background image

22

Instruction Leaflet 

I. L. 29-886B

Effective August 2011

 Instructions for Digitrip RMS 610 Trip Unit

 

 

eaton corporation

 www.eaton.com

appenDiX B:  interpreting Display codes  

 

 

    after circuit Breaker trips

Given a 1600 A frame circuit breaker with an I

n

 = 1000 A rating 

plug installed.
CASE 1e:  Overload Trip Operation and High Load Condition

Long Delay Current (Pick-up) Setting = 1 .0, 

I

r

 = 1000 A

Assume a prolonged 1500 A overload condition which results in an 

automatic breaker trip operation .  The following will occur:

• 

The Long Delay Trip LED will turn "On" (see Figure 1) .

• 

The coded message "LDT will appear in the Display Window (see 

Figure 1) .

• 

The Long Delay Relay in the Power / Relay Module (see Figures 

2 and 10) will operate to close the remote Long Delay Trip Alarm 

Contact .

Operator Actionse:

1 .  Observe the mode of trip LED and coded message in the Display 

Window .

2 .  Press and release "STEP" push-button (see Figure 1) .  This will 

clear the coded cause of trip message in the Display Window .

3.  View values of phase currents in Display Window (see  

Figure 1), e.g.: 

1.50 kA.

otee:

N

The phase current shown will be that identified by the "green" LED (see 

Figure 1) that is turned "On", assume "

I

A

" .  (It may not be the faulted phase .)

4 .  Press and release the "STEP" push-button to view current values 

similar to "I

A

", "I

B

", I

G

", and "I

D

" .  Each value of phase current 

kA

 

appearing in the Display Window is the value at the time of the 

trip operation .

5. 

RECORD

 all Values of interest; note which 

"RED" LEDs

 are 

lighted 

BEFORE

 resetting the Trip Unit .

6 .  Reset the Trip Unit by pressing and releasing the "Trip Reset" 

push-button (lower right corner of Trip Unit, see Figure 1) .  All 

coded messages and/or current values in the display window and 

the cause of trip LED will turn "Off", and the Remote Alarm con-

tacts in the Power / Relay Module will be reset (open) .

NOTICE

FOLLOWING 

LDT

 TRIP OPERATIONS, IT IS ESSENTIAL THAT ANY CAUSE 

OF OVERLOAD TRIP BE CORRECTED PRIOR TO RECLOSING THE CIRCUIT 

BREAKER. SHOULD IT NOT BE CORRECTED AND THE CIRCUIT BREAKER BE 

RE-CLOSED TOO QUICKLY, THEN BECAUSE OF THE INHERENT LONG TIME 

MEMORY FUNCTION (SEE NOTE IN SECTION 3.3), THE LONG DELAY TRIP 

ELEMENT WILL OPERATE FASTER THAN THE RELATED TIME-CURRENT 

CURVE INDICATES. 

 

THE AMOUNT OF TIME REQUIRED TO CLEAR THE LTM MEMORY CIRCUIT 

IS A FUNCTION OF THE LONG DELAY TIME SETTING (SEE FIGURE 5).  THE 

LONGER THE DELAY SETTING, THE LONGER THE TIME REQUIRED TO 

RESET THE MEMORY.  TOTAL MEMORY CLEARING TIME COULD BE UP TO 

TWELVE (12) MINUTES.  THE LTM CAN BE RESET QUICKLY AS DESCRIBED 

IN SECTION 4.4 (3).

The LTM memory function, simulates the conventional thermal type 

(bi-metal) circuit breaker Trip Unit, and serves a useful function by 

allowing the load conductors to cool down after an overload condi-

tion .

7 .  After correcting the cause of the overload trip (LDT), allow for the 

LTM memory circuit to reset and reclose the circuit breaker to 

restore power to the load circuit .

otee:

N

As the current approached the overload condition, prior to the overload 

trip operation, the following Trip Unit indications would have been visible .

• 

The "HILD" message would begin to flash in the window when 

the overload condition had exceeded 0 .85 x 

I

r

 for 40 seconds 

or longer .  To clear the "HILD" message and to view the present 

magnitudes of the currents, press and release the (Black) "STEP" 

push button on the display panel .  Remember to push the "STEP" 

button several times to be sure you see values of currents in all 

phases, and ground/neutral as applicable .

• 

The "High-Load" Relay in the Power / Relay Module (see Figures 

2, 10, and Section 1 .4) would have been picked up (after a 40-sec-

ond delay), to close the remote High Load Alarm Contact .  Press 

and release the "TRIP RESET" push-button to reset the High Load 

Relay Contact .

• 

The Long Delay LED (Figure 1) begins to flash "On" and "Off" .

• 

The message "LDPU" begins to flash in the display window when 

the current value exceeds 

I

r

 .

CASE 2e:  lnstantaneous Trip Operation

lnstantaneous Current (Pick-up) Setting = 8 x I

n

 = 8000 A

Assume a 12 kA fault occurs .
Following the TRIP operation, the following will occur:

• 

The lnstantaneous Trip LED will turn "On" (see Figure 1) .

• 

The coded message "INST will appear in the Display Window (see 

Figure 1) .

• 

The Short-Circuit Relay in the Power / Relay Module (see Figures 

2, 10, and Section 1 .4) will operate to close the Remote Short-

Circuit Trip Alarm contact .

Operator Actionse:

1 .  Observe the mode of trip LED and the "INST" message in the 

Display Window .

2.  Press and release the "STEP" push-button to view current 

values "I

A

", "I

B

", "I

C

", and "I

G

" or "I

D

" in the display window.

otee:

N

The phase current value displayed will be that identified by the "green" 

LED (see Figure 1) that is turned "On" .  (But, the first value you see may not 

be for the faulted phase .) 

Each value of phase current appearing in the Display Window, is the value at 

the time the trip operation was initiated .

3. 

RECORD all Values

 of interest; note which 

"RED" LEDs

 are 

lighted 

BEFORE

 resetting the Trip Unit .

4 .  The value of one phase current in display window (see Figure 1) 

will have been the 12 .0 kA fault level .

otee:

N

Had the level of the fault current been more than 28 x 

I

n

 (or 28 kA in 

this example) when the reason for trip message would be cleared (by push-

ing the "STEP" button), instead of the numerical value of current in kA, the 

"ORNG" code is displayed to show the current level exceeded maximum 

range of current sensor accuracy .

5 .  After making sure you have a record of all pertinent information 

stored in the Trip Unit memory, reset the Trip Unit by pressing 

and releasing the "Trip Reset" push-button (lower right corner of 

the Trip Unit, see Figure 1) .  All coded messages, values of cur-

rent in the display window memory, and cause of trip LEDs will 

turn "OFF", while the Remote Alarm Contacts of the signal relay 

in the Power / Relay Module will reset (open) .

6 .  Following any corrective actions and/or inspections of the circuit 

breaker and related equipment, re-close the circuit breaker to 

restore power to the load circuit .

Содержание Cutler-Hammer Digitrip RMS 610

Страница 1: ...Effective August 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 886B Instructions for Digitrip RMS 610 Trip Unit...

Страница 2: ...Replacing the Back up Battery 20 5 References 20 5 1 Digitrip RMS Trip Assemblies 20 5 2 Type DS Low Voltage AC Power Circuit Breakers 20 5 3 Type DS II Low Voltage AC Power Circuit Breakers 20 5 4 Ty...

Страница 3: ...considered to be all inclusive or covering every application or circumstance which may arise If you have any questions or need further information or instructions please contact your local representa...

Страница 4: ...rs provide the correct input information for the protector func tions as well as tripping power whenever the circuit breaker is carrying current These signals develop analog voltages across the approp...

Страница 5: ...ate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 610 Trip Unit is availab...

Страница 6: ...1 1 Ground Fault Protection Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1...

Страница 7: ...Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 610 Type Ll Figure 4 Digitrip RMS 610 Type LS Figure 5 Digitrip RMS 610 Type LSI...

Страница 8: ...current exceeds approximately 10 of the circuit breaker frame or current sensor rating Whenever the load current falls below 10 the discriminator is rearmed The release once rearmed will remain enabl...

Страница 9: ...the other breaker F can not cause breaker M to trip caution IF ZONE INTERLOCKING IS NOT TO BE USED I E STANDARD TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECT...

Страница 10: ...Phase B Current lb kA Phase C Current lc kA X X X X X X X X X X X X X X X X X X Ground Current lg kA Neutral Current ld kA n n n X X X 1 2 1 1 Local Messages Table 3 DISC DISCriminator GNDT GrouND Tri...

Страница 11: ...mory error Protection functions still operate but may be up to 12 out of tolerance Replace trip unit at first opportunity 1 2 2 1 SDT Short Time Delay Trip Breaker tripped because phase current exceed...

Страница 12: ...still function to protect the circuit but the calibration may be degraded by a few percent The Time Current Curve tolerances may be exceed ed in some cases by as much as 12 It is not necessary to tri...

Страница 13: ...60 640 680 720 760 800 A Plug In 1600 A LDPU Ir 800 960 1120 1280 1360 1440 1520 1600 A Note N Rating plugs from Digitrip models 500 600 700 800 CANNOT be used with model 610 Trip Units The connection...

Страница 14: ...as appli cable Even without available external control power once the load cur rent through the circuit breaker exceeds approximately 20 40 if single phase of the frame current sensor rating the green...

Страница 15: ...Rating of the cir cuit breaker Instantaneous and ground current settings are defined in multiples of In To illustrate the effect of each protection curve setting simulated Time Current curves are pict...

Страница 16: ...Curve referenced in Section 5 Figure 14 Short Delay Current Settings Available Settings 12 15 20 24 I Seconds at 6 Times 6 x Long Time Delay Sec at 6 x Ir Ir 4 I r Long Delay Setting 2 4 7 10 S1 and...

Страница 17: ...0 1200 5000 1200 1200 1200 1200 1200 1200 1200 1200 Tolerances on settings are 10 of values shown Refer to Type DS Type SPB or Series C R Frame supplemental instruction leaflets given in Section 5 for...

Страница 18: ...ts of the Trip Unit and two settings GF and GFT are provided for testing the ground element Figure 19 Integral Test Panel Lower Right Corner of Trip Unit caution A SETTING OF EITHER 6T OR GFT WILL TRI...

Страница 19: ...lly affect ground fault test results but if Ground Fault tests are repeated quickly the GTM can make the breaker appear to trip too soon Note N To STOP a TEST initiated via the integral test panel PRE...

Страница 20: ...F THE 120 VAC CONTROL POWER TO THE POWER RELAY MODULE IS LOST THEN AFTER AN OVER CURRENT OR SHORT CIRCUIT TRIP NO LEDS WILL BE LIGHTED RED TO INDICATE THE REASON FOR THE TRIP The replacement battery s...

Страница 21: ...the event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will init...

Страница 22: ...power to the load circuit Note N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message wou...

Страница 23: ...23 Instruction Leaflet I L 29 886B Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Notes...

Страница 24: ...between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the con...

Отзывы: