I. L. 29-886B

Effective August 2011

 Instructions for Digitrip RMS 610 Trip Unit

 

 

eaton corporation

 www.eaton.com

4.5  Testing the Back-up Battery (Inside the Rating Plug)

The battery has no part in the protection function of the Trip Unit .
The battery is provided only to maintain the "RED" LED indication of 

the cause of TRIP in the Digitrip RMS 610 Trip Unit when external 

control power to the Power / Relay Module is not available .  The 

battery is located in the rating plug along with a battery check push-

button and a green battery check LED (see Figure 9) .

4.5.1  Back-up Battery Check

The battery is a long life, lithium photo type unit .  The status of the 

battery can be checked at any time .  Press and hold the "battery 

check push-button and observe the "Green" LED as shown in Figure 

9 .  If the battery check LED does not light "Green", replace the bat-

tery .  The condition of the battery has no effect on the protection 

function of the Trip Unit .  Even with the battery removed, the unit 

will still trip the breaker in accordance with its settings .  If however, 

control power is lost and the battery is dead, the cause of TRIP LED 

will not be lighted "RED" .

4.5.2  Replacing the Back-up Battery

The battery can be easily replaced from the front of the Trip Unit by 

lowering the hinged cover of the rating plug as shown in  

Figure 9 .  The battery can then be removed by pulling the battery 

tab as shown in Figure 9 .  After the battery is replaced (or after an 

Auxiliary Power Module is plugged into the Trip Unit), one or more of 

the cause of Trip LED'S may be illuminated .  It is necessary to press 

and release the "TRIP RESET button to turn off any of the LEDs that 

may be illuminated .  Failure to do so can cause the battery to run 

down again .  The Trip Unit will then be ready to indicate the next 

cause of trip .

otee:

N

The battery can be replaced at any time, even while the circuit breaker 

is in service, without affecting the operation of the circuit breaker or its pro-
tection function .

CAUTION

CARE SHOULD BE EXERCISED WHEN REPLACING THE BATTERY TO INSURE 

THAT THE CORRECT POLARITY IS OBSERVED.  POLARITY MARKINGS ARE 

VISIBLE ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS 

INDICATED IN FIGURE 9.  IF THE BATTERY IS INSERTED WITH INCORRECT 

POLARITY, AND IF THE 120 VAC CONTROL POWER TO THE POWER RELAY 

MODULE IS LOST, THEN, AFTER AN OVER CURRENT OR SHORT-CIRCUIT 

TRIP, NO LEDS WILL BE LIGHTED RED TO INDICATE THE REASON FOR THE 

TRIP.

The replacement battery should be the same type or equivalent .  

Acceptable 3 .0 volt lithium batteries may be obtained as type desig-

nation CR 1/3N or DL 1/3N .

5  references

5.1  Digitrip RMS Trip Assemblies

I .L . 29-885 

lnstructions for Digitrip RMS 510 Trip Unit

I .L . 29-886 

lnstructions for Digitrip RMS 610 Trip Unit

I .L . 29-888 

lnstructions for Digitrip RMS 810 Trip Unit

I .L . 29-889 

lnstructions for Digitrip RMS 910 Trip Unit

5.2  Type DS Low-Voltage AC Power Circuit Breakers

I .B . 33-790-1 

lnstructions for Low Voltage Power Circuit  

 

 

Breakers Types DS and DSL

Supplement B       Digitrip RMS 510, 610, and 910 Trip Units with 

to I .B . 32-790-1 

Types DS and DSL Low Voltage Power Circuit  

 

 

Breakers

AD 32-870 

Typical Time-Current Characteristic Curves for  

 

 

Types DS and DSL Circuit Breakers

SC-5619 

Instantaneous (I)

SC-5620 

Long Delay and Short Delay (LS)

SC-5621 

Ground (G)

508B508  

Connection Diagram for Type DS Circuit Breakers

5.3  Type DS II Low-Voltage AC Power Circuit Breakers

I .B . 694C694 

lnstructions for Low Voltage Power Circuit  

 

 

Breakers Types DS II and DSL II .

Supplemental 

Digitrip RMS and Optim Trip Units with Type DS II 

I .L . 8700C39 

and DSL II Low-Voltage AC Power Circuit  

 

 

Breakers

AD 32-870 

Typical Time-Current Characteristic Curves for   

 

 

Types DS II and DSL II Circuit Breakers

 

SC-5619 

Instantaneous (I)

 

SC-5620 

Long Delay and Short Delay (LS)

 

SC-5621 

Ground

IA33600   

Connection Diagram for Type DS II Circuit  

 

 

Breakers

5.4  Type SPB Systems Pow-R Breakers

I .L . 29-801 

lnstruction for the Systems Pow-R Breaker and  

 

 

Drawout Mechanism

I .L . 29-849 

Supplementary lnstructions for the Systems  

 

 

Pow-R Breaker used with the Digitrip RMS Trip  

 

 

Units

AD 29-863 

Typical Time-Current Characteristic Curves for 

 

 

 Type SPB Systems Pow-R Breaker

SC-5623 

lnstantaneous (I)

SC-5624 

Long Delay and Short Delay (LS)

SC-5625 

Ground (G)

I .S . 15545 

SPB Master Connection Diagram

5.5  Series C

®

 R-Frame Molded Case Circuit Breakers

29C106   

Frame Book

29C107   

Frame Instruction Leaflet

29C713   

Supplementary Instructions for Series C

®

 

 

 

R-Frame used with the Digitrip RMS Trip Units

AD 29-167R 

Typical Time-Current Characteristic Curves for  

 

 

R-Frame Circuit Breakers

SC-5626 

Instantaneous (I)

SC-5627 

Long Delay and Short Delay (LS)

SC-5628 

Ground (G)

I .L . 29C714 

Master Connection Diagram for Series C

®

 

 

 

R-Frame Circuit Breakers

Содержание Cutler-Hammer Digitrip RMS 610

Страница 1: ...Effective August 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 886B Instructions for Digitrip RMS 610 Trip Unit...

Страница 2: ...Replacing the Back up Battery 20 5 References 20 5 1 Digitrip RMS Trip Assemblies 20 5 2 Type DS Low Voltage AC Power Circuit Breakers 20 5 3 Type DS II Low Voltage AC Power Circuit Breakers 20 5 4 Ty...

Страница 3: ...considered to be all inclusive or covering every application or circumstance which may arise If you have any questions or need further information or instructions please contact your local representa...

Страница 4: ...rs provide the correct input information for the protector func tions as well as tripping power whenever the circuit breaker is carrying current These signals develop analog voltages across the approp...

Страница 5: ...ate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 610 Trip Unit is availab...

Страница 6: ...1 1 Ground Fault Protection Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1...

Страница 7: ...Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 610 Type Ll Figure 4 Digitrip RMS 610 Type LS Figure 5 Digitrip RMS 610 Type LSI...

Страница 8: ...current exceeds approximately 10 of the circuit breaker frame or current sensor rating Whenever the load current falls below 10 the discriminator is rearmed The release once rearmed will remain enabl...

Страница 9: ...the other breaker F can not cause breaker M to trip caution IF ZONE INTERLOCKING IS NOT TO BE USED I E STANDARD TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECT...

Страница 10: ...Phase B Current lb kA Phase C Current lc kA X X X X X X X X X X X X X X X X X X Ground Current lg kA Neutral Current ld kA n n n X X X 1 2 1 1 Local Messages Table 3 DISC DISCriminator GNDT GrouND Tri...

Страница 11: ...mory error Protection functions still operate but may be up to 12 out of tolerance Replace trip unit at first opportunity 1 2 2 1 SDT Short Time Delay Trip Breaker tripped because phase current exceed...

Страница 12: ...still function to protect the circuit but the calibration may be degraded by a few percent The Time Current Curve tolerances may be exceed ed in some cases by as much as 12 It is not necessary to tri...

Страница 13: ...60 640 680 720 760 800 A Plug In 1600 A LDPU Ir 800 960 1120 1280 1360 1440 1520 1600 A Note N Rating plugs from Digitrip models 500 600 700 800 CANNOT be used with model 610 Trip Units The connection...

Страница 14: ...as appli cable Even without available external control power once the load cur rent through the circuit breaker exceeds approximately 20 40 if single phase of the frame current sensor rating the green...

Страница 15: ...Rating of the cir cuit breaker Instantaneous and ground current settings are defined in multiples of In To illustrate the effect of each protection curve setting simulated Time Current curves are pict...

Страница 16: ...Curve referenced in Section 5 Figure 14 Short Delay Current Settings Available Settings 12 15 20 24 I Seconds at 6 Times 6 x Long Time Delay Sec at 6 x Ir Ir 4 I r Long Delay Setting 2 4 7 10 S1 and...

Страница 17: ...0 1200 5000 1200 1200 1200 1200 1200 1200 1200 1200 Tolerances on settings are 10 of values shown Refer to Type DS Type SPB or Series C R Frame supplemental instruction leaflets given in Section 5 for...

Страница 18: ...ts of the Trip Unit and two settings GF and GFT are provided for testing the ground element Figure 19 Integral Test Panel Lower Right Corner of Trip Unit caution A SETTING OF EITHER 6T OR GFT WILL TRI...

Страница 19: ...lly affect ground fault test results but if Ground Fault tests are repeated quickly the GTM can make the breaker appear to trip too soon Note N To STOP a TEST initiated via the integral test panel PRE...

Страница 20: ...F THE 120 VAC CONTROL POWER TO THE POWER RELAY MODULE IS LOST THEN AFTER AN OVER CURRENT OR SHORT CIRCUIT TRIP NO LEDS WILL BE LIGHTED RED TO INDICATE THE REASON FOR THE TRIP The replacement battery s...

Страница 21: ...the event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will init...

Страница 22: ...power to the load circuit Note N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message wou...

Страница 23: ...23 Instruction Leaflet I L 29 886B Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Notes...

Страница 24: ...between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the con...

Отзывы: