manualshive.com logo in svg
background image

21

Instruction Leaflet 

I. L. 29-888B

Effective July 2011

 Instructions for Digitrip RMS 810 Trip Unit

 

 

eaton corporation

 www.eaton.com

4. 

When performing tests on the Ground Fault element, be 

aware that in addition to the standard protection, the 

Digitrip RMS 810 Trip Unit also has a Ground Time Memory 

function (GTM)

, which serves to protect load circuits from the 

effects of repeated (sputtering) ground arcs (see Note under 

Section 3 .9 Ground Fault Time Delay Setting) .  Because the 

GTM

 

resets quickly, it will not normally affect ground fault test results, 

but if Ground Fault tests are repeated quickly, the 

GTM

 can 

make the breaker appear to trip too soon .

otee:

N

To STOP a TEST initiated via the integral test panel PRESS AND 

RELEASE THE "TRIP RESET" PUSH-BUTTON .

4.4.1  Not Tripping the Breaker

1 .  Place the "TEST AMPS" selector switch (see Figure 20) in one of 

the six "No Trip" test settings, i .e ., 1, 2, 3, 8, or 10 x I

n

, or GF .

2 .  Press and release the (Black) "TEST" push-button - the test starts 

when the push-button is released, and the 

elapsed time will 

be displayed

 in the window .  When the timer stops, the lighted 

"RED" cause of trip LED indicates the protection function which 

operated .

3 .  Should any of the various protection settings be less than the 

selected "No Trip" test value, then the LED related to that func-

tion will turn on signifying successful completion of the test 

action .

otee:

N

During the long delay tests the Long Delay LED flashes "RED" .

4 .  Reset the Trip Unit by pressing and releasing the "TRIP RESET" 

push-button; all LEDs lighted by the "No Trip" test action should 

turn "OFF, and the display will again show the value of the cur-

rent through the breaker .  In the event that no one resets the Trip 

Unit after a test, it will wait for about three (3) hours, and then it 

will automatically revert back to its pretest status .

4.4.2  Tripping the Breaker

WARNING

CIRCUIT BREAKER OPERATING MECHANISMS OPEN AND CLOSE THE MOVING 

PARTS VERY FAST, AND WITH VERY HIGH ENERGY.  TOUCHING THE MOVING PARTS 

DURING TEST OPERATIONS CAN CAUSE INJURY.  KEEP CLOTHING, HANDS, FEET, 

AND OTHER PARTS OF YOUR BODY WELL AWAY FROM ALL MOVING PARTS DURING 

TESTING.  FOLLOW THE INSTRUCTIONS GIVEN FOR TESTING YOUR SPECIFIC TYPE 

OF CIRCUIT BREAKER, FOUND IN THE APPROPRIATE INSTRUCTION LEAFLET LISTED 

IN SECTION 6.

1 .  Make sure that the circuit breaker is carrying no current (see 

CAUTION notes under Section 4 .1) .

otee:

N

In the event it is decided to perform a "Breaker Trip Test" while load cur-

rent is flowing, make sure the circuit breaker is carrying no more than 50% of 

the Long Delay Current Setting 

I

r

 .  The Trip Unit will NOT execute your instruc-

tions to Test itself, when the load current exceeds 50% of 

I

r

 .

2 .  Place the "TEST AMPS" selector switch (see Figure 20) in either 

the "6T (or "GFT) position .

3 .  Press and release the (Black) "TEST" push-button (see Figure 

20) - the test starts when the push-button is released and the 

elapsed time is displayed in the window .

4 .  At least one of the various protection settings will be less than 

"6x I

n

", and the circuit breaker will trip, the LED related to that 

function will light "RED", and the reason for TRIP code will appear 

in the display window (see Table 3 for Code meanings) .  If the 

"STEP" push-button is pressed and released at this point, the 

"TEST current value will be shown in the display window, not the 

actual current flowing in the breaker .

5 .  Reset the Trip Unit by pressing and releasing the "Trip Reset" 

push-button (see Figure 20) .  All LEDs lighted by the "Trip" test 

action should turn "OFF, and the display window will again show 

the value of current flowing in the breaker .

4.5  Testing the Back-up Battery (Inside the Rating Plug)

The battery has no part in the protection function of the Trip Unit .
The battery is provided only to maintain the "RED" LED indication of 

the cause of TRIP in the Digitrip RMS 810 Trip Unit when external 

control power to the Power / Relay Module is not available .  The 

battery is located in the rating plug along with a battery check push-

button and a green battery check LED (see Figure 9) .

4.5.1  Back-up Battery Check

The battery is a long life, lithium photo type unit .  The status of the 

battery can be checked at any time .  Press and hold the "battery 

check push-button and observe the "Green" LED as shown in Figure 

9 .  If the battery check LED does not light "Green", replace the bat-

tery .  The condition of the battery has no effect on the protection 

function of the Trip Unit .  Even with the battery removed, the unit 

will still trip the breaker in accordance with its settings .  If however, 

control power is lost and the battery is dead, the cause of TRIP LED 

will not be lighted "RED" .

4.5.2  Replacing the Back-up Battery

The battery can be easily replaced from the front of the Trip Unit by 

lowering the hinged cover of the rating plug as shown in  

Figure 9 .  The battery can then be removed by pulling the battery 

tab as shown in Figure 9 .  After the battery is replaced (or after an 

Auxiliary Power Module is plugged into the Trip Unit), one or more of 

the cause of Trip LED'S may be illuminated .  It is necessary to press 

and release the "TRIP RESET button to turn off any of the LEDs that 

may be illuminated .  Failure to do so can cause the battery to run 

down again .  The Trip Unit will then be ready to indicate the next 

cause of trip .

otee:

N

The battery can be replaced at any time, even while the circuit breaker 

is in service, without affecting the operation of the circuit breaker or its pro-
tection function .

CAUTION

CARE SHOULD BE EXERCISED WHEN REPLACING THE BATTERY TO INSURE 

THAT THE CORRECT POLARITY IS OBSERVED.  POLARITY MARKINGS ARE 

VISIBLE ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS 

INDICATED IN FIGURE 9.  IF THE BATTERY IS INSERTED WITH INCORRECT 

POLARITY, AND IF THE 120 VAC CONTROL POWER TO THE POWER RELAY 

MODULE IS LOST, THEN, AFTER AN OVER CURRENT OR SHORT-CIRCUIT 

TRIP, NO LEDS WILL BE LIGHTED RED TO INDICATE THE REASON FOR THE 

TRIP.

The replacement battery should be the same type or equivalent .  

Acceptable 3 .0 volt lithium batteries may be obtained as type desig-

nation CR 1/3N or DL 1/3N .

Содержание Cutler-Hammer Digitrip RMS 810

Страница 1: ...persedes I L 29 888A 5 97 Instruction Leaflet I L 29 888B Instructions for Digitrip RMS 810 Trip Unit BCS Switchgear Inc Switchgear Circuit Breakers Parts Tech Support bcsswitchgear com 888 599 0486 N...

Страница 2: ...7 No Instantaneous Current Setting 18 3 8 Ground Fault Current Setting 18 3 9 Ground Fault Time Delay Setting 19 4 Test Procedures 19 4 1 General 19 4 2 When To Test 19 4 3 Testing Provisions 20 4 4...

Страница 3: ...lay Time Settings 18 Figure 17 Instantaneous Current Settings 18 Figure 18 Ground Fault Current Settings 18 Figure 19 Ground Fault Time Delay Settings 19 Figure 20 Integral Test Panel Lower Right Corn...

Страница 4: ...uit breaker The Digitrip RMS 810 Trip Unit is designed for use in industrial circuit breaker environments where the ambient temperatures can range from 20 C to 85 C 4 F to 185 F and rarely exceed 70 t...

Страница 5: ...in the LED RED and will continue to send a TRIP signal to LOCKOUT the circuit breaker until the Trip Unit is RESET The Digitrip RMS 810 Trip Unit can be RESET in two ways Either press and release the...

Страница 6: ...l control power to operate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 8...

Страница 7: ...Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1 5 3 9 Trip Unit Over Temp TRIP X...

Страница 8: ...Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 810 Type LI Figure 4 Digitrip RMS 810 Type LS Figure 5 Digitrip RMS 810 Type LSI F...

Страница 9: ...e non adjustable release is pre set at eleven 11 times the installed rating plug current In The DlScriminator is enabled for approximate ly ten 10 cycles following the initial current flow through the...

Страница 10: ...D TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECTED WITH JUMPER WIRES AS SPECIFIED ON THE CONNECTION DIAGRAMS FOR YOUR BREAKER SEE SECTION 6 SO THE TIME DELAY...

Страница 11: ...Power and Energy Values 1 2 1 2 Peak Power Demand MW Present Power Demand MW Reverse Power Flow X X X X X X X X X X X X X X X X X X Energy Consumption MWh Reverse Energy Consumption X X X X X X X X X...

Страница 12: ...will trip and the instantaneous override LED will light If breaker is open it will not close 1 3 ROM ERROR Nonfatal memory error Protection functions still operate but may be up to 12 out of tolerance...

Страница 13: ...breaker positive flow of power If the power flows in the opposite direction i e bottom to top the value of power will not be displayed continuously Instead the power value in the display window will a...

Страница 14: ...ttings without having to remove the circuit breaker from its enclosure For example if one expects a circuit to carry 600 A initially but then increase to 1400 A in the future one could initially insta...

Страница 15: ...IP RELAY ALARMS MAY BE ERRATIC OR NONFUNCTIONAL IF WRONG VOLTAGE IS USED The relays operate when the Trip Unit detects the following condi tions as shown in Figure 2 Short Circuit Trip Alarm High Load...

Страница 16: ...TESTS ON THE CIRCUIT BREAKER SEE ALSO THE SPECIFIC DIELECTRIC TEST PROCEDURES IN THE APPLICABLE CIRCUIT BREAKER INSTRUCTION LEAFLET LISTED IN SECTION 6 Figure 12 Auxiliary Power Module 1 6 Auxiliary...

Страница 17: ...In Multiples of Rating Plug Amperes Ir Ir Ir In I n Ir 3 3 Long Delay Time Setting There are eight 8 available Long Delay Time Settings as illustrated in Figure 14 ranging from 2 to 24 seconds These...

Страница 18: ...ts please see Sections 1 1 3 DlScriminator High initial Current Release and 1 1 4 OVERRIDE Fixed Instantaneous for available fast acting high short circuit pro tection 3 8 Ground Fault Current Setting...

Страница 19: ...LED SEE FIGURE 11 AND INSTRUCTIONS FOR TESTING YOUR SPECIFIC CIRCUIT BREAKER LISTED IN SECTION 6 PTM OR TRIP UNIT DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING PTM AT MORE THAN 600 VOLTS VERIFY THAT NO...

Страница 20: ...o perform all of its Protection Functions with out the external control power and without the display and commu nication functions available results of the tests could be confusing When performing a s...

Страница 21: ...At least one of the various protection settings will be less than 6x In and the circuit breaker will trip the LED related to that function will light RED and the reason for TRIP code will appear in t...

Страница 22: ...ee Figure 1 The address will increase by one unit each time you press the Black DEMAND RESET push button If you press and hold the Black DEMAND RESET push button the address will increase continuously...

Страница 23: ...IBM Twisted Pair No 18 AWG See Section 5 5 Cut off Shield at last Device Do Not Ground Breaker with RMS 810 Trip Unit 3 View A Refer to circuit breaker connection diagrams referenced in Section 6 for...

Страница 24: ...he appropriate data decode and display it in a useful manner Following an over current trip operation the sequence of coded data varies slightly The cause of trip and the value and phase or ground cur...

Страница 25: ...ues Phase A Current IA kA Phase B Current IB kA Phase C Current IC kA X X X X X X X X X X X X X X X X X X 1 2 1 1 I I Ground Current IG kA Neutral Current ID kA n n n X X X I 1 2 1 1 View Power Energy...

Страница 26: ...LOCATION BY THE COMMUNICATIONS NETWORK CAN CAUSE PERSONAL INJURY TO MAINTENANCE PERSONNEL WORKING IN THE IMMEDIATE VICINITY OF THE CIRCUIT BREAKER PROVIDE PERMISSIVE CONTROL SWITCHES OR OTHER MEANS L...

Страница 27: ...32 870 Typical Time Current Characteristic Curves for Types DS II and DSL II Circuit Breakers SC 5619 Instantaneous I SC 5620 Long Delay and Short Delay LS SC 5621 Ground G 1A33600 Connection Diagram...

Страница 28: ...he event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will initi...

Страница 29: ...ote N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message would begin to flash in the win...

Страница 30: ...30 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Страница 31: ...31 Instruction Leaflet I L 29 888B Effective July 2011 Instructions for Digitrip RMS 810Trip Unit eaton corporation www eaton com Notes...

Страница 32: ...etween the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the contr...

Отзывы: