9 Ground Fault Time Delay Setting 19 4 Test Procedures 19 4 1 General 19 4 2 When To Test 19 4 3 Testing Provisions 20 4 4...

Страница 3: ...lay Time Settings 18 Figure 17 Instantaneous Current Settings 18 Figure 18 Ground Fault Current Settings 18 Figure 19 Ground Fault Time Delay Settings 19 Figure 20 Integral Test Panel Lower Right Corn...

Страница 4: ...uit breaker The Digitrip RMS 810 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 185 F and rarely exceed 70 t...

Страница 5: ...in the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 810 Trip Unit can be RESET in two ways Either press and release the...

Страница 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 8...

Страница 7: ...Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp TRIP X...

Страница 8: ...Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 810 Type LI Figure 4 Digitrip RMS 810 Type LS Figure 5 Digitrip RMS 810 Type LSI F...

Страница 9: ...e non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approximate ly ten 10 cycles following the initial current flow through the...

Страница 10: ...D TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECTED WITH JUMPER WIRES AS SPECIFIED ON THE CONNECTION DIAGRAMS FOR YOUR BREAKER SEE SECTION 6 SO THE TIME DELAY...

Страница 11: ...Power and Energy Values 1 2 1 2 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X Energy Consumption MWh Reverse Energy Consumption X X X X X X X X X...

Страница 12: ...will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Protection functions still operate but may be up to 12 out of tolerance...

Страница 13: ...breaker positive flow of power If the power flows in the opposite direction i e bottom to top the value of power will not be displayed continuously Instead the power value in the display window will a...

Страница 14: ...ttings without having to remove the circuit breaker from its enclosure For example if one expects a circuit to carry 600 A initially but then increase to 1400 A in the future one could initially insta...

Страница 15: ...IP RELAY ALARMS MAY BE ERRATIC OR NONFUNCTIONAL IF WRONG VOLTAGE IS USED The relays operate when the Trip Unit detects the following condi tions as shown in Figure 2 Short Circuit Trip Alarm High Load...

Страница 16: ...TESTS ON THE CIRCUIT BREAKER SEE ALSO THE SPECIFIC DIELECTRIC TEST PROCEDURES IN THE APPLICABLE CIRCUIT BREAKER INSTRUCTION LEAFLET LISTED IN SECTION 6 Figure 12 Auxiliary Power Module 1 6 Auxiliary...

Страница 17: ...In Multiples of Rating Plug Amperes Ir Ir Ir In I n Ir 3 3 Long Delay Time Setting There are eight 8 available Long Delay Time Settings as illustrated in Figure 14 ranging from 2 to 24 seconds These...

Страница 18: ...ts please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERRIDE Fixed Instantaneous for available fast acting high short circuit pro tection 3 8 Ground Fault Current Setting...

Страница 19: ...LED SEE FIGURE 11 AND INSTRUCTIONS FOR TESTING YOUR SPECIFIC CIRCUIT BREAKER LISTED IN SECTION 6 PTM OR TRIP UNIT DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING PTM AT MORE THAN 600 VOLTS VERIFY THAT NO...

Страница 20: ...o perform all of its Protection Functions with out the external control power and without the display and commu nication functions available results of the tests could be confusing When performing a s...

Страница 21: ...At least one of the various protection settings will be less than 6x In and the circuit breaker will trip the LED related to that function will light RED and the reason for TRIP code will appear in t...

Страница 22: ...ee Figure 1 The address will increase by one unit each time you press the Black DEMAND RESET push button If you press and hold the Black DEMAND RESET push button the address will increase continuously...

Страница 23: ...IBM Twisted Pair No 18 AWG See Section 5 5 Cut off Shield at last Device Do Not Ground Breaker with RMS 810 Trip Unit 3 View A Refer to circuit breaker connection diagrams referenced in Section 6 for...

Страница 24: ...he appropriate data decode and display it in a useful manner Following an over current trip operation the sequence of coded data varies slightly The cause of trip and the value and phase or ground cur...

Страница 25: ...ues Phase A Current IA kA Phase B Current IB kA Phase C Current IC kA X X X X X X X X X X X X X X X X X X 1 2 1 1 I I Ground Current IG kA Neutral Current ID kA n n n X X X I 1 2 1 1 View Power Energy...

Страница 26: ...LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE IMMEDIATE VICINITY OF THE CIRCUIT BREAKER PROVIDE PERMISSIVE CONTROL SWITCHES OR OTHER MEANS L...

Страница 27: ...32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II Circuit Breakers SC 5619 Instantaneous I SC 5620 Long Delay and Short Delay LS SC 5621 Ground G 1A33600 Connection Diagram...

Страница 28: ...he event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will initi...

Страница 29: ...ote N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message would begin to flash in the win...

Страница 30: ...30 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Страница 31: ...31 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Страница 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Отзывы: