Eaton Cutler-Hammer Digitrip RMS 610 Скачать руководство пользователя страница 18

18

Instruction Leaflet 

I. L. 29-886B

Effective August 2011

 Instructions for Digitrip RMS 610 Trip Unit

 

 

eaton corporation

 www.eaton.com

4  test procedures

4.1  General

DANGER

DO NOT ATTEMPT TO INSTALL, TEST OR PERFORM MAINTENANCE ON 

EQUIPMENT WHILE IT IS ENERGIZED.  DEATH OR SEVERE PERSONAL 

INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. 

 

DE-ENERGIZE THE CIRCUIT AND DISCONNECT THE CIRCUIT BREAKER 

BEFORE PERFORMING MAINTENANCE OR TESTS. 

 

REFER TO THE APPLICABLE CIRCUIT BREAKER INSTRUCTION LEAFLET 

SUPPLEMENT (LISTED IN SECTION 5) FOR COMPLETE INSTRUCTIONS.

CAUTION

TESTING A CIRCUIT BREAKER UNDER "TRIP CONDITIONS" WHILE IT IS IN 

SERVICE AND CARRYING LOAD CURRENT, WHETHER DONE BY LOCALLY OR 

BY REMOTE MEANS, IS NOT RECOMMENDED.

 

ANY TRIPPING OPERATION WILL CAUSE DISRUPTION OF SERVICE 

AND POSSIBLE PERSONAL INJURY RESULTING FROM UNNECESSARY 

SWITCHING OF CONNECTED EQUIPMENT. 

 

TESTING OF A CIRCUIT BREAKER THAT RESULTS IN THE TRIPPING OF THE 

CIRCUIT BREAKER SHOULD BE DONE ONLY WITH THE CIRCUIT BREAKER 

IN THE "TEST" OR "DISCONNECTED" CELL POSITIONS OR WHILE THE 

CIRCUIT BREAKER IS ON A TEST BENCH.

4.2  When To Test

Tests can be conducted with the breaker in the "connected" cell posi-

tion while carrying load current .  However, as stated in the caution 

note in Section 4 .1, good practice will limit circuit breaker in-service 

"trip tests", where required, to maintenance periods during times of 

minimum load conditions .  Testing is accomplished with the breaker 

out of its cell or in the "Test", "Disconnected", or "Withdrawn" (or 

Removed) cell positions .

otee:

N

Since time-current settings are based on desired system coordination 

and protection schemes, the protection settings selected and preset in accor-

dance with Section 3 should not be altered during or as a part of any routine 

test sequence .

4.3  Testing Provisions

As illustrated in Figures 1 and 19, an integral test panel is provided 

to test the Digitrip RMS 610 Trip Unit .
While the Integral Test Panel does enable one to check the perfor-

mance of many parts of the trip system, including:

• 

Microprocessor Functions;

• 

Trip Release;

• 

Trip Settings;

• 

LEDs;

• 

Display Panel;

• 

Zone Interlocking Function;

• 

Power Relay Module; and

• 

Rating Plug .

There are some parts it cannot check, for example:

• 

Current Sensors;

• 

Auxiliary Current Transformers;

• 

Bridge Circuits;

• 

Calibration Resistors;

• 

Analog Override Circuit;

 

and the functions of these elements are best verified by primary cur-

rent injection testing .
As indicated in Figure 19, Note 1, six different "Test Amps" settings 

(1, 2, 3, 6T, 8 and 10 x I

n

) are available for testing the phase ele-

ments of the Trip Unit, and two settings (GF and GFT) are provided 

for testing the ground element .

Figure 19. Integral Test Panel (Lower Right Corner of Trip Unit).

CAUTION

A SETTING OF EITHER 6T OR GFT WILL TRIP THE CIRCUIT BREAKER (SEE 

SECTIONS 4.1 AND 4.4.2.). 

 

FOR ANY COMBINATION OF THE PHASE PROTECTION SETTINGS, AN 

APPROPRIATE "NO TRIP" CONDITION CAN BE SET TO TEST THE LONG 

TIME, SHORT TIME, AND INSTANTANEOUS TRIP SETTINGS WITHOUT 

TRIPPING THE CIRCUIT BREAKER (SEE SECTION 4.4.1). 

 

IN THE "GF" TEST POSITION, THE LEVEL OF TEST CURRENT, BASED ON I

    

IS ADEQUATE TO DEMONSTRATE THE OPERATING CONDITION OF THE TRIP 

UNIT WITHOUT TRIPPING THE CIRCUIT BREAKER.  THIS IS A FUNCTIONAL 

CHECK ONLY, NOT A CALIBRATION.

4.4  Conducting Tests

To preserve the primary protection function of the Trip Unit, all in-ser-

vice testing whether under "Trip" or "No-Trip" conditions is executed 

ONLY if load current values are no greater than 50% x 

I

r

 

(

I

r

 = the 

Long Delay Current Setting) .  

Any attempt to conduct in-service 

testing when the load current exceeds 50% of 

I

r

, will NOT be 

executed by the Trip Unit.

Since the Digitrip RMS 610 Trip Unit is designed to run with control 

power from the Power / Relay Module for the display window, all 

testing should be conducted with the control power available, either 

through the Power Relay Module or, when the breaker is outside the 

enclosure, through the Auxiliary Power Module (APM) (see Section 

1 .5 and Figure 11) .  Although the Trip Unit is designed to perform all 

of its Protection Functions without the external control power, and 

without the display results of the tests could be confusing .  When 

performing a single-phase primary current injection test, for exam-

ple, especially when the single-phase current is low, without the 

APM it may appear as if the Trip Unit does not respond until the cur-

rent is well-above the set value, leading the tester to believe there is 

an error in the Trip Unit when there is none .  The reason this occurs 

is that the single-phase test current is not a good simulation of the 

normal three-phase circuit .  If three-phase current had been flowing, 

the Trip Unit would actually have performed correctly .  Use the APM 

for correct Trip Unit performance whenever single-phase current 

injection tests are made .

Available "Test Amps" Settings

Breaker Trips

at 6T and GFT

“6T” = Phase Current Test at 

and

TRIPS breaker;

Test Amps

"1, 2,

3, 8 or 10"

x

Phase

Current Test

NO

breaker

TRIP;

"GFT"

=

Ground Current Test

and

TRIPS breaker;

"GF"

=

Ground Current Test

Test

NO breaker

TRIP.

See Section

4.4.2 for inser-

Trip

vice test trip limitations.

Reset

Push, then release

button to reset Trip Unit.

Unit

Status

Required following all automatic

trip and test operations.

Push, then release

button to test. Test operation

begins with release of

pushbutton

6xI

n

I

n

n

Содержание Cutler-Hammer Digitrip RMS 610

Страница 1: ...Effective August 2011 Supersedes I L 29 889A 5 97 Instruction Leaflet I L 29 886B Instructions for Digitrip RMS 610 Trip Unit...

Страница 2: ...Replacing the Back up Battery 20 5 References 20 5 1 Digitrip RMS Trip Assemblies 20 5 2 Type DS Low Voltage AC Power Circuit Breakers 20 5 3 Type DS II Low Voltage AC Power Circuit Breakers 20 5 4 Ty...

Страница 3: ...considered to be all inclusive or covering every application or circumstance which may arise If you have any questions or need further information or instructions please contact your local representa...

Страница 4: ...rs provide the correct input information for the protector func tions as well as tripping power whenever the circuit breaker is carrying current These signals develop analog voltages across the approp...

Страница 5: ...ate its protection systems It operates from current signal levels and control power derived through current sensors inte grally mounted in the circuit breaker The Digitrip RMS 610 Trip Unit is availab...

Страница 6: ...1 1 Ground Fault Protection Adj Current Setting Pick up Adj Time Delay Setting Opt I Squared T Curve Shape Opt Zone Interlocking Ground Fault Time Memory X X X X X X X X X X X X X X X 3 8 3 9 3 9 1 1...

Страница 7: ...Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Figure 3 Digitrip RMS 610 Type Ll Figure 4 Digitrip RMS 610 Type LS Figure 5 Digitrip RMS 610 Type LSI...

Страница 8: ...current exceeds approximately 10 of the circuit breaker frame or current sensor rating Whenever the load current falls below 10 the discriminator is rearmed The release once rearmed will remain enabl...

Страница 9: ...the other breaker F can not cause breaker M to trip caution IF ZONE INTERLOCKING IS NOT TO BE USED I E STANDARD TIME DELAY COORDINATION ONLY IS INTENDED THE ZONE INTERLOCKING TERMINALS MUST BE CONNECT...

Страница 10: ...Phase B Current lb kA Phase C Current lc kA X X X X X X X X X X X X X X X X X X Ground Current lg kA Neutral Current ld kA n n n X X X 1 2 1 1 Local Messages Table 3 DISC DISCriminator GNDT GrouND Tri...

Страница 11: ...mory error Protection functions still operate but may be up to 12 out of tolerance Replace trip unit at first opportunity 1 2 2 1 SDT Short Time Delay Trip Breaker tripped because phase current exceed...

Страница 12: ...still function to protect the circuit but the calibration may be degraded by a few percent The Time Current Curve tolerances may be exceed ed in some cases by as much as 12 It is not necessary to tri...

Страница 13: ...60 640 680 720 760 800 A Plug In 1600 A LDPU Ir 800 960 1120 1280 1360 1440 1520 1600 A Note N Rating plugs from Digitrip models 500 600 700 800 CANNOT be used with model 610 Trip Units The connection...

Страница 14: ...as appli cable Even without available external control power once the load cur rent through the circuit breaker exceeds approximately 20 40 if single phase of the frame current sensor rating the green...

Страница 15: ...Rating of the cir cuit breaker Instantaneous and ground current settings are defined in multiples of In To illustrate the effect of each protection curve setting simulated Time Current curves are pict...

Страница 16: ...Curve referenced in Section 5 Figure 14 Short Delay Current Settings Available Settings 12 15 20 24 I Seconds at 6 Times 6 x Long Time Delay Sec at 6 x Ir Ir 4 I r Long Delay Setting 2 4 7 10 S1 and...

Страница 17: ...0 1200 5000 1200 1200 1200 1200 1200 1200 1200 1200 Tolerances on settings are 10 of values shown Refer to Type DS Type SPB or Series C R Frame supplemental instruction leaflets given in Section 5 for...

Страница 18: ...ts of the Trip Unit and two settings GF and GFT are provided for testing the ground element Figure 19 Integral Test Panel Lower Right Corner of Trip Unit caution A SETTING OF EITHER 6T OR GFT WILL TRI...

Страница 19: ...lly affect ground fault test results but if Ground Fault tests are repeated quickly the GTM can make the breaker appear to trip too soon Note N To STOP a TEST initiated via the integral test panel PRE...

Страница 20: ...F THE 120 VAC CONTROL POWER TO THE POWER RELAY MODULE IS LOST THEN AFTER AN OVER CURRENT OR SHORT CIRCUIT TRIP NO LEDS WILL BE LIGHTED RED TO INDICATE THE REASON FOR THE TRIP The replacement battery s...

Страница 21: ...the event that the feeder breaker Z2 would not clear the fault the main breaker Z1 will clear the fault in 0 5 s as above Fault 1 There are no interlocking signals The main breaker trip unit will init...

Страница 22: ...power to the load circuit Note N As the current approached the overload condition prior to the overload trip operation the following Trip Unit indications would have been visible The HILD message wou...

Страница 23: ...23 Instruction Leaflet I L 29 886B Effective August 2011 Instructions for Digitrip RMS 610Trip Unit eaton corporation www eaton com Notes...

Страница 24: ...between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipment is the con...

Отзывы: